INSTRUCTION MANUAL 

for „DELTAFAN” wall fans of the type: ***/R/*-*/**/***/Ex 

Page 11/14 

 

6.1  THE SMALL INSPECTION 

 

visual  inspection,  and  motor  and  protection  equipment  cleaning  without  disassembly,  as  long  as  the 
inspection does not necessitate it, 

 

resistance measurement of motor winding isolation, 

 

efficiency measurement of resetting or protection connection resistance, 

 

resistance measurement of power supply cable isolation, 

 

checking the correct setting of overload protection, 

 

discharge the condensate: 

o

 

pull out the rubber plug from the drain hole in both plates to discharge water and re-plug both holes. 

 

6.2  THE MAIN INSPECTION 

 

motor removal consisting in performing the below activities in the following order: 

o

 

unscrew the three screws mounting the fan cover, 

o

 

removal of the fan from the shaft using a puller, 

o

 

unscrew the three bolts holding bearing plates, 

o

 

removal  of  bearing  plates  using  special  pullers  or  by  lightly  tapping  the  protruding  plate  logs  with  a 
wooden hammer, 

o

 

removal of the rotor with bearings, 

o

 

removal of bearing from the motor shaft using three-arm pullers – only when it is necessary to replace 
them. 

 

Bearings should be absolutely replaced after 40000 motor working hours. 

Double-sidedly closed ball bearings (2Z) that do not require grease filling are used in the motor (bearings are 
factory greased by the manufacturer). 

 

Motor 

Bearing type 

63 

63 6202 2Z 

71 

71 6203 2Z 

80 

80 6204 2Z 

 

 

checking  the  stator  winding  condition,  which  should  be  carefully  cleaned  and  blown  out  with  compressed 
air;  winding  faces  cannot  have  damaged  spots,  faces  must  be  well  stiffened;  if  necessary  they  should  be 
coated with an electric isolation paint without solvent PK-155 and well dried in the temperature below 373 K 
(+ 100°C), 

 

check  the  isolation  resistance  between  particular  winding  phases  and  between  the  winding  and  motor 
housing, 

 

check the correct setting of the motor overload protection, 

 

it is forbidden to replace any motor elements and make any modification. If a repair is necessary (motor 
rewinding), it can be done by the manufacturer or a authorised company, 

 

the motor should be installed in the reverse order. 

 

Summary of Contents for 355/R/6-6/30/400/Ex

Page 1: ...ca 234B 34 114 Brze nica Phone 48 33 879 20 38 Fax 48 33 879 22 65 E mail biuro deltafan pl INSTRUCTION MANUAL for DELTAFAN wall fans R Ex type The instruction manual should be read before starting up...

Page 2: ..._____8 4 5 OPERATION ___________________________________________________________________________8 4 6 POWER SUPPLY OF FAN MOTOR ______________________________________________________________9 5 TRANSP...

Page 3: ...equences which the manufacture cannot be held responsible for The device requires the use of original parts only Damages caused by using incorrect unoriginal materials and other accessories are not su...

Page 4: ...few rotors equipped with blades uses the energy to constantly transfer a medium Therewith the value of transferred work per a mass unit does not exceed the normal value of 25 kJ kg Wall fans of the ty...

Page 5: ...powder epoxy polyester paint ALESTA EP KP E45 of the surface resistance of 2x105 106 The fan rotor is made of antistatic polyamide PAGAS die cast and reinforced with glass fibre blades and silumin al...

Page 6: ...nd are available on our regularly updated website at www deltafan pl The selection of a fan for a particular application should be carried out by a competent person so that the fan operation point in...

Page 7: ...oncerns the power on the electric motor shaft The current value is given for the star motor connection The level of acoustic pressure in the distance of 1m from the fan with spherical form of sound pr...

Page 8: ...eeding 5 of the motor rated voltage All rating is related to rated voltage If voltage variations exceed 5 of the rated voltage the motor should not be started The fan motor has protection rating of IP...

Page 9: ...nnection The installation must have correctly selected overload and short cut protection The installation must have efficient protection against electric shocks Leads of the electric installation are...

Page 10: ...pecial attention should be paid to stability and inertia of the fan in its packaging Fans and their parts should not be stored in a room with chemical substances causing metal corrosion Fans should be...

Page 11: ...a wooden hammer o removal of the rotor with bearings o removal of bearing from the motor shaft using three arm pullers only when it is necessary to replace them Bearings should be absolutely replaced...

Page 12: ...cking the electrical isolation strength high voltage tests should be performed by a trained and qualified person 7 DISPOSAL In the countries of the European Union and other European countries there ar...

Page 13: ...INSTRUCTION MANUAL for DELTAFAN wall fans of the type R Ex Page 13 14 10 RATING PLATE...

Page 14: ...irements of the following harmonized standards PN EN 60079 0 2009 PN EN 60079 7 2010 PN EN 13463 2010 PN EN 13463 5 2005 PN EN 14986 2009 PN EN ISO 12100 1 2005 PN EN ISO 12100 2 2005 A1 2009 In the p...