Delta HEX080QA Series Instruction Manual Download Page 7

HEX080QA  Heat  Exchanger  Instruction  Manual 

 

 

Page 4   

User can follow dry contact definition that is Normal Close (N.C.) to 

detect abnormal status from pin 10 & pin 11 

 

Definition 

N. C 

Connection 

Pin 10 & Pin 11 

Control board, NTC and fan are in 
normal status 

CLOSE 

NTC resistance is over range such as 
“open circuit” or “short circuit” 

OPEN 

Fan speed is lower than 50% of 
definition or fan is locked 

OPEN 

 

Dry contact max. rating : 75VDC/50mA 

 

LED indicator 

 

INNER FAN / OUTER FAN / STATUS LEDs indicate fan and NTC   

sensor status . 

Depress "TEST" button to start auto-test of outer and inner fans 

  running from low to high speed. Turn off by depressing the “TEST” button 

again . 

 

 

INNER FAN 

OUTER FAN 

STATUS 

Normal 

GREEN 

GREEN 

GREEN 

Failed* 

RED 

RED 

RED 

Normal   

(touch TEST / CLEAN) 

Blinking 

GREEN 

Blinking 

GREEN 

N/A 

Failed* 

(touch TEST / CLEAN) 

Blinking 

RED 

Blanking 

RED 

N/A 

               

   

    * FAN failed : Fan speed is lower than 50% of definition or fan is locked 

                      * STATUS Failed : NTC resistance is over range such as “open circuit” or 

                                                        “short circuit” 

Summary of Contents for HEX080QA Series

Page 1: ...ation and maintenance 22 49 Operating voltage range 40 60 Note The cooling capacity W K W C or W is defined as Q TI TA Q Heat dissipation W from inside of cabinet TI Return temperature of internal air...

Page 2: ...HEX080QA Heat Exchanger Instruction Manual...

Page 3: ...Electrical specification 3 4 1 Connection and LED indicator on HEX panel 3 4 2 Standalone control mode 5 5 Mechanical feature 6 5 1 Thermal path and Airflow baffle 6 5 2 Configuration 6 6 Maintenance...

Page 4: ...external air loop conforms to IP55 protection rating 2 2 Specification Main feature Unit Model Number HEX080QA Outline Dimension W x D x H mm in 555 x 500 x 265 22 x 20 x 11 Cooling Capacity Note 1 W...

Page 5: ...14 F 149 F Storage temperature 40 C 70 C 40 F 158 F Humidity External air circuit 0 100 RH Internal air circuit 0 90 RH Ingress protection on external side l IEC60529 IP55 NEMA 3 GR 487 720hrs salt sp...

Page 6: ...out and waterproof foam sticking 4 Electrical specification 4 1 Connection and LED indicator on HEX panel Power Connection on panel plate CVILUX 3W3CS0000100000 mate with CVILUX 3W3CP0000100000 COMM c...

Page 7: ...Dry contact max rating 75VDC 50mA LED indicator INNER FAN OUTER FAN STATUS LEDs indicate fan and NTC sensor status Depress TEST button to start auto test of outer and inner fans running from low to hi...

Page 8: ...ort Pin7 Pin8 via J8 connector on controller as shown below to change sensor location 4 2 Standalone control mode HEX can detect ambient temperature to control cooling capacity Internal fan and extern...

Page 9: ...en flow out from internal supply opening The air supply of the cold air will be used to cool down the system On the opposite side cooler air from the surrounding environment will be drawn in from the...

Page 10: ...an tray Item 2 and disconnect fan from controller Note the connection location Use brush and low pressure air to remove the dust on internal fan tray Item 2 heat exchange core opening Hold internal fa...

Page 11: ...submit spare part s below for replacement Internal fan P N AFB1548EH BJ51 External fan P N AFB1548VH CE1L Controller P N HEX080QA 000C User can then refer to maintaince sequence on previous page or r...

Page 12: ...re Use caution at all times Incorrect installation may cause damage and or injury Installation and maintenance should be performed only by qualified personnel Use caution at all times Ensure the groun...

Reviews: