12.
Recommissioning the inverter after
work
Before carrying out any
work on the inverter,
carry out the work steps described in the chapter
“10. Disconnecting the inverter from the power
supply before working on it”, page 93!
To complete all
work on the inverter, carry out
the work steps described in this chapter!
12.1 Safety Instructions
DANGER
Electric shock
Potentially fatal voltages are present in the
inverter during operation. When the inverter
is disconnected from all power sources, this
voltage remains in the inverter for up to 60
seconds.
You should therefore always carry out the fol-
lowing steps before working on the inverter:
1. Turn both DC disconnectores to the
OFF
position.
2. Disconnect the inverter from all AC and DC
voltage sources and make sure that none
of the connections can be restored acciden-
tally.
3. Wait at least 60 seconds for the internal
capacitors to discharge.
DANGER
Electric shock
Potentially fatal voltages are present at the DC
connections of the inverter. When light falls on
the solar modules, they immediately start to
generate electricity. This also happens when
light does not fall directly on the solar modules.
►
Never disconnect the inverter from the solar
modules when it is under load.
►
Turn both DC disconnectores to the
OFF
position.
►
Disconnect the connection to the grid so that
the inverter cannot feed energy into the grid.
►
Disconnect the inverter from all AC and DC
voltage sources. Make sure that none of the
connections can be restored accidentally.
►
Ensure that the DC cables cannot be
touched accidentally.
DANGER
Electric shock
The inverter has a high leakage current value.
►
Always
connect the ground cable first, then
the AC and DC cables.
WARNING
Electric shock
The IP65 protection degree is no longer guaran-
teed when the door is open.
►
Only open the door when absolutely
necessary.
►
Do not open the door if water or dirt might
enter the inverter.
►
After work is completed, ensure that the
door is properly shut and tightened again.
Check that the door is properly sealed.
WARNING
Heavy weight
The inverter is heavy.
►
Lift and carry the inverter with at least 2
people.
WARNING
Hot surfaces
The surface of the inverter can get very hot dur-
ing operation.
●
Always wear safety gloves when touching
the inverter.
All work described in this section must only be
carried out by electrical installers who are trained
and approved for work on grid-connected solar
inverters.