![Det-Tronics X3300 Instructions Manual Download Page 6](http://html1.mh-extra.com/html/det-tronics/x3300/x3300_instructions-manual_2487468006.webp)
Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
The detector is factory sealed. While conduit seals are
not required for compliance with explosion-proof
installation requirements, steps must be taken to
prevent water ingress into the junction box area. Units
with M25 threads must use an IP66 washer.
MOUNTING AND WIRING PROCEDURE
IMPORTANT
If installing an X3300 in place of an existing
detector, be sure to move the “A” Lead (detector
power) at the controller from the +290 VDC
source to the +24 VDC source. Do not apply
290 VDC to the X3300.
Refer to the procedure below and the listed figures to
mount and wire the X3300.
Figure 1 –
Detector Orientation Relative to Horizon
Figure 2 –
Front View of the X3300 Detector
Figure 3A/B – X3300 Mounting Options
Figure 4A/B – Mounting Bracket Dimensions
Figure 5A/B – X3300 Wiring Identification
Figure 6 –
A Typical System, X3300 Detectors Wired
to R7404 Controller
Figure 7 –
A Typical System, X3300 Detectors Wired
to R7404 Star Logic Controller
Figure 8 –
A Typical System, X3300 Detectors Wired
to R7494 Controller
Figure 9 –
A Typical System, X3300 Detectors Wired
to R7495 Controller
Figure 10 –
A Typical System, X3300 Detectors Wired
to R7405 Controller
oi
PLATE ORIENTATION
Refer to Figure 2 and insure that the
oi
plate will be
oriented as shown when the X3300 is mounted and
sighted. This will ensure proper operation of the
oi
system and will also minimize the accumulation of
moisture and contaminants between the
oi
plate and
the viewing windows. The
oi
plate includes an arrow,
which should be pointed in the up direction, indicating
that the
oi
plate and detector are correctly oriented.
IMPORTANT
The
oi
plate must be securely tightened to ensure
proper operation of the
oi
system (40 oz./inches
recommended).
INSTALLATION PROCEDURE
1.
Install the mounting bracket assembly on the wall.
The installation surface should be free of vibration
and suitable to receive 1/4 inch (M6) screws with a
length of at least 1 inch (25 mm).
2.
Attach the detector to the mounting bracket and
tighten the nut to secure it in place. Refer to
Figures 3A, 3B, 4A and 4B.
4
A1926
DETECTOR STATUS INDICATOR
oi
PLATE
oi
PLATE KNOB
oi
ARROW
(MUST BE ORIENTED WITH ARROW POINTING UP)
VIEWING WINDOW (3)
Figure 2—Front View of the X3300 Detector