ERROR
Message
Possible cause
Action
6
Error message and Trouble Shooting
AC Freq
High
(E01)
1. Actual utility frequency is over
the OFR setting
2. Incorrect Grid Code setting
3. Detection circuit malfunction
1. Check the utility frequency
2. Check Grid Code setting
3. Contact our customer service for
technical support
AC Freq
Low
(E02)
1. Actual utility frequency is under
the UFR setting
2. Incorrect Grid Code or Grid setting
3. Detection circuit malfunction
1. Check the utility frequency
2. Check Grid Code & Grid setting
3. Contact our customer service for
technical support
Grid Quality
(E07)
Non-linear load in Grid and near
to inverter
Grid connection of inverter need to be
far away from non-linear load if necessary
AC Con.
Fail
(E08)
1. Wrong connection in AC terminal
2. Detection circuit malfunction
1. Check the AC connection in accordance
with the user manual
2. Contact our customer service for
technical support
No Grid
(E09)
1. AC breaker is OFF
2. Disconnect in AC terminal
1. Switch on AC breaker
2. Check the connection in AC terminal and
make sure it connects to inverter
AC Volt
Low
(E10, E15,
E20)
1. Actual utility voltage is under
the UVR setting
2. Incorrect Grid Code or Grid setting
3. Wrong connections in AC terminal
4. Detection circuit malfunction
1. Check the utility voltage within the suitable
range
2. Check Grid Code & Grid setting
3. Check the connection in AC terminal
4. Contact our customer service for
technical support
AC Volt
High
(E11, E13,
E16, E18,
E21, E23)
1. Actual utility voltage is over the
OVR setting
2. Utility voltage is over the Slow
OVR setting during operation
3. Incorrect Grid Code or Grid setting
4. Detection circuit malfunction
5. Wrong connection in AC terminal
1. Check the utility voltage within the suitable
range
2. Check Grid Code & Grid setting
3. Check the connection in AC terminal
4. Contact our customer service for
technical support
Solar1
High
(E30)
1. Actual Solar1 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Contact our customer service for
technical support
Solar2
High
(E31)
1. Actual Solar2 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Contact our customer service for
technical support
Insulation
(E34)
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Minus to Ground or both.
3. Detection circuit malfunction
1. Check the insulation of Solar inputs
2. Check the capacitance, dry PV panel
if necessary
3. Contact our customer service for
technical support
Table 6-1 : Error Message
80
Error message and Trouble Shooting
Summary of Contents for M88 Series
Page 2: ......
Page 29: ...Figure 3 16 AC gland assembling for M88H_122 Torque 0 8 N m to fix the screw 29 Installation ...
Page 96: ......
Page 97: ...M88H 操作手冊 三相併網型變流器 The power behind competitiveness www deltaww com English 1 97 繁體中文 ...
Page 117: ...要使用遮蔽板 請參考圖3 9的安裝方式 鎖附扭力45 kgf cm 圖3 9 遮蔽板的安裝方法 117 安裝 ...
Page 124: ...圖3 16 M88H_122交流固定頭的組裝方式 Torque 0 8 N m to fix the screw 安裝 124 ...
Page 163: ...圖5 5 AC DC SPD 損壞時的告警 圖5 6 拔起連接線並移除螺絲 AC SPD DC SPD 163 維護 ...
Page 169: ...圖5 14 拆卸功率模組風扇 僅以單側為例 組裝所需的螺釘扭矩 8 kgf cm 0 8N m 169 維護 ...
Page 170: ...圖5 15 濾網拆卸方向 圖5 15為濾網位置 170 維護 ...
Page 174: ...7 卸下8顆螺絲並用手抓住功率模組使其與配線箱分開 8 確定密封蓋有蓋上 圖5 18 拆下8顆螺絲後 將配線箱與功率模組分離 174 維護 ...
Page 191: ......
Page 192: ...Version 04201204 ...