II. TECHNICAL SPECIFICATIONS

Power Supply

230V, 50Hz

Detected Gas

CO

Range

0-350 ppm

Sensor

Electrochemical cell

Pre-alarm level “ALARM 1”

50 ppm CO - adjustable

Alarm level “ALARM 2”

150 ppm CO - adjustable

Pre-alarm output signal “REL 1”

SPDT relay, 5A/250V

Alarm output signal “REL 2”

SPDT relay, 5A/250V

Signalization

Audible 85dB/m + visual

Indication

LED

Ambient temperature for sensors

-10

+50

С

Reaction delay of sensors

60s

Dimensions of control unit

140 x 50 x 135 mm

Protection degree of control unit

IP30

Weight

250 g

CONNECTION SCHEME

220VAC

REL1

REL2

NOTE: In larger areas can be connected several gas detectors parallely to
operate a common ventilation system.

III. MOUNTING INSTRUCTIONS

Mount the gas detector in areas with normal risk of fire at heights of 10-15 cm below

the ceiling or at the height of a man, measured from the floor.

When mounting, the following factors have to be considered:

vibrations presence

The Sensor is vibration-sensitive, so the gas detector should either be mounted in a

place where vibrations are not present, or measures for their reduction have to be taken.