Det-Tronics X3300 Instructions Manual Download Page 6

Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals.  If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.

The detector is factory sealed.  While conduit seals are
not required for compliance with explosion-proof
installation requirements, steps must be taken to
prevent water ingress into the junction box area.  Units
with M25 threads must use an IP66 washer.

MOUNTING AND WIRING PROCEDURE

IMPORTANT

If installing an X3300 in place of an existing
detector, be sure to move the “A” Lead (detector
power) at the controller from the +290 VDC
source to the +24 VDC source.  Do not apply
290 VDC to the X3300.

Refer to the procedure below and the listed figures to
mount and wire the X3300.

Figure 1 –

Detector Orientation Relative to Horizon

Figure 2 –

Front View of the X3300 Detector

Figure 3A/B – X3300 Mounting Options
Figure 4A/B – Mounting Bracket Dimensions
Figure 5A/B – X3300 Wiring Identification

Figure 6 –

A Typical System, X3300 Detectors Wired
to R7404 Controller

Figure 7 –

A Typical System, X3300 Detectors Wired
to R7404 Star Logic Controller

Figure 8 –

A Typical System, X3300 Detectors Wired
to R7494 Controller

Figure 9 –

A Typical System, X3300 Detectors Wired
to R7495 Controller

Figure 10 –

A Typical System, X3300 Detectors Wired
to R7405 Controller

oi 

PLATE ORIENTATION

Refer to Figure 2 and insure that the 

oi 

plate will be

oriented as shown when the X3300 is mounted and
sighted.  This will ensure proper operation of the 

oi

system and will also minimize the accumulation of
moisture and contaminants between the 

oi 

plate and

the viewing windows.  The 

oi 

plate includes an arrow,

which should be pointed in the up direction, indicating
that the 

oi 

plate and detector are correctly oriented.

IMPORTANT

The 

oi 

plate must be securely tightened to ensure

proper operation of the 

oi 

system (40 oz./inches

recommended).

INSTALLATION PROCEDURE

1.

Install the mounting bracket assembly on the wall.
The installation surface should be free of vibration
and suitable to receive 1/4 inch (M6) screws with a
length of at least 1 inch (25 mm).  

2.

Attach the detector to the mounting bracket and
tighten the nut to secure it in place.  Refer to
Figures 3A, 3B, 4A and 4B.

4

A1926

DETECTOR STATUS INDICATOR

oi 

PLATE

oi 

PLATE KNOB

oi 

ARROW 

(MUST BE ORIENTED WITH ARROW POINTING UP)

VIEWING WINDOW (3)

Figure 2—Front View of the X3300 Detector

Summary of Contents for X3300

Page 1: ...Protect ir Multispectrum IR Flame Detector with Pulse Output X3300 Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829...

Page 2: ...d to R7404 Star Logic Controller 8 Figure 8 A Typical System X3300 Detectors Wired to R7494 Controller 9 Figure 9 A Typical System X3300 Detectors Wired to R7495 Controller 10 Figure 10 A Typical Syst...

Page 3: ...c sensitive devices ATTENTION The X3300 includes the Automatic Optical Integrity oi feature a calibrated performance test that is automatically performed once per minute to verify complete detector op...

Page 4: ...recommended since the material being welded may be contaminated with organic substances paint oil etc that will burn and possibly trigger the X3300 Artificial Lighting The X3300 should not be located...

Page 5: ...driver leads from each detector should be shielded from the B and D leads of all other detectors in order to prevent false alarms resulting from crosstalk between zones It is recommended that the A a...

Page 6: ...d to R7404 Controller Figure 7 A Typical System X3300 Detectors Wired to R7404 Star Logic Controller Figure 8 A Typical System X3300 Detectors Wired to R7494 Controller Figure 9 A Typical System X3300...

Page 7: ...N 3 4 INCH NUT USED TO SECURE DETECTOR TO SWIVEL MOUNT DETECTOR SCREWS ONTO SWIVEL MOUNT HERE B1467 2 1 2 64 DIA 3X 0 25 6 4 3X 120 2 2 0 50 8 DIA Figure 4A Q9001L Swivel Mount Dimensions in Inches mm...

Page 8: ...d to power minus at the controller end Refer to Figures 6 through 10 4 Check all field wiring to be sure that the proper connections have been made IMPORTANT Do not test any wiring connected to the de...

Page 9: ...TA BUS 4 DATA BUS 5 DATA BUS 6 DATA BUS 7 CHASSIS EARTH GND J1 7 J1 15 J1 5 J1 13 J1 6 J1 14 J1 8 J1 16 J1 9 J1 17 J1 10 J1 18 J1 11 J1 19 J2 R7404 CONTROLLER J1 10 TO 38 VDC RED BLACK WHITE GREEN X33...

Page 10: ...USED NOT USED DATA STROBE IN NOT USED NOT USED 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUTPUT 1 ZONE OUTPUT 2 ZONE OUTPUT 3 ZONE OUTPUT 4...

Page 11: ...S OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT NOT USED NOT USED DATA STROBE IN NOT USED NOT USED 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUT...

Page 12: ...CK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 6 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 7 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 8 RED BLACK WHITE GREEN R7...

Page 13: ...EN X3300 DETECTOR 6 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 7 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 8 RED BLACK WHITE GREEN R7405 CONTROLLER J1 J2 A2015 NOTE IF...

Page 14: ...e problem zone to verify detector and wiring operation COUNT TEST MODE The detector can be tested using the Count Test mode When in the Count Test mode the frequency of the digital pulses from the det...

Page 15: ...flamepaths WARNING The detector contains no user serviceable components and should never be opened To maintain maximum sensitivity the viewing windows of the X3300 must be kept relatively clean Refer...

Page 16: ...etector housing CSA FM and CENELEC Certified Models available with CENELEC Certified EEx d e Class A wiring per NFPA 72 5 year warranty SPECIFICATIONS OPERATING VOLTAGE 24 volts dc nominal 18 vdc mini...

Page 17: ...and entries M25 Conduit connection 3 4 inch NPT or M25 SHIPPING WEIGHT Approximate Standard Model Aluminum 2 4 pounds 1 1 kilograms Stainless Steel 4 8 pounds 2 2 kilograms Integral Junction Box Model...

Page 18: ...30 ft 20 ft 10 ft 70 ft 60 ft Figure 12F Horizontal Field of View at Indicated Distance in Feet for Gasoline at Medium Sensitivity 0 15 15 30 45 30 45 50 ft 40 ft 30 ft 20 ft 10 ft 70 ft 60 ft Figure...

Page 19: ...ndition to maintain explosion proof rating CE Conforms to all relevant European norms NOTE Operational performance verified from 40 C to 75 C WARRANTY PERIOD 5 years sensor and electronics DEVICE REPA...

Page 20: ...junction box and allows detector sighting REPLACEMENT PARTS Part Number Description 001680 001 Window cleaner squeeze bottle package of six bottles 006967 001 oi plate kit 005003 001 Silicone free gr...

Page 21: ...40 F to 167 F 40 C to 75 C Automatic Fire Alarm Signaling Performance verified per FM 3260 RESPONSE CHARACTERISTICS Fuel Size Distance Average Response Time feet seconds Gasoline 1 x 1 foot 100 6 0 Ga...

Page 22: ...n Axis 0 Off Axis 45 Heptane 36 Sq In 40 4 5 10 6 5 3 11 4 0 023 Sq M 12 OPTICAL FAULT The detector generated an optical fault in the presence of contamination on any single or combination of lens sur...

Page 23: ...0 1 x 1 foot gasoline 100 4 2 Two 34 w fluorescent lamps modulated 3 1 x 1 foot gasoline 100 1 7 Very High Sensitivity False Alarm Source Distance Fire Source Distance Average Response Time feet feet...

Page 24: ...electric radiant heater 3 No alarm No alarm Two 34 w fluorescent lamps 3 No alarm No alarm Very High Sensitivity False Alarm Source Distance Modulated Response Unmodulated Response feet Sunlight dire...

Page 25: ...45 8 2 Paper 0 5 lb 45 9 8 30 6 0 Corrugated 18 x 36 80 45 15 6 45 14 7 Panel 45 12 2 30 10 6 Very High Sensitivity Outdoor test condition 10 second flame pre burn from ignition Fuel Size Distance Hor...

Page 26: ...20 20 30 45 30 45 150 135 120 75 60 45 30 15 105 90 40 40 10 10 Figure A3 Horizontal Field of View at Indicated Distance in Feet for Methanol at Very High Sensitivity 0 20 20 30 45 30 45 50 40 30 20 1...

Page 27: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Reviews: