DVP04AD-S 

                               

 DVP04AD-S

                   

Analog Input Module 

                                                                                 

Instruction Sheet

 

 

WARNING 

 

Always read this instruction thoroughly before using the DVP04AD-S. 

  The DC input power must be disconnected before any maintenance. 

  This is an OPEN-TYPE built-in DVP04AD-S, and the DVP04AD-S is certified to meet the safety 

requirements of IEC 61131-2 (UL 508) when installed in the enclosure to avoid high temperature, 
high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or metallic particles. 
Also, it is equipped with protective methods such as some special tool or key to open the 
enclosure, so as to avoid the hazard to users and the damage to the DVP04AD-S. 

  Do not connect the AC power to any of the input/output terminals, as it might cause damage to 

the DVP04AD-S. Make sure that all the wiring is well conducted prior to power on. 

  Do not touch the internal circuit for at least 1 minute after the power supply is disconnected. 
  Make sure that the DVP04AD-S is properly grounded 

, to avoid any electromagnetic noise.

 

 

INTRODUCTION

 

2.1  Model Explanation and Peripherals

 

 

Thank you for choosing DELTA’s PLC DVP Series. The analog input module receives external 
4-point analog signal input (voltage or current) and transforms it into 14 bits digital signal. The 
analog input module of DVP04AD-S series can read/write the data of analog input module by 
using commands FROM / TO via DVP-PLC SS/SA/SX Series MPU program.  There are 49 
CR(Control Register) in each module and there are 16 bits in each register. 

 

DVP04AD-S analog input module can update software version by RS-485 communication. Power 
unit and module are separate. Small volume and easy to install. 

 

Users can select input from voltage or current via wiring. Voltage input range is 

±

10V DC 

(resolution is 1.25 mV). Current input range is 

±

20 mA (resolution is 5 µA). 

 

Nameplate Explanation

 

P L C  m o d e l

Input power Supply Spec.

Analog Input /Output Module Spec.

Barcode, series and version

04AD-S0T3250003

VX.XX

20.4VDC ~ 28.8VDC

MADE  IN  XXXXX X

1.25 mV or  5    A

 -10V ~ + 10V or  -20mA ~ +20mA

 

 

Model Explanation

 

Serial Number

Model

S: for SS series MPU
P: for EP series MPU
H: for EH series MPU 

XA: Analog input/output mixed module

Product Series
Input + Output points 

Model type

AD: Analog input module

DA: Analog output module

PT: Platinum temperature sensors (PT-100) 

TC: Thermocouple sensors (Type J/K)

Production series

Production week

Production year (2004)

Production place (Taoyuan)
Serial number of version

Production Model

RT: Resistor Thermocouple

HC: Input module of high-speed counter

PU: single axis positioning unit

 

2.2  Product Profile and Outline 

90.00

4.00

3.00

25.20

1

2

3

4

60.00

5

6

7

8

9

3

10

FG

V+
I+

COM

C

H

1

FG

V+
I+

COM

C

H

2

FG

V+
I+

COM

C
H

3

FG

V+
I+

COM

C

H

4

11

12

13

3.4

90.00

60.00

3.00

14

 

UNIT: mm

 

1. Status indicator (Power, RUN and ERROR) 

8. Expansion port 

2. Model name 

9. Expansion unit clip 

3. DIN rail clip 

10. DIN rail (35mm) 

4. I/O terminals 

11. RS-485 Communication port 

5. I/O point indicator 

12. Mounting rail of the Expansion unit 

6. Mounting hole of the Expansion unit 

13. DC Power input 

7. Nameplate 

14. Expansion port 

 

2.3 External 

wiring 

Voltage Input
-10V ~ +10V

Current Input

-20mA ~ +20mA

V+

COM

Isolation Wire    1

 

 

5

FG

I+

250

 Ω

~

~

V+

FG

I+

2

CH1

CH4

250

 Ω

24+

24-

3

AG

+15V

-15V

DC/DC

Converter

4

System 

Grounding

Class 3 Grounding

(100      or less)

 Ω

COM

CH1

CH4

104.7K

104.7K

 

AG

104.7K

104.7K

 

AG

Isolation Wire    1

 

terminal of 

power module

Note 1: Please isolate analog input and other 

power wiring. 

Note 2: If connect to current signal, please 

short circuit between V+ and I+ 
terminals. 

Note 3: If noise is too loud, please connect 

FG to grounding. 

Note 4: Please connect   

 terminal of 

power module and 

 terminal of 

analog input module to system 
earth point and make system earth 
point be grounding or connects to 
machine cover.   

Note 5: If wave of input terminal of loaded is 

too big that noise interferes wiring, 
please connect capacitance with 
0.1~0.47µF 25V. 

Warning: DO NOT wire to the No function 

terminal  .

 

2.4    Terminal of analog module layout 

DVP04AD-S 

DVP02DA-S 

DVP04DA-S 

DVP04PT-S 

DVP04TC-S 

DVP06XA-S 

DVP08RT-S 

V+

I+

COM

FG

V+

I+

COM

FG

I+

COM

FG

V+

I+

COM

FG

V+

 

V+

I+

COM

FG

V+

I+

COM

FG

 

V+

I+

COM

FG

V+

I+

COM

FG

V+

I+

COM

FG

V+

I+

COM

FG

 

L+

L-

FG

FG

I-

L+

L-

I-

L+

L-

FG

FG

I-

L+

L-

I-

 

L+

L-

SLD

L+

L-

L+

L-

L+

L-

SLD

SLD

SLD

 

V+

I+

COM

V+

I+

COM

I+

COM

V+

I+

COM

V+

V+

I+

COM

V+

I+

COM

 

L1+

L1-

FG

L3+

L3-

L2-

L2+

L4-

L4+

L51

L5-

FG

L7+

L7-

L6-

L6+

L8-

L8+

 

 

 

STANDARD SPECIFICATIONS 

3.1 Function 

Specifications 

Analog/ Digital (4A/D) module 

Voltage input 

Current input 

Power supply voltage 

24 VDC(20.4VDC~28.8VDC) ( –15% ~ +20%) 

Analog input channel 

4 channel / each module 

Analog input range 

±

10V 

±

20 mA 

Digital conversion range 

±

8000 

±

4000 

Resolution 

14 bits(1

LSB

=1.25 mV) 

13 bits (1

LSB

=5 µA) 

Input impedance 

200 K

Ω以上

 250

Ω

 

Overall accuracy 

±

0.5% of full scale of 25

(77

)  

±

1% of full scale during 0~55

 (32~131

Response time 

3 ms 

×

 channels 

Isolation Method 

It has isolation between digital area and analog area. There is no isolation among 
channels.  

Absolute input range 

±

15 V 

±

32 mA 

Digital data format 

2’s complementary of 16-bit, 13 Significant Bits   

Average function 

Yes (CR#2~CR#5 can be set and setting range is K1~K4096) 

Self diagnose function 

Upper and lower bound detection / channels 

Communication mode (RS-485) 

MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / 9600 / 19200 / 38400 /
57600 / 115200. For ASCII mode, date format is 7Bits, even, 1 stop bit (7 E 1). For RTU 
mode, date format is 8Bits, even, 1 stop bit (8 E 1). The RS-485 is disabled when the 
DVP04AD-S is connected in series to an MPU. 

Connect to DVP-PLC MPU in series 

The input point of the first analog expansion unit it connects from the near to the distant 
is from 0 to 7. The Max. is 8 modules and it won’t waste digital I/O point. 

3.2 Other 

Specification 

Power Specification 

Max. Rated Consuming Power 

24 VDC(20.4VDC~28.8VDC) ( –15%

+20%), 2W, supply from external power 

Environment Condition 

Environment Condition 

It is the same with DVP-PLC MPU. 

Spec. of Prevent Static Electricity

All places between terminal and grounding 

 

 

CR (Control Register)

 

 

 

 

 

 

 

 

DVP04AD-S analog signal input module 

Explanation 

CR

No.

RS-485

Parameter 

address

Latched Register 

name b15 

b14 

b13 

b12 

b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

#0

H 4000

 

Model type 

System used, data length is 8bits (b7~b0). DVP04AD-S model code =H 88 

reserved  CH4 CH3 CH2 CH1 

#1

H 4001

  R/W Input 

mode 

setting 

Input mode setting: factory setting is H0000. 

Mode 0: input voltage mode (-10V~+10V). 

Mode 1: input voltage mode (-6V~+10V). 
Mode 2: input current mode (-12mA~+20mA) 
Mode 3: input current mode(-20mA~+20mA) 
Mode 4: none use. 

#2

H 4002

  R/W  CH1 average times 

#3

H 4003

  R/W  CH2 average times 

#4

H 4004

  R/W  CH3 average times 

#5

H 4005

  R/W  CH4 average times 

Average times setting of channel CH1~CH4. Setting range is K1~K4096 and factory 
setting is K10. 

#6

H 4006

 

average value of 
CH1 input signal   

#7

H 4007

 

average value of 
CH2 input signal   

#8

H 4008

 

average value of 
CH3 input signal 

#9

H 4009

 

average value of 
CH4 input signal 

Display average value of CH1~CH4 input signal 

#10 ~ #11 

Reserved 

#12

H 400C

 

present value of CH1 
input signal   

#13

H 400D

 

present value of CH2 
input signal   

#14

H 400E

 

present value of CH3 
input signal 

#15

H 400F

 

present value of CH4 
input signal 

Display present value of CH1~CH4 input signal 

#16 ~ #17 

Reserved 

#18

H 4012

  R/W  To adjust OFFSET 

value of CH1 

#19

H 4013

  R/W  To adjust OFFSET 

value of CH2 

#20

H 4014

  R/W  To adjust OFFSET 

value of CH3 

#21

H 4015

  R/W  To adjust OFFSET 

value of CH4 

Offset setting of CH1~CH4. Factory setting is K0 and unit is LSB. 
Voltage input: setting range is K-4000 ~K4000 
Current input: setting range is K-4000 ~K4000 

#22 ~ #23

 

Reserved 

#24

H 4018

  R/W  To adjust GAIN value 

of CH1 

#25

H 4019

  R/W  To adjust GAIN value 

of CH2 

#26

H 401A

  R/W  To adjust GAIN value 

of CH3 

#27

H 401B

  R/W  To adjust GAIN value 

of CH4 

GAIN setting of CH1~CH4. Factory setting is K4000 and unit is LSB. 
Voltage input: setting range is K-3200 ~K16000. 
Current input: setting range is K-3200 ~K10400. 

#28 ~ #29 

Reserved 

#30

H 401E

 

Error status 

It is the data register to save all error status. Please refer to fault code chart for detail.

#31

H 401F

  R/W Communication 

address setting 

Setting RS-485 communication address. Setting range is 01~255 and factory setting 
is K1 

#32

H 4020

  R/W Communication 

baud 

rate setting 

It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600, 
115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). 
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1). 

b0: 4800 bps (bit/sec).               b1: 9600 bps (bit/sec). (factory setting) 
b2: 19200 bps (bit/sec).                            b3: 38400 bps (bit/sec).                                   
b4: 57600 bps (bit/sec).              b5: 115200 bps (bit/sec). 
b6-b13: reserved.                                         
b14: exchange low and high byte of CRC check code (only for RTU mode) 
b15: ASCII / RTU mode selection 

b15 b14 b13 b12 b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Reserved CH4 CH3 CH2 CH1 

#33

H 4021

  R/W Reset 

to 

factory 

setting and set 
characteristics 
adjustable priority 

Factory setting is H0000. 
Give CH1 setting for example:   

1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18, CR#24). 

When b0=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#18, 
CR#24). 

2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1 

(not latched).   

3. When b2 is set to 1, all settings will reset to factory setting. 

#34

H 4022

 

Software version 

It is hexadecimal to display software version. For example: H 010A means 1.0A. 

#35~#48 System 

used 

 means latched.  

 means not latched.  

R means can read data by using FROM command or RS-485.   
W means can write data by using TO command or RS-485. 

LSB (Least Significant Bit):    1. Voltage input: 1

LSB

=10V/8000=2.5mV.  2. Current input: 1

LSB

=20mA/4000=5µA. 

Explanation: 
1. 

CR#0: The content of CR#0 is model type, user can read the data from program to know if there 
is expansion module. 

2. 

CR#1: CR#1 is used to set 4 inner channels working mode of analog input module. Every 
channel has four modes to set and can be set individually. For example: if setting CH1 to mode 0 
(b2~b0=000), CH2 to mode 1(b5~b3=001), CH3: mode2 (b8~b6=010), CH4: mode 
3(b11~b9=011). It needs to set CR#1 to H0688 and the upper bit (b12~b15) will reserved. The 
factory setting of CR#1 is H0000. 

3. 

CR#2 ~ CR#5: it is used to set average times of CH1~CH4. Setting range is K1~K4096 and 
factory setting is K10. 

4. 

CR#6 to CR#9 are the average value that calculates according to the value that is set in 
CR#2~CR#5 (average time of CH1~CH4 input signal). For example, if CR#2 (the average times 
of CH1) is 10, it will calculate the average of CH1 input signal every 10 times. 

5. 

CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28, CR#29 reserved. 

6. 

CR#12 ~ CR#15: display present value of CH1~CH4 input signal. 

7. 

CR #18~ CR #21: the content is the value of adjusting OFFSET value of CH1~CH4 if analog 
input voltage or current is 0 after it transfers from analog to digital. Voltage setting range: 
-5V~+5V(-4000

LSB

~+4000

LSB

). Current setting range: -20mA~+20mA (-4000

LSB

~+4000

LSB

). 

 