9
12.4
95-8616
+
–
24 VDC
A2502
NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE
END ONLY AND BOND THE SHIELD TO THE
ENCLOSURE.
NOTE 2 250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3 EXTERNAL HART COMMUNICATION DEVICES
CAN BE CONNECTED ACROSS THE 250 OHM
RESISTOR OR ACROSS THE GT3000.
NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
BLACK
RED
SEE NOTES 2 & 3
SEE NOTE 1
GT3000
GAS DETECTOR
SENSOR TERMINATION BOX
RED
RED
BLA
CK
BLACK
GREEN
Figure 7—GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Explosion-Proof)
+
–
24 VDC
A2530
NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE
END ONLY ONLY AND BOND THE SHIELD TO THE
ENCLOSURE.
NOTE 2 250 OHM RESISTOR REQUIRED FOR HART
MENU ACCESS.
NOTE 3 EXTERNAL HART COMMUNICATION DEVICES
CAN BE CONNECTED ACROSS THE 250 OHM
RESISTOR OR ACROSS THE GT3000.
NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
BLACK
RED
SEE NOTES 2 & 3
SEE NOTE 1
GT3000
GAS DETECTOR
SENSOR TERMINATION BOX
RED
RED
BLA
CK
BLACK
GREEN
HAZARDOUS LOCATION
NON-HAZARDOUS LOCATION
INTRINSIC
S
AFETY
B
ARRIER
Figure 8— GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Intrinsically Safe)