InfraSuite RowCool Precision Cooling –
Chilled Water
Fault events
1. Emergency stop/remote emergency
stop
8. Remote sensor failure
2YHUÀRZRIFRQGHQVHGZDWHU
9. Abnormal chilled water inlet/outlet
sensor
3. Leakage
$EQRUPDOFKLOOHGZDWHUÀRZPHWHU
4. Fire
11. Abnormal fan
5. Smoke
12. Abnormal three-way ball valve
6. Abnormal air supply/return temperature
and humidity sensor
1
3. Abnormal heater
7. Abnormal input voltage/current/branch
circuit
$EQRUPDOKXPLGL¿HU
5.6.2 Set Point
3DWK
0DLQ0HQXĺ6HWWLQJĺ6HW3RLQW
Supply Air T
Supply Air RH
:
:
24 C
50%
y
Supply Air T
In the automatic mode, the cooling unit will automatically adjust the fans and ball valve in
accordance with this targeted supply air temperature.
5.6.3 Controller Setting
3DWK
0DLQ0HQXĺ6HWWLQJĺ&RQWUROOHU
:
:
:
:
Force Mode
P Gain
I Gain
D Gain
OFF
09.00
0.550
0.000
:
:
:
:
Min Flow T
Max Flow T
Fan Step
Group Work
25 C
40 C
10
OFF