Complies with BS 5446-2:2003 

 

Cautions 

 

PRODUCT LIMITATIONS:

 Caution! This device does not detect smoke, gas or flame, 

and should not be covered with a guard or similar obstructing item. 

Hazardous levels of smoke and toxic gas can build up before a heat alarm might operate. 

Where life safety is the primary requirement in the event of a fire, smoke, gas or combination 

alarms usually provide earlier warning than heat alarms alone. 
This device may not alert people who are hearing impaired. It is strongly recommended that 

the special-purpose heat alarms, using visual or vibrating alerting devices, be installed for 

these occupants. 
This device may not be effective in fires where heat is prevented from reaching the device 

(eg where intermediate doors are closed), where the fire grows so rapidly that the egress path 

is blocked (even when correctly located), and where the fire is intimate to a person (eg where a 

victim's clothes catch fire). 

SLEEPING OCCUPANTS:

 Heat alarms should not replace required smoke alarms in 

sleeping areas. 

INSTALLATION LIMITATIONS:

 This product is designed for use in a single 

residential unit, such as a family home or apartment. Heat alarms located outside the 

dwelling may not provide adequate warning to occupants. This product is not 

designed for use in non-residential buildings. Non-residential buildings require special fire 

detection and alarm systems. This product alone is not a suitable substitute for a fire detection 

system installed in places of work or where people sleep on a temporary basis, such as hotels 

or motels, dormitories, hospitals, nursing homes or group homes of any kind, even if they were 

once dwellings. Please refer to local regulations for fire detection and alarm system 

requirements. 

 

Features 

 

Numens 205 DC heat alarms provide battery powered heat detection, together 

with alarm functions within a single unit. The technology provides reliable 

performance and low maintenance. 
Numens 205 DC smoke alarms are powered by a long-life lithium-ion battery, 

and do not require a mains supply. Models are available with either 

user-replaceable batteries or non-replaceable batteries.  
Interconnectable 205 DC heat alarms use a wireless transmission path. 

Configuration into a closed group ensures that other units within radio signal 

range are not affected by a test or fire alarm occurring within the configured 

group. 
Numens 205 DC heat alarms are suitable for general residential applications 

where a smoke alarm may result in unwanted unwanted activation (such as 

cooking areas, parking garages with exhaust fumes, and areas subject to high 

levels of dust and other air-borne contaminants). The 205 DC heat alarm 

provides home owners and installers with an easy-to-install, long-life solution for 

property protection applications. 

Normal Operation 

When operating normally, a red LED adjacent to the Test/Hush button will flash 

every 40 s.  

Alarm Condition 

When heat is detected, an internal sounder will activate to alert occupants, and 

the red LED will flash every 1 s. The sounder is a loud, pulsating alarm. 

Fault Conditions 

Battery Low 

When the battery is depleted, the heat alarm will emit a short audible signal 

every 40 s, synchronized with a single flash of the red LED indicator. The 

Battery Low indication will operate for at least 30 days.  

Model 205-007 

The battery for Model 205-007 is not user-replaceable and will last up to 

10 years under normal conditions. When the Low Battery signal is given, 

replace the heat alarm without delay.  

Model 205-008 

The battery for Model 205-008 (wireless interconnection) is replaceable by the 

user and will last up to 5 years under normal conditions. When the Low Battery 

signal is given, replace the battery without delay. 

Model 205-009 

The battery for Model 205-009 is replaceable by the user and will last up to 

10 years under normal conditions. When the Low Battery signal is given, 

replace the battery without delay.  

Heat Sensor Fault  

When a fault is detected in the heat sensor, the heat alarm will emit a short 

audible signal every 40 s sounder, and a single flash of the red LED indicator 

midway between the audible indications. 

Test/Hush Button 

Test 

When in the Normal condition, pressing and holding the Test/Hush button for 

5 s will activate the heat alarm to check its operation. The alarm will sound, and 

the red LED will flash every 1 s. Releasing the Test/Hush button will cancel the 

alarm test. 
For interconnected heat alarms (Model 205-008, a test on one unit will operate 

all interconnected units. After releasing the Test/Hush button, it may take up to 

10 s for the interconnected units to silence.  

Hush (Alarm Condition) 

When in the Alarm condition, pressing the Test/Hush button reduces the 

sensitivity of the heat alarm for 9 min and silences the alarm sounder. The hush 

feature allows time for excess heat to dissipate. During the hush time, the red 

LED will continue to flash every 1 s on the unit in fire alarm, and every 6 s on 

any interconnected units.  

The hush feature should only be used after the cause of the alarm is 

known (such as an excessive heat from cooking). 

After the hush time has expired, the heat alarm will automatically return to 

normal sensitivity. If heat is still present in the unit, the alarm sounder will re-

activate. The hush feature can be used repeatedly. 

Hush (Battery Low) 

When the heat alarm signals that the battery is depleted, pressing the 

Test/Hush button silences the audible signal for 10 hours. During the hush time, 

the red LED will flash every 20 s.  

After the hush time has expired, the heat alarm will automatically return to 

normal. If the battery has not been changed (excluding Model 205-007), the low 

battery signal will re-activate. The hush feature can be used repeatedly. 
 
 

Hush (Heat Sensor Fault Condition) 

When the heat alarm signals a heat sensor fault, pressing the Test/Hush button 

silences the fault condition for 10 hours. During the hush time, the red LED will 

flash every 20 s.  
After the hush time has expired, the unit will automatically return to normal. If 

the heat sensor fault is still present, the fault signal will re-activate. The hush 

feature can be used repeatedly. 

Interconnection (Model 205-008) 

Interconnectable heat alarms (Model 205-008) use a wireless transmission path 

to connect units together.  

Individual units must first be configured into a closed Group so that 

sounders on all units in the group will activate during an Alarm condition, 

Alarm Hush, or a Test. 

When excessive heat is detected in one unit, the sounders in all interconnected 

units will activate. The LED indicator on units that have not detected heat will 

flash every 6 s. This allows the home owner to quickly locate the cause of the 

alarm. 
When a unit is tested, the sounders in all interconnected units will activate and 

the LED indicator will flash every 40 s. After releasing the Test/Hush button, it 

may take up to 10 s for the interconnected units to silence.  
The maximum transmission path between each interconnected unit is 500 m. 

There is no limit to the number of units that can be interconnected using the 

wireless interconnection function. 

WARNING

: Wireless interconnection signalling may not operate in the 

low battery condition.  

Understanding Indicator and Alarm Signals 

205 DC heat alarms produce the following indicator and alarm signals, 

depending on the status condition. 

Primary Smoke Alarm 

LED 

Audible Signal 

Status Condition 

Flash every 40 s 

 

Normal 

Flash every 1 s 

0.5 s on / 0.5 s off 

Fire alarm 

Flash every 1 s 

 

Hush after fire alarm 

Flash every 1 s 

0.5 s on / 0.5 s off

 

Test 

Flash every 40 s 

Short beep at the same 

time of LED flash 

Low battery 

Flash every 20 s 

 

Hush after low battery fault 

Flash every 40 s 

Short beep midway 

between LED flashes 

Smoke chamber fault 

Flash every 20 s 

 

Hush after smoke chamber fault 

 

Interconnected Units 

When configured as a Group, interconnected units produce the following 

additional indicator and alarm signal when the primary unit is operated. 

LED 

Audible Signal 

Status Condition 

Flash every 6 s 

 

Hush after fire alarm, activated 

from another device 

Flash every 40 s 

0.5 s on / 0.5 s off 

Test activated from another 

device 

 

 

Summary of Contents for Numens 205 Series

Page 1: ...fault is detected in the heat sensor the heat alarm will emit a short audible signal every 40 s sounder and a single flash of the red LED indicator midway between the audible indications Test Hush Button Test When in the Normal condition pressing and holding the Test Hush button for 5 s will activate the heat alarm to check its operation The alarm will sound and the red LED will flash every 1 s Re...

Page 2: ...s In an environment of between 0 50 C and 10 90 relative humidity non condensing Dusty or dirty areas Insect infested areas WARNING Hazardous levels of smoke and toxic gas can build up before a heat alarm might operate Where life safety is the primary requirement in the event of a fire smoke gas or combination alarms usually provide earlier warning than heat alarms alone For complete coverage smok...

Page 3: ...ere installed check the activation of interconnected units see above WARNING Never use a naked flame of any kind to test your heat alarm You may set fire to and damage the device as well as your home The built in Test feature accurately tests all alarm functions If the unit fails to operate correctly contact your supplier or Numens see below Annual Maintenance Vacuum or carefully clean the heat al...

Page 4: ...deltronic se 2020 09 30 2019 Ambest Electronics Ningbo Co Ltd All rights reserved All specifications and other information shown were current at the date of publication and subject to change without notice See all products at www numens com Numens 55 Yunhui Road Yunlong Town Yinzhou District Ningbo Zhejiang China 315121 Helpline 86 574 8281 7218 ...