Part no. :
Delta model no. : HEC2500BFE
Page 12
•
B:
LED indicator:
•
Power
When the system power on and the LED will light in green.
If any alarm happens and the LED will flash in red. Customer could
check the root cause according to alarm code.
If the system gets into self-test mode and the LED will flash in green.
•
C: Button Controller
按钮
↑: UP or increase
↓: DOWN or decrease
SET: Parametric setup
2-2. Parametric Setup
Panel item
Content
Range
Note
d1.01
Aircon Address
1~128
,
Default :21
Optional
d1.02
Baud Rate Setup
0 : 9600
1 : 19200
(Default :0)
Optional
d1.03
Comp.
Turn On
Temp.
20~50
,
Default :26
d1.04
Comp. Difference Comp.
1~10
,
Default :6
d1.05
Cabinet Over Temperature
20~80
,
Default :65
d1.06
Self-Test
0: Disable
1: Enable
(Default :0)
d1.07
Emergency Fan
SetupSetup
0: Disable
1: Enable
(Default :1)
Optional
d1.08
Alarm Default Setup
0: Normal Open
1:Normal Closed
(Default :1)
d1.09
Recovery Default Value
0: Disable
1: Enable
(Default:0)