Det-Tronics SmokeWatch U5015 Instructions Manual Download Page 6

95-8723

4

3.5

NOTE

The output of the 0 to 20 mA current loop 
is monitored by the fault detection circuitry 
of the U5015. Therefore, an open circuit on 
the loop will cause the fault relay to change 
state.

An alarm will normally override a fault, unless 

the nature of the fault impairs the ability of 

the detector to generate or maintain an alarm 

output (i.e., loss of operating power).

INTEGRAL WIRING COMPARTMENT

All external wiring to the device is connected 

within the integral junction box.  The detector is 

furnished with a maximum of four conduit entries, 

with either 3/4 inch NPT or M25 threads. 

LED

An LED, located on the detector (see Figure 1), 

indicates normal operation and notifies personnel 

of an alarm.  Table 2 indicates the condition of the 

LED for each status.

LATCHING

A detector configured for latching operation will 

remain in an alarm state indefinitely, after an 

alarm occurs.

NON-LATCHING

A detector configured for non-latching operation 

will check the alarm status of the detector once 

every 10 seconds. Once smoke falls below the 

alarm threshold, the alarm annunciation will clear 

within 10 seconds. 

IMPORTANT

The latching or non-latching configuration 
must be specified during order placement.
It is 

not

 field configurable.

Only the alarm annunciation can be 
configured for latching operation.

CONTINUOUS SELF-TEST

During normal operation, the detector performs 

the Self-Test function automatically in the 

background once per second. During the test, 

detection is not interrupted and no indication is 

given if the test passed. If the test fails, a critical 

fault will occur. If degradation is present and 

approaching critical levels, an advisory fault will 

occur.   

MANUAL SELF-TEST

The Manual Self-Test function will immediately 

check the smoke chamber optics for degradation. 

Once initiated, there will be a one second delay 

before the result of the check is active. If there is 

a failure, the LED will shut off immediately after 

the one second test and a critical fault will occur. 

If the test passes, an alarm will be annunciated 

while the LED remains active. 

For a latching detector, the alarm will continue 

until power is cycled to the unit. For a non-latching 

detector the alarm will clear after 10 seconds. If 

the test passes, but there is degradation present 

and approaching critical levels, an advisory fault 

will occur. 

Magnetic Switch

The magnetic switch is used to initiate the Manual 

Self-Test (see Figure 3). Apply the magnet to the 

exterior housing and the LED will light to indicate 

that the magnet is detected. The LED will remain 

lit for at least one second during the test. After 

the initial delay, the test status will be indicated as 

described in the "Manual Self-Test" section. 

Table 2—Detector Status Indicator

Detector Status

LED Indicator

Power On /

Normal Operation

Steady Off

1 blink on every 4 seconds

Alarm

Steady On

Figure 3—Location of Magnetic Switch

Summary of Contents for SmokeWatch U5015

Page 1: ...3 5 95 8723 Instructions Det Tronics SmokeWatch Explosion Proof Smoke Detector U5015 ...

Page 2: ...Locations 5 Protection Against Moisture Damage 6 Power Supply Requirements 6 Transport Cover 6 Mounting Location Options 6 Mount the Detector 7 Wiring Cable Requirements 7 Jumper 7 Wiring Procedure 8 MAINTENANCE 9 Routine Inspection 9 DEVICE REPAIR AND RETURN 13 ORDERING INFORMATION 13 Spare Parts 13 Accessories 13 U5015 Model Matrix 13 APPENDIX A FM APPROVAL DESCRIPTION 14 APPENDIX B CSA APPROVAL...

Page 3: ...fe and allows live maintenance while under power without de classifying the hazardous area The integrated junction box is available in a variety of port configurations for simplified wiring and installation See Figure 1 for all the U5015 Smoke Detector components FEATURES FM Approved for use in Class I Division 1 hazardous locations FM Approved for smoke detection performance IECEx Zone approved T...

Page 4: ...30 Vdc The auxiliary relay has normally open normally closed contacts and normally de energized operation TEMPERATURE RANGE Operating 20 C to 65 C 4 F to 149 F Storage 55 C to 70 C 67 F to 158 F HUMIDITY RANGE 5 to 95 relative humidity INGRESS PROTECTION IP44 Note Applicable to ceiling mount only CURRENT OUTPUT 0 20 mA 0 3 mA dc current with maximum loop resistance of 300 ohms from 12 17 9 Vdc 500...

Page 5: ...n contacts and normally energized operation The auxiliary relay has a single set of terminals and normally open normally closed contacts and normally de energized operation IMPORTANT The auxiliary relay functions as pre alarm 0 to 20 mA Output The U5015 provides a 0 to 20 mA dc current for transmitting detector status information to other devices The circuit is wired in a non isolated configuratio...

Page 6: ...mal operation the detector performs the Self Test function automatically in the background once per second During the test detection is not interrupted and no indication is given if the test passed If the test fails a critical fault will occur If degradation is present and approaching critical levels an advisory fault will occur MANUAL SELF TEST The Manual Self Test function will immediately check...

Page 7: ...resent INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each plug or fitting be wrench tightened to an appropriate installation torque and meet the minimum thread engagement requirements per the applicable local standards codes and practices in order to retain the defined ratings PTFE sealant or equivalent should be used on NPT threads NOTE De...

Page 8: ...ower supply with adequate capability for the calculated load Ensure that the selected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float type battery charging system is recommended If an existing source of power is being used verify that system requirements are met TRANSPORT COVER The Transport Cover see Figure 4...

Page 9: ... are rated at 20 C greater than the maximum ambient temperature NOTE In applications where the wiring is installed in conduit dedicated conduit is recommended Avoid low frequency high voltage and non signaling conductors to prevent nuisance EMI problems JUMPER Depending on the wiring option that is used jumpers may be required See Table 3 for the Jumper Usage Guide and Figures 12 to 15 for wiring ...

Page 10: ... to the appropriate terminals Figure 9 shows the wiring terminals Figure 10 shows the ground lug locations Figures 12 and 13 show wiring for single detector configurations Figures 14 and 15 show wiring for multiple detector configurations 4 Re install the assembly Use the alignment guide see Figure 11 to align the retaining ring with the junction box 5 Screw the retaining ring on to the junction b...

Page 11: ... should be opened by the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke chamber should be inspected periodically when detectors are located in abnormally dirty or dusty environments to ensure the smoke chamber is not blocked by dirt or debris The smoke detector can be tested using the same methods employed for any photo electr...

Page 12: ...95 8723 10 3 5 Figure 12 Single Detector Wiring 0 20 mA used Relays not used Figure 13 Single Detector Wiring 0 20 mA not used Relays used ...

Page 13: ...11 95 8723 3 5 Figure 14 Multiple Detector Wiring 0 20 mA used Relays not used ...

Page 14: ...95 8723 12 3 5 Figure 15 Multiple Detector Wiring 0 20 mA not used Relays used ...

Page 15: ...inside the packaging Please make certain to display the RMA number clearly on the outside of your packaging Shipments received without this RMA number displayed will be refused Pack the unit properly always using sufficient packing material Wherever possible return the product using the original Det Tronics packing materials Where applicable use an antistatic bag as protection from electrostatic d...

Page 16: ...uipment protection by Flameproof Enclosures d ANSI ISA 60079 11 2014 Explosive atmospheres Part 11 Equipment protection by intrinsic safety i Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic charging hazard please see instructions for proper installation 3 All unused device openings must be closed usi...

Page 17: ... 0 General Requirements C22 2 No 60079 1 2016 Explosive atmospheres Part 1 Equipment protection by flameproof enclosures d C22 2 No 60079 11 2014 Electrical apparatus for explosive gas atmospheres Part 11 Intrinsic Safety i Special Conditions For Safe Use X 1 Field wiring must be in accordance with CEC Part 1 Section 18 2 The enclosure must be bonded to ground according to CEC Part 1 Section 18 3 ...

Page 18: ...mospheres Equip protection by Intrinsic Safety Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic charging hazard please see instructions for proper installation 3 All unused device openings must be closed using a suitably certified plug 4 For field connections use wire rated 20 C greater than maximum a...

Page 19: ...ICATE OF CONFORMITY TO TP TC 012 2011 No TC RU C US BH02 B 00239 1Exd ia IICT4 IP44 T4 Tamb 20 C to 65 C Declaration of Conformity to TP TC 020 2011 EMC EAЭC No RU д US PA01 B 50006 RUSSIA VNIIPO CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS GOST R 53325 2012 C US цC13 B 00192 ...

Page 20: ...ice 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com Specifications subject to change without notice All trademarks are the property of their respective owners 2020 Detector Electronics Corporation All rights reserved Det Tronics manufacturing system is certified to ISO 9001 the world s most recognized quality management standard Phone 952 941 5665 Toll free 800 765 3473 Fax 952...

Reviews: