AIRFLOW
OPERATION
24
3.3.1 AIRFLOW SETTINGS
The Airflow section contains screens related to airflow control. Screens may vary based on system configuration.
STATIC PRESSURE
This numeric display and bar graph show the
system static pressure measured between the
clean side of the filter and atmosphere.
AIRFLOW CONTROLLER STATUS
This text display shows details of the current
status of the controller.
Stopped
System is stopped.
Initializing
Waiting for airflow to become stable
prior to initializing control.
Increasing Blower Speed
System is running below the minimum
set point and increases blower speed in
order to increase airflow.
a
b
c
3
4
3.3
1
3
4
8
9
10
11
12
5
6
7
2
ZERO METER
The Zero push button will zero any reading,
should it wander from zero over the lifespan of
sensor. This can only be done when the system
is not running. Additionally, the pneumatic
tubing should be disconnected from the
control panel.
SAVE, LOAD AND RESET
These buttons affect items on the displayed
screen only. The reset button must be held
until all indicators in the button turn blue,
approximately 3 seconds.
Save
Saves the settings for later use.
Load
Loads previously saved settings.
Hold To Reset
Resets settings to factory defaults.
2
a
b
c
1
Summary of Contents for AYRDYNE
Page 1: ...www ayrdyne com Installation Operation and Maintenance Manual...
Page 2: ...www ayrdyne com 2...
Page 36: ...www ayrdyne com SYSTEM OPERATION 36 1 7 4 5 6 9 2 8 3 3 6 3 6 4 METRICS...
Page 38: ...www ayrdyne com SYSTEM OPERATION 38 2 6 5 1 4 3 7 8 3 6 3 6 5 SERVICE REMINDERS...
Page 43: ...www ayrdyne com NOTES 43...