Delta HEC1000PB Specification And Manual Download Page 21

Part no. :   

Delta model no. : HEC1000PB 

 
 

 

 

Page 21   

8.  Installation Notice 

Check the surrounding obstacles to make sure the product get enough space for air circulate. 

 

 

9.  Reclaim 

At the end of the unit  working  life, the  produce must not be disposed of as urban  waste. It must be 

taken to a special local authority differentiated waste collection center or to a dealer providing this service. 

10. Versions   

 

REV. 

Description 

Owner 

Date 

00 

Issue SPEC   

VIC 

2015.06.15 

01 

Modify TUV.CE.UL ICON 

REX.LYU  2020.08.13 

02 

Modify Caution. 

REX.LYU  2020.09.15 

* X 

means temporary version

   

 

* Recommended “a” keeps 1.0 
meter at least

 

Space tight causes air re0circulation. Reduce cooling 
performance potentially keeps space as wide as possible

 

Summary of Contents for HEC1000PB

Page 1: ...v Delta Model No HEC1000PB Rev 02 Sample Date Code Sample Issue Date SEP 15 2020 DELTA ELECTRONICS INC 252 SHANG YING ROAD KUEI SAN TEL 886 0 3 3591968 TAOYUAN CITY 333 TAIWAN FAX 886 0 3 3591991 Plea...

Page 2: ...nce 12 1 6 Thermal and Airflow 13 2 Electrical Specification 14 2 1 Indicator Connector 14 2 1 1 Power Supply Alarm Connector 14 2 1 2 Protection 15 3 Environmental Condition 17 3 1 Operating Temperat...

Page 3: ...Part no Delta model no HEC1000PB Page 3 9 Reclaim 21 10 Versions 21...

Page 4: ...objects on it Please pay attention to the following icons on the package If air conditioner is toppled over slanted or dropped unfortunately please follow below steps a stand for 12 hours to ensure re...

Page 5: ...ing into wall or ceiling do not damage electrical wiring or hidden utilities 8 Be sure to use only the specified accessories and parts for installation work 9 Protective earth connection The enclosure...

Page 6: ...onditioner while moving or storage 8 The hole in the bottom of the air conditioner should be connected to a sealed container through a drainpipe 9 The appliance is not to be used by persons including...

Page 7: ...n for Approval Customer Description Air conditioner for Equipment with 1000 W Rated Cooling Capacity Through Wall Mounting Customer P N Rev Delta model no HEC1000PB Rev 02 Sample revision Date Code Sa...

Page 8: ...od Dimension H x W x D without flange mm inch 700 x 500 x 200 27 7 x 19 8 x 7 9 Application Outdoor Weight Kg lbs 28 0 61 7 Mounting Method Door Side Color optional RAL7035 Environmental Protection Pe...

Page 9: ...o HEC1000PB Page 9 Power Range Input Voltage VDC 48 Max Operating DC Current A 14 3 Alarm N A Dry Contact Output Key Components Controller Built in Smart Controller Fans Delta High Efficiency Blowers...

Page 10: ...Part no Delta model no HEC1000PB Page 10 1 3 Dimension mm inch 1 Material Case SGCC Sheet 2 Finish Powder coating 75 120 uM Color RAL 7035 3 Dimensional Tolerance 1 mm...

Page 11: ...Part no Delta model no HEC1000PB Page 11 1 4 Mounting Panel Cutout Inside Outside Gasket...

Page 12: ...an clean the condenser with water directly The external side fan blade can also be cleaned with normal pressure water if there is dust accumulation Please do not use strong water jet to impact the cen...

Page 13: ...protecting cover is sealed with silicon for IP55 requirement Please do not dismantle the sealed cover or will lose the quality assurance of the compressor 1 6 Thermal and Airflow The internal and ext...

Page 14: ...3 N A N A 4 N A N A 5 N A N A Pin Description 3 Alarm 4 Alarm System alarm default setup Note Customers can setup the N O or N C by themselves when any alarm happen through display board d1 6 Dry cont...

Page 15: ...rmally and the LED will light in green If the system gets into self test mode and the LED will flash in green Fan In When the inner fan is running normally and the LED will light in green Fan Out When...

Page 16: ...PB Page 16 Allow reverse voltage 42 58 VDC Short Ckt If compressor UVW short for any both phase the compressor will not operate Compressor H T protection Tcomp 105 oC Eva L T protection TEVA 0 oC Powe...

Page 17: ...otection Rating IP55 IEC60529 on external side GR487 on external side 4 Reliability Table Test item Condition High temperature IEC 60068 2 2 Low temperature IEC 60068 2 1 High temp High humidity IEC 6...

Page 18: ...Table 7 1 System Setup Item System Parameter Default Range d1 1 System Version 2 5 N A d1 2 Alarm Logs 0 0 N A d1 3 Inside over temp Setup 60 oC 40 oC 70 oC d1 4 Auto Self Test Function Enable Enable...

Page 19: ...ection 2 2 PWB Temperature Protection 2 3 IPM Temperature Protection 2 4 Amb Temperature Protection 2 5 3 Temperature Sensor Fault Amb Temperature Sensor 3 1 Eva Temperature Sensor 3 2 Cond Temperatur...

Page 20: ...onditioner is running but the cabinet temperature is still high no obvious cooling effect 1 The air conditioner capacity is not match the load of the system 2 The ambient temperature is too high 3 Low...

Page 21: ...te It must be taken to a special local authority differentiated waste collection center or to a dealer providing this service 10 Versions REV Description Owner Date 00 Issue SPEC VIC 2015 06 15 01 Mod...