HEX080PD  Heat  Exchanger  Instruction  Manual 

 

 

Page 8   

Test   

Please power on and follow LED status to check that HEX has 

resumed to normal function after maintenance . 

 

6-2. Replacement 

Delta HEX is designed with dry contact alarm output and LED   

indicator on panel shown below to describe abnormal situation . 

Refer to Section 4-1 for checking abnormal part is internal fan ,   

external fan or controller for abnormalities .   

 

                      In cases of parts abnormality , Delta will follow the reading and submit 

spare part(s) below for replacement .   

 

Internal fan P/N : TCA1748ATAMW 

External fan P/N : TCA1748ATAMV 

Controller P/N : HEX080PD-000C 

 

User can then refer to maintaince sequence on previous page , or   

request Delta authorized support for assistance . 

 

7.  MTBF and Reliability 

 

7-1. MTBF 

L10 Fan life is expected to be a minimum 80,000 hours continuous 

operation at 40°C with 15 ~ 65%RH .@ label rated vo ltage 

 

7-2. Relibability 

 

Test item 

Condition 

   

High temperature 

   

IEC 60068-2-2 

   

Low temperature 

   

IEC 60068-2-1 

   

High temp. / High humidity 

   

IEC 60068-2-14 TEST Nb 

   

Temperature cycle 

   

IEC 60068-2-3 

   

Vibration 

   

ETSI 300 019-1-4 CLASS 4.1 

   

Ingress protection 

    (External side) 

   

IEC 60529 IP55 (NEMA 3) 

    GR-487 720hrs salt spray 

   

Package bump 

   

IEC 60068-2-29 

Summary of Contents for HEX080PD Series

Page 1: ...n feature Specification Dimension H x W x D 950 x 450 x 150 37 x 18 x 6 Cooling capacity Note 80 44 Rated voltage 48 Operating current 2 2 Opearting power 106 Operating voltage range 40 60 Operating t...

Page 2: ...HEX080PD Heat Exchanger Instruction Manual...

Page 3: ...d waterproof sticking 3 4 Electrical specification 3 4 1 Connection and LED indicator on HEX panel 3 4 2 Standalone control mode 4 5 Mechanical feature 5 5 1 Thermal path and Airflow baffle 5 5 2 Conf...

Page 4: ...nd dirt The fan on the external air loop conforms to IP55 protection rating 2 2 Specification Main feature Unit Model Number HEX080PD Outline Dimension H x W x D mm in 950 x 450 x 150 37 x 18 x 6 Cool...

Page 5: ...14 F 149 F Storage temperature 40 C 70 C 40 F 158 F Humidity External air circuit 0 100 RH Internal air circuit 0 90 RH Ingress protection on external side l IEC60529 IP55 NEMA 3 GR 487 720hrs salt sp...

Page 6: ...TOLERANCE 0 5MM 0 197 View from internal side 4 Electrical specification 4 1 Connection and LED indicator on HEX panel Connection Dry contact max rating 60VDC 400mA User can select dry contact definit...

Page 7: ...over range such as open circuit or short circuit CLOSE OPEN Fan speed is lower than 50 of definition or fan is locked CLOSE OPEN LED indicator Fan NTC sensor Normal GREEN GREEN Abnormal or failed RED...

Page 8: ...o the internal return opening and pass though the HEX then flow out from internal supply opening The air supply of the cold air will be used to cool down the system On the opposite side cooler air fro...

Page 9: ...nd Replacement Be sure to SHUT DOWN the power before proceeding with any maintenance or component replacement Item Q ty Description 1 1 Chassis assy 2 2 Frame assy 3 1 Controller 4 1 Internal fan 5 1...

Page 10: ...4 heat exchange core opening Hold internal plate assy Item 7 and connect fan to controller Item 3 Re attach internal plate assy Item 7 and use screw driver to secure screw with chassis assy Item 1 Ext...

Page 11: ...elow for replacement Internal fan P N TCA1748ATAMW External fan P N TCA1748ATAMV Controller P N HEX080PD 000C User can then refer to maintaince sequence on previous page or request Delta authorized su...

Page 12: ...mes Incorrect installation may cause damage and or injury Installation and maintenance should be performed only by qualified personnel Use caution at all times Ensure the grounding wire is connected b...

Reviews: