Model MCX-32
Model MCX-32 Instruction Manual
Rev. 2.3
Page 47 of 49
Bit 7
Not Used
Bit 8
Not Used
Bit 9
Not Used
Bit 10
Not Used
Bit 11
Not Used
Bit 12
Not Used
Bit 13
Not Used
Bit 14
Not Used
Bit 15
Not Used
Bit 16
Not Used
Notes:
1)
Registers 40001~40128 are read only registers. Use Modbus
™
Function Code 3 only
2)
Register 40129 will accept Modbus
™
Function 03 or 06 only
3)
The decimal point specifies the divisor for reading registers.
Example:
Assuming the channel is 01 (40001-40002):
40001=150, 40002=01. User should divide the value in register 40001 by 10 (150/10=15.0).
11.3 Spare Parts
Part Number
Spare Parts
360-DLP120-024
120Watt 24VDC Din-rail Mounted Power Supply
320-228120-300
3Amp Din-rail mounted Circuit Breaker
320-228861-105
5Amp Din-rail Mounted Circuit Breaker
500-005133-000
MC Series Interface PCA
995-0G306M-100
Graphic LCD Display, Programmed (must be programmed at Detcon)
995-0G3RS0-000
RS-232 / RS-485 option card (installed in Main MCX-32 Display)
976-041400-000
DA-4 I/O Module
975-041402-000
DI-4 I/O Module
975-041400-000
RL-4 Relay Module
975-041401-000
AO-4 4-20mA Output Module