background image

110399-01A

For more information, visit www.desatech.com

For more information, visit www.desatech.com

6

40,000

33,000

73,000

DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION

Determining if You Have a Confined or
Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining

rooms with doorless passageways or ventilation grills between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ___________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling

height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.

2.

Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example:

 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum

Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Gas fireplace logs

_____________ Btu/Hr

Other gas appliances*  + _____________ Btu/Hr

Total                             = _____________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws com-
bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

_____________ Btu/Hr

Vent-free heater

+ _____________ Btu/Hr

Total

= _____________ Btu/Hr

4.

Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

AIR FOR COMBUSTION AND
VENTILATION

Continued

 WARNING: If the area in which the heater may be

operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight
construction, provide adequate combustion and ven-
tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec-
tion 5.3 or applicable local codes.

The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:

A.

Rework worksheet, adding the space of an adjoining room. If the ex-
tra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See Ventilation Air From
Inside Building
, page 7.

B.

Vent room directly to the outdoors. See Ventilation Air From Out-
doors
, page 7.

C.

Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support,
the space is an unconfined space. You will need no additional fresh air ventilation.

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow for Heater Location

Summary of Contents for FLAME-MAX FLAME-MAX Golden

Page 1: ...asonry or UL127 factory built fireplace or in an approved ventless firebox It is design certified for these installations in accor dance with ANSI Z21 11 2 Exception Do not install this appliance in a...

Page 2: ...ck and carbon monoxide poisoning WARNING Anychangetothisheateroritscontrols can be dangerous WARNING Do not use a blower insert heat exchanger insert or other accessory not approved for use with this...

Page 3: ...ow the instructions in Clean ing and Maintenance page 24 8 Before using furniture polish wax carpet cleaner or similar products turn heater off If heated the vapors from these prod ucts may create a w...

Page 4: ...you bought heater UNPACKING CAUTION Do not remove the data plates from the grate assembly The data plates contain important warranty and safety information OPTIONAL REMOTE CONTROL ACCESSORIES There a...

Page 5: ...as been added on openable win dows and doors and c caulking or sealants are applied to areas such as joints around window and door frames between sole plates and floors between wall ceiling joints bet...

Page 6: ...ir from the outdoors and vents to the outdoors Example Gas water heater _____________ Btu Hr Vent free heater _____________ Btu Hr Total _____________ Btu Hr 4 Compare the maximum Btu Hr the space can...

Page 7: ...ntilation grills or ducts You must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors or spaces open to the outdoor...

Page 8: ...ater in a bedroom or bathroom unless installed as a vented appliance see page 11 Remote Ready and Variable Manually Controlled Models Only in a recreational vehicle where curtains furniture clothing o...

Page 9: ...erial Clearances If Not Using Mantel Note If using a mantel proceed to If Using Mantel If not using a mantel follow the information on this page You must have noncombustible material s above the firep...

Page 10: ...in Figure 6 are not met you must have a hood When using a hood there are still certain minimum mantel clearances required Follow minimum clearances shown in Figure 7 when using hood NOTICE Surface tem...

Page 11: ...the fireplace floor to allow access to heater control panel This will insure adequate air flow and guard against sooting and controls being damaged Raise fire place floor with noncombustible material...

Page 12: ...ut moving heater base 7 Mark screw locations through one hole on each side of the mounting bracket see Figures 13 14 or 15 depending on your model If installing in a brick bottom fireplace mark screw...

Page 13: ...pe Internally tinnedcoppertubingmaybeusedincertain areas Check your local codes Use pipe of 1 2 diam eter or greater to allow proper gas volume to heater If pipe is too small undue loss of volume will...

Page 14: ...propane LPsupplyandheater See guidelines under Connecting to Gas Supply page 13 Pressure Testing gas Supply Piping system Test Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its a...

Page 15: ...e grate and over front posts on chassis see Figure 22 page 15 2 Place rear log on rear of chassis see Figure 22 page 15 Slide log forward so that it sits against rear posts on chassis MPORTANT Make su...

Page 16: ...View Figure 24 Installing Golden Oak One Piece Log Set Log 2 Chassis Rear Post Middle Section at Bottom of Log Set Five Piece Log Set Chassis Burner U shaped Cutout in Chassis Log Set Burner Ports Gol...

Page 17: ...chassis see Figure 28 Log will hug the burner see Figure 29 4 Place right top log 4 over logs 1 2 and 3 as shown in Figure 29 Top log will sit down into indentions in these logs 5 Place left top log...

Page 18: ...efer to operate their heater with the chimney damper closed This will put all the heat into the room However there may be times you will desire the full flames of the HI heat setting but will find the...

Page 19: ...ou must open the vents before operating heater Youmustoperatethisheaterwithafireplacescreen in place Make sure fireplace screen is closed before running heater NOTICE During initial operation of new h...

Page 20: ...s Selecting higher settings produces greater heat output This results in increased heating comfort WARNING Do not operate heater between PILOT and HI positions CAUTION Do not try to adjust heating lev...

Page 21: ...ly to release some of the heat WARNING Damper handle will be hot if heater has been running Figure 34 Control Knob and Ignitor Button Location Shown as Supplied No Control Options OPERATING HEATER Con...

Page 22: ...sehold depending upon the amount of space to be heated the output of the central heating system etc For wall thermostat operation follow instruction supplied with thermostat accessory GWMT1 For wall s...

Page 23: ...ton un til OFF lights The pilot will remain lit IMPORTANT To turn the pilot off manually turn the con trol knob on the heater to the OFF position Figure 38 Thermostat Hand Held Remote Control Unit Sel...

Page 24: ...ures 41 and 42 3 Blow air through the ports slots and holes in the burner 4 Check the injector holder located at the end of the burner tube again Remove any large particles of dust dirt lint or pet ha...

Page 25: ...t con trol valve 7 Thermocouple damaged 8 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding pie...

Page 26: ...warm up for a minute 2 Operate burners until air is removed from line Have gas line checked by local natu ral or propane LP gas company 3 Observe minimum installation clearances see pages 8 through 1...

Page 27: ...h air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Ga...

Page 28: ...metal fireplace see Figure 47 for location If your fire place has glass doors position sensing bulb directly behind door gap on right bottom side see Figure 48 4 The mounting clip must be a minimum of...

Page 29: ...lly Controlled Thermostat Controlled Thermostat Controlled Btu Variable 20 000 39 000 20 000 33 000 21 500 36 000 Type Gas Propane LP Only Natural Propane LP Only Natural Propane LP Only Natural Ignit...

Page 30: ...nly original replacement parts This will protect your warranty coverage for parts replaced under warranty PARTS UNDER WARRANTY Contact authorized dealers of this product If they can t supply original...

Page 31: ...ostat and the log heater will automatically cycle from pilot to the heat setting selected WALL MOUNT ON OFF SWITCH GWMS2 Not Shown For all Remote Ready Models Allows the gas log heater to be turned on...

Page 32: ...ED FLAME MAX VINTAGE OAK LOG MODELS VYS18PA H18P VYS18NA H18N VYS24PA H24P VYS24NA AND H24N ILLUSTRATED PARTS BREAKDOWN Variable Manually Controlled Flame Max Vintage Oak Log Models VYS18PA H18P VYS18...

Page 33: ...01 102966 01 Upper Bracket 1 8 098867 10 098867 14 098867 10 098867 14 Gas Regulator 1 9 102780 03 102780 01 102780 03 102780 01 Outlet Burner Tube 1 10 102798 01 102798 01 102798 01 102798 01 Inlet...

Page 34: ...2 1 1 1 2 1 3 Note The Golden Oak Log 107027 01 for the VYD36PA model differs slightly from drawing 20 ODS Pilot Propane LP ILLUSTRATED PARTS BREAKDOWN VARIABLE MANUALLY CONTROLLED FLAME MAX GOLDEN O...

Page 35: ...102843 01 Burner Clip 1 13 102980 01 102772 01 102772 01 102772 01 Burner 1 14 102568 08 102568 06 102568 06 102568 06 Control Valve 1 15 098508 01 098508 01 098508 01 098508 01 Valve Retainer Nut 1 1...

Page 36: ...OAK LOG MODELS VYD18NA VYD24NA VYD30NA and VYD36NA ILLUSTRATED PARTS BREAKDOWN Variable Manually Controlled Flame Max Golden Oak Log Models VYD18NA VYD24NA VYD30NA and VYD36NA 5 21 11 12 13 1 5 1 4 2...

Page 37: ...7 102966 02 102966 01 102966 01 102966 01 Upper Bracket 1 8 098867 14 098867 14 098867 14 098867 14 Gas Regulator 1 9 102798 01 102798 01 102798 01 102798 01 Inlet Tube 1 10 102779 03 102779 01 10277...

Page 38: ...STAT CONTROLLED FLAME MAX GOLDEN OAK LOG MODELS VYD18PTA VYD18NTA VYD24PTA VYD24NTA VYD30PTA and VYD30NTA ILLUSTRATED PARTS BREAKDOWN Thermostat Controlled Flame Max Golden Oak Log Models VYD18PTA VYD...

Page 39: ...3 03 102983 02 102983 02 102983 01 102983 02 102983 01 Outlet Burner Tube 1 10 099056 19 099056 26 099056 17 099056 16 099056 17 099056 16 Burner Orifice Injector 1 11 102843 01 102843 01 102843 01 10...

Page 40: ...A HD30PR VYD36PRA and HD36PR ILLUSTRATED PARTS BREAKDOWN Remote Ready Flame Max Golden Oak Log Models VYD18PRA HD18PR VYD24PRA HD24PR VYD30PRA HD30PR VYD36PRA and HD36PR 5 14 14 15 23 14 9 19 8 7 10 2...

Page 41: ...9056 17 099056 17 Burner Orifice Injector 1 9 102966 01 102966 01 102966 01 Upper Bracket 1 10 102980 01 102772 01 102772 01 102772 01 Burner 1 11 099387 13 099387 09 099387 09 099387 09 Pilot Tube 1...

Page 42: ...VYD36PNA and HD36NR ILLUSTRATED PARTS BREAKDOWN Remote Ready Flame Max Golden Oak Log Models VYD18NRA HD18NR VYD24PNA HD24NR VYD30NRA HD30NR VYD36PNA and HD36NR 5 14 14 15 22 14 9 19 8 7 10 2 1 5 1 4...

Page 43: ...per Bracket 1 10 102980 01 102772 01 102772 01 102772 01 Burner 1 11 099387 15 099387 12 099387 12 099387 12 Pilot Tube Valve to regulator 1 12 103781 01 103781 01 103781 01 103781 01 Gas Control Valv...

Page 44: ...______________________________________________________ _______________________________________________________________________________________________ _________________________________________________...

Page 45: ...Completed College Completed Graduate School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35 0...

Page 46: ...110399 01A For more information visit www desatech com For more information visit www desatech com 46 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TM TAPE TAPE...

Page 47: ...________________________________________________________ _______________________________________________________________________________________________ _______________________________________________...

Page 48: ...ry replacement parts voids this warranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply...

Reviews: