(1) Preface
Thank you for purchasing DELTA’s HMC series. This instruction sheet will be helpful in the installation, wiring and
inspection of Delta HMI. Before using the product, please read this instruction sheet to ensure correct use. You should
thoroughly understand all safety precautions before proceeding with the installation, wiring and operation. Place this
instruction sheet in a safe location for future reference. Please observe the following precautions:
Install the product in a clean and dry location free from corrosive and inflammable gases or liquids.
Ensure that all wiring instructions and recommendations are followed.
Ensure that HMI is correctly connected to a ground. The grounding method must comply with the electrical
standard of the country (Please refer to NFPA 70: National Electrical Code, 2005 Ed.).
Do not disassemble HMI, modify or remove wiring when power is applied to HMI.
Do not touch the power supply during operation. Otherwise, it may cause electric shock.
If you have any questions during operation, please contact our local distributors or Delta sales representatives.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the
most updated version at
http://www.delta.com.tw/ia
.
(2) Safety Precautions
Carefully note and observe the following safety precautions when receiving, inspecting, installing, operating, maintaining
and troubleshooting. The following words, DANGER, WARNING and STOP are used to mark safety precautions when
using the Delta’s HMI product. Failure to observe these precautions may void the warranty!
Installation
Comply with quick start for installation. Otherwise it may cause equipment damage.
Do not install the product in a location that is outside the stated specification for the HMI. Failure to
observe this caution may result in electric shock, fire, or explosion.
Do not install the product in a location where temperatures will exceed specification for the HMI.
Failure to observe this caution may result in abnormal operation or damage the product.
Please note that this equipment has obtained EMC registration for commercial use. In the event that it
has been mistakenly sold or purchased, please exchange it for equipment certified for home use.
Do not use this product as an alarm device for disaster early warning that may result in personal injury,
equipment damage, or system emergency stop.
Wiring
Connect the ground terminals to a class-3 ground (Ground resistance should not exceed 100
Ω
).
Improper grounding may result in communication error, electric shock or fire.
Operation
The users should use Delta Screen Editor software to perform editing in Delta's HMI product. To
perform editing and confirming HMI programs without using Delta Screen Editor software in Delta's
HMI product may result in abnormal operation.
To prevent the personal injury and equipment damage, when designing HMI programs, please ensure
that a communication error occurred between Delta’s HMI product and the connecting controller or
equipment will not result in system failure or malfunction.
Please be sure to backup the screen data and HMI programs in case they are lost, accidentally
deleted or worse.
Do not modify wiring during operation. Otherwise it may result in electric shock or personal injury.
Never use a hard or pointed object to hit or strike the screen as doing this may damage the screen and
let the screen has not respond at all, and then cause HMI to work abnormally.
Maintenance and Inspection
Do not touch any internal or exposed parts of the HMI as electrical shock may result.
Do not remove operation panel while power is on. Otherwise electrical shock may result.
Wait at least 10 minutes after power has been removed before touching any HMI terminals or
performing any wiring and/or inspection as an electrical charge may still remain in the HMI with
hazardous voltages even after power has been removed.
Turn the power off before changing backup battery and check system settings after finishing change.
(all data will be cleared after changing battery).
Be sure the ventilation holes are not obstructed during operation. Otherwise malfunction may result
due to bad ventilation or overheating troubles.
Wiring Method
Do not use a voltage that will exceed specification for the HMI. Failure to observe this caution may
result in electric shock or fire.
Remove the terminal block from the HMI before wiring.
Insert only one wire into one terminal on the terminal block.
If the wiring is in error, perform the wiring again with proper tools. Never use force to remove the
terminals or wires. Otherwise, it may result in malfunction or damage.
For the power line that forced to take out, ensure to check wiring again and restart.
Communication Wiring
Comply with communication wiring specification for wiring.
Wiring length should comply with the stated specification for the HMI.
Proper grounding to avoid bad communication quality.
To avoid noise and interference, the communication cable, all power cables, and motor power cable
should be placed in separate conduits.
(3) Model Explanation
HMC 08 - N 5 00 S 5 2
(1) (2)
(3)
(4)
(5)
(6)
(7)
(8)
(1)
Product Name
HMC: HMI with Controller
(2)
LCM Size
08: 8 inch TFT LCD
(3)
Type of Industries
N: General Purpose
(4)
Display specification
5: SVGA
(5) Version
(6)
Type of Model
S: Standard ( built-in)
(7)
External Control Interface (Bus)
5: DMCNET
(8)
Controller Remote Unit interface
2: Specialized High-speed RS-422
(4) Parts Names
HMC08-N500S52
(
Front View
)
A
Power LED Indicator
(
)
Lights in green when HMI works normally.
B
Operation LED Indicator
(
)
/
Alarm LED Indicator
(
)
Lights in blue: the communication is carried out /the data is
accessing. (Please refer to the “Note” below for explanation).
Lights in red: one of the alarms is on.
C
Touch Screen / Display
Note: The definition of the operation LED indicator (Blue) can be determined by the users freely.
HMC08-N500S52
(
Rear View
)
A
Power Input Terminal
G
USB Host
B
COM3 (It is provided with two LED
indicators to indicate that HMI is in
Read or Write status during the
communication process.)
H
Audio Output Interface
C
COM2 (It is provided with two LED
indicators to indicate that HMI is in
Read or Write status during the
communication process.)
I
Memory Card Slot / Battery
Cover
D
COM1
J
DMCNET
E
USB Slave
K
Remote Module Interface
F
Ethernet Interface
(
LAN
)
(5) Installation and Storage Conditions
The product should be kept in the shipping carton before installation. In order to retain the warranty coverage, the HMI
should be stored properly when it is not to be used for an extended period of time. Some storage suggestions are:
Store in a clean and dry location free from direct sunlight.
Store within an ambient temperature range of -20°C to +60°C (-4°F to 140°F).
Store within a relative humidity range of 10% to 90% and non-condensing.
Do not store the HMI in a place subjected to corrosive gases and liquids.
Correctly packaged and placed on a solid and durable surface.
Do not mount the HMI adjacent to heat-radiating elements or in direct sunlight.
Do not mount the HMI in a location subjected to corrosive gases, liquids, or airborne dust or metallic particles.
Do not mount the HMI in a location where temperatures and humidity will exceed specification.
Do not mount the HMI in a location where vibration and shock will exceed specification.
Do not mount the HMI in a location where it will be subjected to high levels of electromagnetic radiation.
(6) Installation and Wiring
Installation Notes:
Improper installation will result in malfunction and greatly reduce the life of the HMI. Be sure to follow the
guidelines in this quick start when installing the HMI.
In order to ensure the HMI being well ventilated, make sure that the ventilation holes are not obstructed and
must provide sufficient free space around HMI.
To ensure the panel is well protected, be sure to install a waterproof gasket into HMI.
For use on a flat surface of a Type 4X "Indoor Use Only" enclosure or equivalent.
The allowable thickness of the panel for mounting should be less than 5 mm.
Installation Method:
Step 1:
Ensure to put waterproof gasket into HMI and then
insert the HMI into the panel cutout.
Step 2:
Ensure to insert fasteners into the HMI’s
insertion slots and turn the screw till screws
touch panel cutout.
Step 3:
Turn the screw with less than torque 0.7N.M to
avoid damage to plastic box.
Torque: 6.17lb-inch (0.7N-M)
Step 4:
Keep at least 60mm distance from rear of HMI
product to the wall, installation surface or the
other controllers for heat dissipation.
Recommended wiring is in the table below:
Type
Wire Gauge (AWG)
Stripped length
Torque
Solid
28 ~ 12
7 ~ 8 mm
5 kg-cm
(
4.3 lb-in
)
Stranded
30 ~ 12
7 ~ 8 mm
5 kg-cm
(
4.3 lb-in
)
Be sure to perform wiring by referring to the following figure (power supply connector).
Units: mm
B
A
C
A
B
C
D
E
F
G
H
I
J
K