Timer + Counter Function 

In Timer + Counter function, SV1, PV1 and Output 1 are for Timer; SV2, PV2 and Output2 are for Counter. DIP switch is 
disabled. All timer and counter functions remain except 
 

y

 

RCY2, SCON, STON, STOFF in output mode of Timer function 

y

 

Command up/down, Individual up/down, quadrature counting in input mode, S, T, D in output mode of Counter function 

 
Only 1-stage counting in Counter function is available. 

 

 

 

Easy DIP Switch Setup

 

Users can use DIP switch to setup parameters. When DIP is switched to ON, the corresponding parameters can only be 
read, not changed. 

SW 

Counter 

Timer 

Tachometer 

Reset pulse width   
ON: 1ms, OFF: 20ms 

Reset pulse width   
ON: 1ms, OFF: 20ms 

Reset pulse width   
ON: 1ms, OFF: 20ms 

Input type 
ON: PNP  OFF: NPN 

Unit of Timer 
See Table 2 

Input type 
ON: PNP  OFF: NPN 

6 N/A 

Unit of Timer 
See Table 2 

N/A 

Counting speed 
ON: 10KCPS    OFF: 30CPS 

Unit of Timer 
See Table 2 

Counting speed 
ON: 10kHz  OFF: 30Hz 

Output mode of counter 
See Table 3 

Output mode of Timer 
See Table 3 

Output mode of Tachometer 
See Table 3 

Output mode of counter 
See Table 3 

Output mode of Timer 
See Table 3 

Output mode of Tachometer 
See Table 3 

Input mode of counter 
ON: counting down    OFF: counting up 

Time counting up/down 
ON: down    OFF: up 

N/A 

ON: Enable DIP 
OFF: Disable DIP 

ON: Enable DIP 
OFF: Disable DIP 

ON: Enable DIP 
OFF: Disable DIP 

 

SW5 

SW6 

SW7 

Displayed unit   

OFF OFF OFF 0.01s 

 

ON OFF OFF 

0.1s 

 

 

OFF ON OFF 

1s 

 

Output Mode Configuration 

ON ON OFF 

min, 

0.01s   

SW3 

SW4 

Counter

Timer 

Tachometer

OFF 

OFF 

ON 

min, 0.1s 

 

OFF 

OFF 

Signal ON Delay 1 

Lo-Lo 

ON 

OFF 

ON 

0.1 min 

 

ON 

OFF 

Signal ON Delay 2 

Lo-Hi 

OFF 

ON 

ON 

min 

 

OFF 

ON 

Signal OFF Delay 

Hi-Lo 

ON 

ON 

ON 

hr, min, sec 

 

ON 

ON 

Signal ON 

Hi-Hi 

Table 2 

 

 

 

 

 

 

Table 3 

VARITEL INGENIERIA ELECTRONICA S.A.

[email protected] - www.varitel.com - Tel. (54) 11-4243-1171 / Fax: (54) 11-4292-7545

Manuel Baliña 456, Lomas de Zamora (B1832CCJ) Buenos Aires, Argentina. 

Summary of Contents for CTA4000A Series

Page 1: ...ected to proper terminals 6 Keep away from high voltage and high frequency environment during installation in case of interference 7 Prevent using the device in premises which contain Dust or corrosiv...

Page 2: ...operation mode for more than 3 seconds to enter configuration mode Press MODE once to switch among parameters To return to operation mode press MODE for more than 3 seconds Ordering Information CTA 2...

Page 3: ...data or not while switching off power MODE Setup pre scale value MODE Setup the decimal point MODE Setup the pulse width of output 2 MODE Tachometer Select a function MODE Setup output mode of Tachome...

Page 4: ...from 0 to 99 99 secs 0 Hold output Setup output modes Setup the counting unit of the timer sec 0 01 9 999 99 A unit 10ms Max counting 9 999 99 secs sec 0 1 99 999 9 A unit 0 1sec Max counting 99 999 9...

Page 5: ...l Pause signal Clear signal Output signal Up Down SV SV Repeat Cycle 0 0 timer output set as 0 Power signal Start signal Pause signal Clear signal Output signal Up Down SV SV Repeat Cycle t t t timer...

Page 6: ...s include 1 stage counting 2 stage counting batch counting total counting and dual counting 1 stage Only 1 SV is allowed See output modes of counter 2 stage 2 SVs 2 PVs are allowed See output modes of...

Page 7: ...A n n 1 n 2 n 3 n 4 n 5 H L H L CP1 CP2 0 Present Value CP1 Counter input prohibited CP2 Counter input Note has to be larger than width of min Input signal A Command counting up down UD_A Individual c...

Page 8: ...t the counting stops Recounting starts and Output 2 pulse executes after reset signal is over S When PV SV1 Output 1 is enabled When PV SV2 Output 2 is enabled T When PV SV1 Output 1 is enabled When P...

Page 9: ...OUT2 OUT1 Output mode setting Input mode Up Down Up Down A B C K P Q A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T VARITEL INGENIERIA ELECTRONICA S A info varitel c...

Page 10: ...RTU mode Function codes 03H register read and 06H single register write Function code 03H can read maximum 8 words at a time ASCII Mode Register Read 03H Response Register Write 06H Response Start ch...

Page 11: ...ter Content Remark 1000H 0 V V V PV1 Low byte 1001H 0 V V V PV1 High byte 1002H 0 V PV2 Low byte 1003H 0 V PV2 High byte Available on batch total dual counter and mixed mode 1004H 0 V V V SV1 Low byt...

Page 12: ...Tachometer Function Measuring Rotation speed Measuring pulse width and determining current frequency Output methods Lo Lo Lo Hi Hi Lo Hi Hi OUT2 set value Measurement value OUT1 set value OUT1 OUT2 OU...

Page 13: ...eed ON 10KCPS OFF 30CPS Unit of Timer See Table 2 Counting speed ON 10kHz OFF 30Hz 4 Output mode of counter See Table 3 Output mode of Timer See Table 3 Output mode of Tachometer See Table 3 3 Output...

Page 14: ...D series Multi function input pin Counter Timer Tachometer Timer Counter CP1 CP1 CP1 CP2 Gate Gate Reset1 Reset1 Reset1 Reset1 Reset2 Start Start VARITEL INGENIERIA ELECTRONICA S A info varitel com ww...

Page 15: ...he top and bottom of the controller and push the mounting bracket forward until the bracket stops at panel wall 3 Insert and tighten screws on bracket to secure the controller in place VARITEL INGENIE...

Reviews: