VENT-FREE NATURAL GAS COMPACT FIREPLACE

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space

: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills

between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: 

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

_______________ Btu/Hr

Gas water heater

_______________ Btu/Hr

Gas furnace

_______________ Btu/Hr

Vented gas heater

_______________ Btu/Hr

Gas fireplace logs

_______________ Btu/Hr

Other gas appliances* _______________ Btu/Hr

Total

_______________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

56,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Example:

Gas water heater

30,000

Btu/Hr

Vent-free fireplace +

26,000

Btu/Hr

Total

=

56,000

Btu/Hr

Summary of Contents for Comfort Glow CGCF26TNA

Page 1: ...or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a...

Page 2: ...all into the control area of fireplace 7 You must operate this fireplace with the fireplace screen in place Make sure fireplace screen is in place before run ning fireplace 8 This fireplace is designe...

Page 3: ...et 4 Check fireplace for any shipping damage If fireplace is damaged promptly inform dealer where you bought fireplace PRODUCT FEATURES SAFETY PILOT This fireplace has a pilot with an Oxygen Depletion...

Page 4: ...ided with blower 5 Gently place back log on burner sup port see Figure 2 The log should fit flat against top of burner support Place two 10 one inch long screws through burner support into the log and...

Page 5: ...buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the outside atmosphere ha...

Page 6: ...__ Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amou...

Page 7: ...LATION AIR Ventilation Air From Inside Building Thisfreshairwouldcomefromanadjoining unconfined space When ventilating to an adjoining unconfined space you must pro vide two permanent openings one wit...

Page 8: ...lling fireplace make sure you have the items listed below piping check local codes sealant resistant to propane LP gas manual shutoff valve test gauge connection ground joint union sediment trap tee j...

Page 9: ...mfort Glow fireplace is de signed to be used in zero clearance installa tions Wallorframingmaterialcanbeplaced directly against any exterior surface on the rear sides or top of your fireplace Actual F...

Page 10: ...houlder Screws Assembled Brass Trim Hole for 3 wood screw for attaching fireplace to wooden base Hole for 3 wood screw for attaching fireplace to mantel 5 Firmly snap brass trim kit on shoulder screws...

Page 11: ...m LP gas Purchase the optional A G A design cer tifiedmanualshutoffvalvefromyourdealer See Accessories page 22 Figure 16 Gas Connection ATTACHING WOOD BASE TO SOLID FLOOR For attaching base to solid f...

Page 12: ...to flexible gas line see Figure 18 Con nect flexible gas line to flexible gas line attached to gas regulator of fireplace see Figure 18 5 Check all gas connections for leaks See Checking Gas Connecti...

Page 13: ...ect all leaks at once WARNING Neveruseanopen flame to check for a leak Apply a mixture of liquid soap and water toalljoints Bubblesformingshow a leak Correct all leaks at once Pressure Testing Firepla...

Page 14: ...repair it call a qualified service technician or gas supplier Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call...

Page 15: ...ool When the thermo couple cools the fireplace will shut down If pilot flame pattern is incorrect as shown in Figure 24 turn fireplace off see To Turn Off Gas to Appliance see Troubleshooting pages 16...

Page 16: ...valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down control knob Repeat igniting operation until air is removed 5 Clean ODS pilot see Cl...

Page 17: ...on 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural gas company 3 Observe minimum installation cle...

Page 18: ...atement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Not enough combustion ventilation air OBSERVED PROBL...

Page 19: ...ur local natural gas supplier SERVICE HINTS CLEANING BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE The primary air inlet holes allow the proper amount of air to mix with the gas This provides a clea...

Page 20: ...GAS COMPACT FIREPLACE 17 23 29 32 8 14 36 37 13 7 8 42 33 11 4 17 10 4 7 8 8 30 3 1 2 9 19 6 22 31 21 40 41 38 39 16 15 18 24 28 5 34 26 25 20 35 1 4 35 2 12 24 12 1 25 14 8 3 27 12 1 12 2 ILLUSTRATE...

Page 21: ...1 17 097403 01 Screw Panhead 10 x 1 3 4 2 18 098303 02 Regulator Screw 2 19 104335 01CK Outer Shell Base 1 20 102649 02CJ Branch Support 1 21 099415 10 Gas Regulator 1 22 102875 01 Regulator Bracket 1...

Page 22: ...nstructions included Three sided brass trim kit included CORNER MANTEL WITH BUILT IN HEARTH BASE Unfinished Birch GMC20U Walnut Finished Birch GMC19F Forusewithfireplace Space savingmantel andhearthba...

Page 23: ...entrals are privately owned businesses They have agreed to support our customer s needs by providing original replacement parts and accessories Dayton Hardware P O Box 275 North Dayton Station Dayton...

Page 24: ...efects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective fireplace will be the responsibility of the owner T...

Reviews: