SAFETY PRECAUTIONS

Exposure to ultraviolet radiation from the W867
Test Lamp can be damaging to the eyes.  Do not
look directly into the window of the test lamp
when it is on.

OPERATION

To operate the W867 Test Lamp, push the “ON” button
(see Figure 2) and aim the test lamp at the detector.
The UV and IR emitting lamp inside the W867 will flash
on and off at a rate of approximately 2 times per
second.  This flashing operation satisfies the “flicker”
circuit in the IR detector.  Response of the detection
system will depend upon the distance between the
W867 and the detector, and upon the sensitivity
programmed into the detection system.  It may be
necessary to decrease the distance between the
detector and the test lamp in order to obtain a
response.  

Do not operate the test lamp longer than is necessary
to actuate the detector.  Each detector can be checked
with less than 30 seconds of operating time.  It is
important to avoid discharging the battery to the point
where the battery charge level Indicating LED (see
Figure 2) is on steady.  Refer to the Batter y
Maintenance section of these instructions for further
information.

CAUTION

Do not remove the shock insulators from the lens
cap or battery storage compartment.

SYSTEM CHECKOUT

A system checkout should be per for med after
installation is complete.  A periodic maintenance
checkout (with minimum frequency of once every six
months) should be scheduled to ensure that the system
is in proper operating condition.  Depending on the
degree of hazard and the amount of contaminants in
the atmosphere, the checkout can be scheduled more
often.  Note that oil films will significantly reduce the
transmission of ultraviolet radiation through the detector
windows.

For specific system checkout instructions, see the
“Checkout Procedure” section of the instruction manual
for the flame detection system being used.

The W867 Test Lamp is a safe, portable UV/IR source
for external testing and verification of the response of
Det-Tronics UV, single frequency IR, and UV/IR
detectors.  It is suitable for use in hazardous
(classified) areas, but is not a substitute for an actual
open flame test.

A1713

4.25

(10.8)

7.38

(18.7)

10.38 (26.4)

7.00

(17.8)

10.625 (27.0)

3.75

(9.5)

TOP VIEW

SIDE VIEW

Figure 1—W867 Test Lamp Dimensions in Inches (CM)

A1714

WINDOWED PLUG

ON PUSHBUTTON

HANDLE

INDICATING LED

CHARGER CABLE CONNECTION

Figure 2—Top View of W867 Test Lamp

2

Summary of Contents for W867

Page 1: ... E F and G For storage and use in dry or damp locations only ELECTRICAL RATINGS Battery Charger Input Voltage 120 volts ac 60 Hz 220 volts ac 50 Hz optional TEMPERATURE RANGE Operating 5 F to 122 F 15 C to 50 C Charge 32 F to 104 F 0 C to 40 C Storage 5 F to 104 F 15 C to 40 C OPERATING TIME Approximately 15 minutes continuous between recharges This will vary with the ambient temperature OUTPUT Br...

Page 2: ...structions for further information CAUTION Do not remove the shock insulators from the lens cap or battery storage compartment SYSTEM CHECKOUT A system checkout should be performed after installation is complete A periodic maintenance checkout with minimum frequency of once every six months should be scheduled to ensure that the system is in proper operating condition Depending on the degree of ha...

Page 3: ...ction Plug the charger cable plug into the battery Plug the battery charger into the appropriate ac outlet The Power On and Fast Charge LEDs on the battery charger should be on When the battery is fully charged the Fast Charge LED will go out This should take from 12 to 14 hours from a discharged state To return the W867 Test Lamp to service unplug the battery charger from the ac outlet Disconnect...

Page 4: ...E G I STERED F I R M R E G I S TERED F I R M Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 Operator 952 941 5665 or 800 765 FIRE Customer Service 952 946 6491 Fax 952 829 8750 www detronics com E mail detronics detronics com ...

Reviews: