![Delta DRP048V240W1B Series Assembly & Installation Download Page 4](http://html.mh-extra.com/html/delta/drp048v240w1b-series/drp048v240w1b-series_assembly-and-installation_2474071004.webp)
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
48V 240W 1 Phase / DRP048V240W1B
□
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 01)
4
Safety Standards / Directives
Electrical Equipment in Power Installations
EN 50178 / IEC 62103
Electrical Safety
SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1
and CSA C22.2 No. 60950-1, CB scheme to
IEC 60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01,
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX (For DRP048V240W1BA)
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA
12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4,
Ta= -25°C to +80°C (Vertical: > +50°C derating,
Horizontal: > +40°C derating)]
EN 60079-0:2009, EN 60079-15:2010 [ II 3G Ex nA
nC IIC T4 Gc, Ta= -25°C to +80°C (Vertical: > +50°C
derating, Horizontal: > +40°C derating)]
II 3G ATEX 94/9/EC (For DRP048V240W1BA)
Certificate No. EPS 12 ATEX 1 491 X
CE
In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
For DRP048V240W1BA:
In conformance with Equipment for explosive
atmospheres (ATEX) directive 94/9/EC
Material and Parts
RoHS Directive 2011/65/EU Compliant
Galvanic Isolation
Input to Output
4.0KVac
Input to Ground
1.5KVac
Output to Ground
1.5KVac