background image

DFC-304R3 Rev 2.1 Installation Guide.doc 

Page 3 of 8 

Device Configuration 

Device Type 

Various products have the capability of being configured as one of several 

possible device types, which represents the network level that it will reside on 

in the network architecture (Area, System, Subnet). Other than the one device 

acting as a router, all other devices on the same network segment must be 

configured the same. 

System/Subnet

: The DFC-304R3-240 is a Subnet device only. It cannot be 

configured as a System device. 

 

AREA

SYSTEM

SUBNET

 

 

Derived Network Addressing 

The 

DNA jumper

 comes ON by default. This allows the device to automatically 

configure a BACnet device address. This should NOT be removed unless you 

are assigning a BACnet device number through software. The BACnet device 

number should not be confused with the DIP switch setting, and each device 

must still have a unique dip switch address even when using software to define 

the device number. 

DNA

 

Device Addressing  

The Dip Switch is a binary switch. Each individual DIP switch represents a 

unique value, which forms the device address when added together. 

To set the address, simply move the switches that add up to the devices 

desired address to the ON position. 

Example: If the device is to be address 5 on the network, set the switch 

numbered 4 and the switch numbered 1 (equals 5) to the On position. 

Note

: Each device on the same MS/TP segment must have a unique DIP 

switch address. 

Refer to the DNA section of the 

ORCAview Technical Reference Manual

, and 

the 

General System Description 

for more information on DNA and 

System/Subnet devices. 

 

 

 

Summary of Contents for DFC-304R3-240

Page 1: ...including two and four pipe fan coils And room temperature can be a standard 10K sensor or a BACstat II connected via a secondary LINKnet network and 24 VAC power out connection Important Information...

Page 2: ...nside Equipment damage or loss of data may occur if the user does not follow a procedure as specified This controller is an Electro statically sensitive device Proper ESD protection ground strap shoul...

Page 3: ...ess you are assigning a BACnet device number through software The BACnet device number should not be confused with the DIP switch setting and each device must still have a unique dip switch address ev...

Page 4: ...load stranded or solid copper wire with Class I insulation Keep Class 2 wiring separate from Class 1 wiring Power The Fan Coil Controllers require 240 VAC 2000VA maximum this includes fan motor load a...

Page 5: ...epeater RPT 768 LINKnet networks that have only 1 2 devices and have less then 100 ft of cable length do not require network terminators Input and Output Wiring Inputs and outputs on the DFC 304R3 240...

Page 6: ...hat requires delays when switching the fan speeds the database must be modified to suit It is recommended that the Speed III terminal be used for single speed fan applications use Speed II and III ter...

Page 7: ...d click enter to add a row Power Requirements 240 VAC 50 60Hz 2000 VA maximum Class 1 18 AWG to 12 AWG copper wire non removable terminal blocks 90 C minimum rated wire or equivalent to be used Power...

Page 8: ...tage Power only 18 AWG to 12 AWG Copper wire non removable terminal blocks Technology 16 bit processor 1 MB 8 megabit Flash Memory 256 KB SRAM memory 64 available for database Database backup via non...

Reviews: