Product Description 

The DFC-304R3-240 Fan Coil Controller is a 

line powered, fully programmable (via GCL+) 

Native BACnet

 Application Controller that 

communicates using the BACnet MS/TP 

protocol. Direct 240 VAC line voltage terminal 

connections are provided for one, two, or three 

speed fans (up to 1 HP).  

The binary model, with additional 4 triac 

outputs, covers a wide range of Fan Coil Unit 

applications, including two and four pipe fan 

coils.  And room temperature can be a 

standard 10K sensor or a BACstat II 

connected via a secondary LINKnet network 

and 24 VAC power out connection. 

 

Important Information  

 

 

This controller has terminals for connecting 240VAC (Class 1, Line Voltage). The terminals are 

safety rated, however this controller may have to be mounted in an enclosure if it is not 

mounted inside the FCU. Check local electrical codes.    

Package Contents 

 

Product: DFC-304R3-240 (Rev. 2.1) 

 

DFC-304R3-240 Installation Guide 

Related Documents 

 

Delta Controls Wiring Guidelines 

 

DSC/DSC Release Notes for related Firmware  

 

Delta Controls General System Description (Delta Products System Architecture Description) 

Summary of Contents for DFC-304R3-240

Page 1: ...including two and four pipe fan coils And room temperature can be a standard 10K sensor or a BACstat II connected via a secondary LINKnet network and 24 VAC power out connection Important Information...

Page 2: ...nside Equipment damage or loss of data may occur if the user does not follow a procedure as specified This controller is an Electro statically sensitive device Proper ESD protection ground strap shoul...

Page 3: ...ess you are assigning a BACnet device number through software The BACnet device number should not be confused with the DIP switch setting and each device must still have a unique dip switch address ev...

Page 4: ...load stranded or solid copper wire with Class I insulation Keep Class 2 wiring separate from Class 1 wiring Power The Fan Coil Controllers require 240 VAC 2000VA maximum this includes fan motor load a...

Page 5: ...epeater RPT 768 LINKnet networks that have only 1 2 devices and have less then 100 ft of cable length do not require network terminators Input and Output Wiring Inputs and outputs on the DFC 304R3 240...

Page 6: ...hat requires delays when switching the fan speeds the database must be modified to suit It is recommended that the Speed III terminal be used for single speed fan applications use Speed II and III ter...

Page 7: ...d click enter to add a row Power Requirements 240 VAC 50 60Hz 2000 VA maximum Class 1 18 AWG to 12 AWG copper wire non removable terminal blocks 90 C minimum rated wire or equivalent to be used Power...

Page 8: ...tage Power only 18 AWG to 12 AWG Copper wire non removable terminal blocks Technology 16 bit processor 1 MB 8 megabit Flash Memory 256 KB SRAM memory 64 available for database Database backup via non...