background image

www.delta.com.tw/products/plc.asp

                           

 

DVP-SA

 

Compact, Multi-function, 

Multiple Commands 

PLC

 

Instruction Sheet 

 

WARNING 

  This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation & 

wiring, troubleshooting and peripherals. Other detail infromation about programming and commands is compatible 
with EP series; please see PLC Application Manual.    For more information about the optional peripherals , please 
see individual product manual. 

  This is an OPEN TYPE PLC.    The PLC should be kept in an enclosure away from airborne dust, humidity, electric 

shock risk and vibration.    Also, it is equipped with protective methods such as some special tools or keys to open 
the enclosure, so as to avoid the hazard to users and the damage to the PLC. 

  Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the PLC.   

Check all the wiring prior to power up.  To avoid any electromagnetic noise, make sure the PLC is properly 

grounded 

.

 

 

INTRODUCTION 

2.1 Model Name Explanation and Peripherals

 

Thank you for choosing DELTA’s PLC DVP series. The 
DVP-SA series has a 12-points (8 input 4 
outputs) PLC main processing unit with multiple 
commands for use. It also has an 8K Steps program 
memory to connect to every SS series expansion unit, 
including digital I/O (Maximum 112 Input / 112 Output 
expansion points), analog module, etc. for various 
applications. Its power unit is separated from the MPU 
for better space utilization and easier installation. 

 

Nameplate Explanation 

PLC Model

Input Power Supply Spec.

Output Module Spec.

Barcode and Serial Number

CPU Version

MODEL   :    DVP12SA11R

POWER INPUT       : 24DC 6W  MAX

OUTPUT MODULE : 2.0A 250Vac 50/60Hz RES. LOAD

DELTA ELECTRONICS INC.

MADE IN XXXXXX

V1.00

1 2 SA11R 0T402 00 01

 

 

Model Name 

Series Name
Points (8  4 outputs)

SA Series

R: Relay
T: Transistor

DC Power Input

 

 

Serial Number 

Production number
Production week
Production Year

 20 04

Production factory
Version type
Production model

 

 

Peripherals 

◎ 

DVPHPP02: Handheld Programming panel 

◎ 

WPLSoft: Windows Ladder Logic Programming Software 

◎ 

DVPACAB115: 1.5M Cable (HPP   PLC, included in DVPHPP02) 

◎ 

DVPACAB215: 1.5M Cable (PC (DB9+DB25)   PLC) 

◎ 

DVPACAB230: 3.0M Cable (PC (DB9+DB25)   PLC) 

◎ 

DVPACAB2A30: 3.0M Cable (PC (DB9)   PLC) 

2.2 Product Profile and Outline 

1  Status indicator: POWER, RUN, 

ERROR, BAT.LOW 

2  RUN/STOP switch 
3  VR0: M1178 Start-up/D1178 

Corresponding value 

4  VR1: M1179 Start-up/D1179 

corresponding value 

5  DIN rail clip 
6  I/O terminals 
7  I/O point indicators 
8  COM1 (RS-232) (Rx) indicator 
9  COM2 (RS-485) (Tx) indicator 

10  COM1 (RS-232) programming port 

11  Nameplate 

12  Expansion port 
13  Mounting hold of the expansion unit 
14  DIN rail (35mm) 
15  Expansion unit clip 
16  COM2 (RS-485) Communication 

port 

17  DC Power input 
18  RS-485 Cable (standard accessory) 
19  Power input cable (standard 

accessory) 

20  Battery Cover 
21  Battery socket connection 

RUN

RUN

ERROR

POWER

Y3

R

S

-232

R

S

-485

Y1

Y2

C2

Y0

C1

 

Units :mm 

 

※ 

Battery replacement: Please change the battery within 3 minutes, or 

the internal data of the PLC (including the program area, perpetual 
calendar and latched registers) could be lost or destroyed. 

 

 

22  Battery mount 

 

FUNCTION SPECIFICATIONS 

 

Items 

Specifications 

Remarks 

Control Method 

Stored program, cyclic scan system 

 

I/O Processing Method 

Batch processing method (when END command 
is executed) 

I/O refresh command is available 

Execution Speed 

Basic commands (several us) 

Application Commands 
(10~hundreds us) 

Program language 

Co Ladder Logic + SFC 

Including the Step commands 

Program Capacity 

7920 STEPS 

SRAM + Battery 

Commands 

32 Basic sequential commands (including 
STL/RET) 

168 Application commands   

X  External input relay 

X0~X177, octal number system, 128 
points 

Correspond to external input point 

Y  External output relay 

Y0~Y177, octal number system, 128 
points 

Total 

256 

points Correspond to external output point

General 

M0~M511, 512 points (*1) 
M512~M999, 488 points (*3) 

Latched 

M2000~M4095, 2096 points (*3) 

Auxiliary 

Relay 

Special 

M1000~M1999, 1000 points (some are 
latched) 

Total 

4096 

points

Contacts can switch to On/Off in 
program 

T0~T199, 200 points (*1) 
T192~T199 for Subroutine 

100ms 

T250~T255, 6 points Accumulative (*4) 
T200~T239, 40 points (*2) 

10ms 

T240~T245, 6 points Accumulative (*4) 

T Timer 

1ms 

T246~T249, 4 points Accumulative (*4) 

Total 

256 

points

When the timer that set by TMR 
command reaches the preset value, 
the T contact with the same number 
will be On. 

C0~C95, 96 points (*1) 

16-bit count up

C96~C199, 104 points (*3) 
C200~C215, 16 points (*1) 

32-bit count 
up/down 

C216~C234, 19 points (*3) 
C235~C242, 1 phase 1 input, 9 points (*3)
C246~C249, 1 phase 2 input, 3 points (*3)

C Counter 

32bit 
high-speed 
count up/down C251~C254, 2 phase 2 input, 3 points (*3)

Total 

250 

points

When the counter that set by CNT 
(DCNT) command reaches the 
preset value, the C contact with the 
same number will be On. 

Initial step point S0~S9, 10 points (*1) 
Zero point 
reset 

S10~S19, 10 points (use with IST 
command) (*1) 

General 

S20~S511, 492 points (*1) 

Latched 

S512~S895, 384 points (*3) 

Relay (bit mode) 

Step 

point 

Alarm 

S896~S1023, 124 points (*3) 

Total 

1024 

points

Usage device of step ladder diagram 
(SFC) 
Latched Range: 
Start: D1214 (K512) 
End: D1215 (K895)   

Current value of the 
timer 

T0~T255, 256 points 

When the timer reaches the preset 
value, the contact of timer will be On.

C0~C199, 16-bit counter, 200 points 

Current value of the 
counter 

C200~C254, 32-bit counter, 50 points 

When the counter reaches the 
preset value, the contact of counter 
will be On. 

General 

D0~D199, 200 points (*1) 
D200~D999, 800 points (*3) 

Latched 

D2000~D4999, 3000 points (*3) 

Special 

D1000~D1999, 1000 points 

Data 
register 

Index 

E0~E3, F0~F3, 8 points (*1) 

Total 

5000 

points

Can be memory area for storing 
data.    E and F can be used as the 
special purpose of index indication.

Register (WORD dat

a) 

None

 

File register 

0~1599 (1600 points) (*4) 

Expansion register for storing data.

For master control 
nested loop 

N0~N7, 8 points 

Control point of master control 
nested loop 

P  For CJ, CALL commands P0~P255, 256 points 

The location point of CJ, CALL. 

External interrupt 

I001 (X0), I101 (X1), I201 (X2), I301 (X3), I401 
(X4), I501 (X5); 6 points (all are rising-edge 
trigger) 

Time interrupt 

I6

□□

 (1ms), I7

□□

 (1ms), (

□□=

1~99ms) 

Hi-speed counter 

I010, I020, I030, I040, I050, I060; 6 points 

Pointer  I 

Interrupt Service  Communication 

I150, 1 point 

The location pointer of interrupt 
subroutine 

K-32,768 ~ K32,767 (16-bit operation) 

K Decimal 

K-2,147,483,648 ~ K2,147,483,647 (32-bit operation) 

Const

ant 

H  Hexadecimal 

H0000 ~ HFFFF (16-bit operation), H00000000 ~ HFFFFFFFF (32-bit operation) 

Programming port 

COM1: RS-232, COM2: RS-485 (Master/Slave), They can be used at the same time. 

Analog Volume / Perpetual 
Calendar (RTC) 

MPU built-in 2 points VR / MPU built-in RTC 

Special Expansion Module 

Use the same modules (AD, DA, PT, TC, XA, RT) of SS series. (Max. 8 Expansion Unit 
points) 

*1: The non-latched area is fixed, and can’t be changed.   
*2: The non-latched area can be changed to a latched area with parameter setting. 
*3: The latched area can be changed to a non-latched area with parameter setting. 
*4: The latched area is fixed, and can’t be changed.

 

General 

Latched 

Special auxiliary relay 

Latched 

M0~M511 M512~M999 

M1000~M1999 M2000~M4095 

Latched (default) 

Latched (default) 

Auxiliary 

Relay 

Non-latched (fixed) 

Start: D1200 (K512) 

End: D1201 (K999)   

Some are latched and 

can’t be changed 

Start: D1202 (K2000)

End: D1203 (K4095) 

100 ms 

10 ms 

10ms 

1 ms 

100 ms 

T0 ~T199 

T200~T239 

T240~T245 T246~T249 T250~T255 

Timer 

Non-latched (fixed) 

Non-latched (fixed) 

Accumulative Latched (fixed) 

16-bit count up 

32-bit count up/down 

32-bit high-speed count up/down

C0~C95 C96~C199 

C200~C215

C216~C234 C235~C245 

C246~C255 

Latched (default) 

Latched (default) Latched 

(default) 

Counter 

Non-latched 

(fixed) 

Start: D1208 (K96) 
End: D1209 (K199) 

Non-latched 

(fixed) 

Start: D1210 (K216) 

End: D1211 (K234) 

Start: D1212 (K235)   

End: D1213 (K255)   

General Latched 

Special registers 

Latched 

D0~D199 D200~D999 

D1000~D1999 D2000~D4999 

Factory setting is latched.

Factory setting is latched.

Register 

Non-latched (fixed) 

Start: D1216 (K200) 

End: D1217 (K999)   

Some are latched and 

can’t be changed. 

Start: D1218 (K2000) 

End: D1219 (K4999) 

K0~K1599 

File Register 

Latched (fixed) 

  When switching between power On/Off or MPU RUN/STOP modes: 

Memory Type 

POWER 

Off On 

STOP RUN 

RUN STOP 

Clear all M1031 

non-latched area

Clear all M1032 

latched area 

Factory 

Setting

M1033=Off, clear

Non-latched Clear 

Unchanged M103=On, 

unchanged 

Clear Unchanged 

Latched Unchanged 

Unchanged 

Clear 

Special M, Special 

D, Index register 

Initial value 

Unchanged 

Unchanged 

Initial 
value

File register 

Unchanged 

 

4

ELECTRICAL SPECIFICATIONS 

 

                      Model 
  Item 

DVP12SA11R/T  DVP08SM11N

DVP08SN11R/T DVP08SP11R/T DVP16SP11R/T

Power supply voltage 

MPU: 24VDC (-15%~20%) (with DC input reverse polarity protection),   
Expansion Unit: supplied by the MPU 

Fuse 

2A / 250VAC 

 

Power Consumption 

6W 5W 5W 8W 8W 

Insulation Resistance 

> 5 M

Ω

  at 500 VDC (Between all inputs / outputs and earth) 

Noise Immunity 

ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz~1GHz, 10V/m 

Grounding 

The diameter of grounding wire cannot be smaller than the wire diameter of 

terminals L and N (All DVP units should be grounded directly to the ground pole). 

Environment 

Operation: 0

~55

  (Temperature), 50~95% (Humidity), Pollution degree 2;   

Storage: -25

~70

  (Temperature), 5~95% (Humidity) 

Vibration / Shock Resistance  Standard: IEC1131-2, IEC 68-2-6 (TEST Fc) / IEC1131-2 & IEC 68-2-27 (TEST Ea)
Weight (approx.) (g) 

158 

128 

154 /146 

141 /136 

162 /154 

 

Input Point Electrical Specification 

Output Point Electrical Specification 

Input Type

DC (SINK or SOURCE) 

Output Type 

Relay-R 

Transistor-T 

Input Current 24VDC 5mA 

Current 
Specification 

1.5A/1 point 
(5A/COM) 

0.3A/1 point @ 40

; When the output 

of Y0 and Y1 is high-speed pulse, Y0 
and Y1 = 30mA 

Off

On, above16VDC 

Voltage 
Specification 

Below 250VAC, 
30VDC 

30VDC 

Active Level

On

Off, below 

14.4VDC 

75VA 
(Inductive) 

Maximum 
Loading 

90 W 
(Resistive) 

9W/1 point

When the output of Y0 and 
Y1 is high-speed pulse, Y0 
and Y1 = 0.9W (Y0 = 
32kHz, Y1 = 10kHz) 

Responding 

Time 

About 10ms (An 
adjustment range of 
0~10,000ms could be 
selected through D1020 
and D1021) 

 

Responding 
Time 

About 10 ms 

Off

On 

20us 
On

Off 

30us 

Y0 and Y1 are specified 
points for high-speed pulse

 

5

MODEL NAME & I/O CONFIGURATION 

 

 Standard MPU 

Input / Output 

Input Unit 

Output Unit 

Model 

Power 

Point 

Type 

Point 

Type 

Profile 

reference 

I/O Configuration

DVP12SA11R 8 

Relay 

DVP12SA11T 

24VDC 

DC Sink or 

Source 

4 Transistor

 

S/S

X0

X1

X2

X3

X4

X5

X6

X7
C0

Y0

C1

C2

Y1

Y2

Y3

 

 

6

INSTALLATION & WIRING 

6.1 PLC Mounting Arrangements and Wiring Notes 

 Installation of the DIN rail 

The DVP-PLC can be secured to a cabinet by using the 
DIN rail that is 35mm high with a depth of 7.5mm. When 
mounting the PLC on the DIN rail, be sure to use the end 
bracket to stop any side-to-side motion of the PLC, thus to 
reduce the chance of the wires being pulled loose. At the 
bottom of the PLC is a small retaining clip. To secure the 
PLC to the DIN rail, place it onto the rail and gently push 
up the clip. To remove it, pull down the retaining clip and 
gently pull the PLC away from the DIN rail.    As shown on 
the right: 

When installing the DVP 

series PLC, make sure that it is 
installed in an enclosure with 
sufficient space (as shown 
below) to its surroundings so as 
to allow heat dissipation. 

DVP

MP

D

D

D

D

D > 50 mm

 

 

 Wiring 

22-16AWG

<1.5mm

 

Notes: 

1

 Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for I/O 

wiring terminals. The specification for the terminals is as shown on the left. PLC 
terminal screws should be tightened to between 5~8 kg-cm (4.3~6.9 in-lbs). 

2

 I/O signal wires or power supply should not run through the same multi-wire 

cable or conduit.

 

6.2 Wiring Notes 

 Environment 

1. DO NOT store the PLC in an atmosphere that is dusty, smoky, with metallic debris or corrosive or flammable gases. 
2. DO NOT store the PLC in an environment with high temperature or high humidity. 
3. DO NOT install the PLC on a shelf or on an unstable surface. 

 Power Input Wiring 

DVP-SA series input power supply is DC input. Please take a note of listed items when operating DVP-SA. 

Series. 