![DencoHappel MultiMAXX HD Operation Manual Download Page 38](http://html1.mh-extra.com/html/dencohappel/multimaxx-hd/multimaxx-hd_operation-manual_2480041038.webp)
Electrical Connections
Multi
MAXX
HD
39
PR-2007-0350-GB • Subject to modifications • R2-04/2016
9.6
Electrical connection with MATRIX
9.6.1 Connecting mains voltage for units with 230 V operating voltage
MATRIX
2001
3001
4004
4004+IO
9
9
9
9
Pos. 1: Input 230 V AC / 50 Hz,
Fusing by others max. B 10 A
Pos. 2: Connection to 1st unit; L1, N on fan switch
Pos. 3: Connection to 2nd unit; L1, N on fan switch
Pos. 4:
To further units
•
Connect the mains voltage in accordance with the
wiring diagram.
Fig. 9-10: Connecting mains voltage for controller/unit
PE
PE
PE
1
2
3
4
PE
N
L1
N
L1
PE
L1
N
NOTE:
Slave units can be supplied by the master unit
(see Fig. 9-10, Pos. 3 and Pos. 4). Consider the total power consumption of the
units. You may have to connect a second power supply.