10

107297

INFRARED PROPANE/LP GAS HEATER

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

Test
Gauge
Connection *

Sediment
Trap

Tee Joint

Pipe Nipple

Cap

Equipment
Shutoff
Valve *

3/8" NPT
Pipe Nipple

Heater
Cabinet

Figure 15 - Gas Connection

*  A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional CSA/AGA design-certified
equipment shutoff valve from your dealer. See Accessories, page 19.

3" Minimum

Ground Joint
Union

Pressure
Regulator

Regulator
Bracket

Inlet Pipe From
External Regulator
(11" W.C. to 14"
W.C. Pressure)

CONNECTING TO GAS
SUPPLY

 WARNING: A qualified service

person must connect heater to
gas supply. Follow all local codes.

Typical Inlet Pipe Diameters

FB-3B/FBS-3C

3/8" or greater

FB-5B/FBS-5C

1/2" or greater

Installation must include equipment shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
heater (see Figure 15).

IMPORTANT:

 Install an equipment shutoff

valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.

Install sediment trap in supply line as shown
in Figure 15. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

IMPORTANT:

  Hold pressure regulator

with wrench when connecting it to gas pip-
ing and/or fittings.

 CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure to between 11 and 14
inches of water. If you do not reduce incom-
ing gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
14. Pointing the vent down protects it from
freezing rain or sleet.

 CAUTION: Never connect

heater directly to the propane/
LP supply. This heater requires
an external regulator (not sup-
plied). Install the external regu-
lator between the heater and
propane/LP supply.

 CAUTION: Use only new, black

iron or steel pipe. Internally-tinned
copper tubing may be used in
certain areas. Check your local
codes. Use pipe of large enough
diameter to allow proper gas vol-
ume to heater. If pipe is too small,
undue loss of pressure will occur.

INSTALLATION

Continued

Figure 14 - External Regulator with Vent
Pointing Down

Propane/LP
Supply
Tank

Vent Pointing Down

External Regulator

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

 WARNING: This appliance re-

quires a 3/8" NPT (National Pipe
Thread) inlet connection to the
pressure regulator.

Summary of Contents for FBS-3B

Page 1: ...ed by a qualified installer service agency or the gas supplier Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING This is an unvented gas fired heater It uses air o...

Page 2: ...ir ven tilation to run properly This heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Fresh Air for Combus tion a...

Page 3: ...safety shutoff system The ODS pilot is a required feature for vent free room heaters The ODS pilot shuts off the heater if there is not enough fresh air PIEZO IGNITION SYSTEM This heater has a piezo i...

Page 4: ...rating of one perm 6 x 10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to...

Page 5: ...Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu...

Page 6: ...ce To Crawl Space To Attic FRESH AIR FOR COMBUSTION AND VENTILATION Continued Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 12 12 Ventilation Grills into...

Page 7: ...ing heater in rooms without enough ventilationairmaycausemildewtoformfrom too much moisture See Fresh Air for Com bustion and Ventilation pages 4 through 6 Continued CAUTION If you install the heater...

Page 8: ...WARNING Maintainminimum clearances shown in Figure 8 If you can provide greater clear ancesfromfloorandjoiningwall INSTALLING HEATER TO WALL Mounting Bracket The mounting bracket is located on back p...

Page 9: ...ocations using 9 64 drill bit 2 Place mounting bracket onto wall Line up last hole on each end of bracket with holes drilled in wall 3 Insert mounting screws through bracket and into wall studs 4 Tigh...

Page 10: ...ts This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly IMPORTANT Hold pressure regulator with wrench when connecting it...

Page 11: ...gas joints Bubbles forming show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater column 3 and page 12 for non thermo stat models pages 13 and 14 for ther mostat models Check the...

Page 12: ...qualified service person or supplier for repairs 6 Release downward pressure on con trol knob and turn clockwise to OFF position 7 Press in control knob and turn back to PILOT IGN This will cause the...

Page 13: ...OFF ON PILOT IGN 1 7 3 5 4 6 2 Figure 23 Burner Patterns Temperature Control Setting Knob Knob FBS 3C FBS 5C ON OFF 3 Pushincontrolknobslightlyandturn clockwise to the OFF posi tion Be sure that the...

Page 14: ...Turn Off Gas to Ap pliance page 12 for non thermostat mod els or page 13 for thermostat models see Troubleshooting pages 15 through 17 Figure 25 Incorrect Pilot Flame Pattern GRH OV 009 GOOD PILOT Fi...

Page 15: ...ally clogged ODS pilot 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if pinched by any metal or tubing Keep i...

Page 16: ...r replace burner orifice s 2 Replace burner 3 Replace gas regulator 1 Replace burner 2 Contact local propane LP gas company 3 Turn control knob until it locks at de sired setting 1 Problem will stop a...

Page 17: ...OBLEM Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Moisture condensationnoticedonwindows REMEDY 1 V...

Page 18: ...n KY 42103 3414 270 846 1199 1 800 654 8534 Fax 1 800 846 0090 franktalk aol com Master Parts Dist 1251 Mound Ave NW Grand Rapids MI 49504 2672 616 791 0505 1 800 446 1446 Fax 616 791 8270 www nbmc co...

Page 19: ...omthe address listed on the back page of this manual Send a check for 5 00 payable to DESA International SERVICE HINTS When Gas Pressure is Too Low pilot will not stay lit burner s will have delayed i...

Page 20: ...97 INFRARED PROPANE LP GAS HEATER 26 19 25 25 24 7 2 7 1 20 21 22 23 3 4 See Detail ILLUSTRATED PARTS BREAKDOWN FB 3B Burner Assembly 11 10 6 16 7 9 14 7 13 12 8 17 15 5 4 18 18 18 5 1 5 2 ODS Pilot A...

Page 21: ...98411 01 Ignitor Line 1 10 L98028 01 Control Valve Bracket 1 11 L98054 01 Control Valve Fixed Nut 1 12 L98059 01 Control Valve Main Inlet Nut 1 13 L98115 02 Main Inlet Tube Assembly 1 14 L98123 02 ODS...

Page 22: ...HEATER ILLUSTRATED PARTS BREAKDOWN FB 5B Burner Assembly 31 24 30 30 29 7 2 4 See Detail 7 1 25 26 27 28 3 11 10 4 6 7 5 9 7 21 19 23 22 22 22 22 22 20 18 13 14 12 8 14 16 23 15 17 TO B1 TO B2 TO C1...

Page 23: ...1 12 L98059 01 Control Valve Main Inlet Nut 1 13 L98115 01 Main Inlet Tube Assembly 1 14 L98123 01 ODS Gas Line Assembly 1 15 L98116 01 Burner Gas Line Assembly C 1 16 L98117 01 Burner Gas Line Assem...

Page 24: ...PROPANE LP GAS HEATER ILLUSTRATED PARTS BREAKDOWN FBS 3C Burner Assembly 15 16 13 17 21 20 11 9 12 19 16 14 10 4 21 18 16 16 27 2 27 26 22 23 1 24 25 16 8 16 13 7 9 17 22 4 See Detail 3 5 6 14 1 14 2...

Page 25: ...tor Bracket 1 12 L98057 01 4 Way Connector Fixed Nut 1 13 L98411 01 Ignitor Line 1 14 L98071 04 ODS Pilot 1 14 1 098514 01 Thermocouple 1 14 2 L98071 07 Ignitor Electrode 1 15 L98072 01 ODS Mounting B...

Page 26: ...USTRATED PARTS BREAKDOWN FBS 5B Burner Assembly 12 11 4 15 16 14 13 16 24 22 26 23 19 26 25 25 25 25 25 20 17 10 18 21 9 TO B1 TO B2 TO C1 TO C2 16 16 32 2 32 31 27 28 1 29 30 16 8 16 13 7 9 17 27 4 S...

Page 27: ...Assembly 1 14 1 098514 01 Thermocouple 1 14 2 L98071 07 Ignitor Electrode 1 15 L98072 01 ODS Mounting Bracket 1 16 L98817 01 Self Tapping Screw 14 17 L98123 03 ODS Gas Line Assembly 1 18 L98116 02 Bu...

Page 28: ...shed with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of...

Reviews: