Panel operation
•
A:
Dis
A
7-Segment Display
:
It will show the temperature inside the cabinet and system parametric setup.
•
B
:
LED indicator:
Power:
When the system power on and the LED will light in green.
If any alarm happens, according to flashing times of red led to check the root cause.
If the system gets into self-test mode and the LED will flash in green.
•
C
:
Press Buttons:
↑: UP or increase
↓: DOWN or decrease
SET: Parametric setup or into self-test function
2-2. Parametric Setup
Panel menu
Content
Range
d1.01
Communication address setting
1~128
,
(Default) 21
d1.02
Communication speed
0 : 9600
1 : 19200
(Default) : 0
d1.03
Cooling start temperature setting
temperature
20~50
,
(Default)40
d1.04
Cooling hysteresis setting
1~10
,
(Default)5
d1.05
High temperature alarm point setting
20~80
,
(Default)65
d1.06
System self-test
0: (Not self-test)
1: (self-test) (Default) : 0