TECHNICAL DATASHEET
Sync DIN Rail Power Supply
24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (July 2019, Rev. 04)
9
Safety Instructions
•
ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the device. If mains are not turned OFF,
there is risk of explosion / severe damage.
•
To guarantee sufficient convection cooling, keep a distance of > 40mm
(1.57 inch) above and > 20mm (0.79 inch) below the device as well as a
lateral distance of > 10mm (0.39 inch) to other units. In case the
adjacent device is a heat source, the lateral distance will be > 25mm
(0.98 inch).
•
Note that the enclosure of the device can become very hot depending on
the surrounding air temperature and output load connected to the device.
Risk of burns!
•
The main power must be turned off before connecting or disconnecting the
wires to the terminals!
•
DO NOT insert any objects into the device.
•
Dangerous voltages present for at least 5 minutes after disconnecting all
sources of power.
•
The power supplies unit should be installed in minimum IP54 rated
enclosure.
•
The power supplies are built in units and must be installed in a cabinet or
room (condensation free environment and indoor location) that is relatively
free of conductive contaminants.