Communication Module DVPSCM12/52-SL
DVP-PLC Operation Manual
【
BACnet object
】
Network Number: The network number on the BACnet network is unique. It can not be used repeatedly.
(Default: 65536)
BACnet object edit: Editing the AV and BV values which correspond to the data registers and coils in the
Delta PLC master connecting to the SCM module
The lenghth of tha AV value corresponds to two data registers in the Delta PLC, and the lenghth of the BV
value corresponds to one coil in the Delta PLC.
Object: The user can select “AV” or “BV”. “AV” corresponds to data the registers in the PLC, and “BV”
corresponds the coil in the PLC.
SCM address: The user can set the address of the AV, or the address of the BV. The setting range is
0~383.
Length: A unit is a double word.
PLC: The start address in the Delta PLC.