Delta HEX080PD Series Instruction Manual Download Page 1

HEX080PD series

Dimension drawing

Features

Unit

    

 IP55 waterproof at external side

mm

(in)

    

 Standalone temperature control

W/K (W/

)

    

 RS-485 function

VDC

    

 Clear LED status indicator

A

    

 Dry contact alarm output

W

VDC

Design

°C

    

 Air to air heat exchange

dB-A

    

 Rated voltage at 48V

Kg (Lb)

    

 High efficiency and reliable fan

    

 Easy installation and maintenance

Main feature

Specification

Dimension (H x W x D)

950 x 450 x 150

(37 x 18 x 6)

Cooling capacity

*Note

80 (44)

Rated voltage

48

Operating current

2.2

Opearting power

106

Operating voltage range

40 ~ 60

Operating temperature range

-10 ~ +65

Noise (1.5 meter)

65.0

* Specifications are subject to change without notice.

Weight

19 (42)

* Note : The cooling capacity (W/K , W/°C or W/

) is defined as  Q/ (T

I

-T

A

)

              Q : Heat dissipation (W) from inside of cabinet

              T

I

 : Return temperature of internal air circuit (K , °C or 

)

              T

A

 : Ambient temperature of external air circuit (K , °C or 

)

Internal Door mount

Summary of Contents for HEX080PD Series

Page 1: ...n feature Specification Dimension H x W x D 950 x 450 x 150 37 x 18 x 6 Cooling capacity Note 80 44 Rated voltage 48 Operating current 2 2 Opearting power 106 Operating voltage range 40 60 Operating t...

Page 2: ...HEX080PD Heat Exchanger Instruction Manual...

Page 3: ...d waterproof sticking 3 4 Electrical specification 3 4 1 Connection and LED indicator on HEX panel 3 4 2 Standalone control mode 4 5 Mechanical feature 5 5 1 Thermal path and Airflow baffle 5 5 2 Conf...

Page 4: ...nd dirt The fan on the external air loop conforms to IP55 protection rating 2 2 Specification Main feature Unit Model Number HEX080PD Outline Dimension H x W x D mm in 950 x 450 x 150 37 x 18 x 6 Cool...

Page 5: ...14 F 149 F Storage temperature 40 C 70 C 40 F 158 F Humidity External air circuit 0 100 RH Internal air circuit 0 90 RH Ingress protection on external side l IEC60529 IP55 NEMA 3 GR 487 720hrs salt sp...

Page 6: ...TOLERANCE 0 5MM 0 197 View from internal side 4 Electrical specification 4 1 Connection and LED indicator on HEX panel Connection Dry contact max rating 60VDC 400mA User can select dry contact definit...

Page 7: ...over range such as open circuit or short circuit CLOSE OPEN Fan speed is lower than 50 of definition or fan is locked CLOSE OPEN LED indicator Fan NTC sensor Normal GREEN GREEN Abnormal or failed RED...

Page 8: ...o the internal return opening and pass though the HEX then flow out from internal supply opening The air supply of the cold air will be used to cool down the system On the opposite side cooler air fro...

Page 9: ...nd Replacement Be sure to SHUT DOWN the power before proceeding with any maintenance or component replacement Item Q ty Description 1 1 Chassis assy 2 2 Frame assy 3 1 Controller 4 1 Internal fan 5 1...

Page 10: ...4 heat exchange core opening Hold internal plate assy Item 7 and connect fan to controller Item 3 Re attach internal plate assy Item 7 and use screw driver to secure screw with chassis assy Item 1 Ext...

Page 11: ...elow for replacement Internal fan P N TCA1748ATAMW External fan P N TCA1748ATAMV Controller P N HEX080PD 000C User can then refer to maintaince sequence on previous page or request Delta authorized su...

Page 12: ...mes Incorrect installation may cause damage and or injury Installation and maintenance should be performed only by qualified personnel Use caution at all times Ensure the grounding wire is connected b...