ASDA-A3
Operation Mode
Revision December, 2017
6-27
6
6.4.3
Smooth Torque command
Relevant parameters: refer to Chapter 8 for more information.
Parameter
Function
P1.007
Torque command smoothing constant (Low-pass filter)
Target
speed
TFLT
6.4.4
Scaling of the analog command
The Torque command is controlled by the analog voltage difference between T_REF and GND.
You can adjust the torque slope and its range with parameter P1.041.
For example:
1. If you set P1.041 to 100 and the external input voltage is 10V, the Torque command is 100%
of the rated torque.
2. If you set P1.041 to 300 and the external input voltage is 10V, the Torque command is 300%
of the rated torque.
300%
100%
-300%
-100%
The slope is set by
P1.041
Analog voltage
input (V)
10
5
-10
-5
Torque
command
Relevant parameters: refer to Chapter 8 for more information.
Parameter
Function
P1.041
Maximum output for analog Torque command
Summary of Contents for ASD-A3-0121
Page 13: ...Revision December 2017 This page is intentionally left blank...
Page 43: ...Installation ASDA A3 2 20 Revision December 2017 2 This page is intentionally left blank...
Page 105: ...Wiring ASDA A3 3 62 Revision December 2017 3 This page is intentionally left blank...
Page 187: ...Operation Mode ASDA A3 6 36 Revision December 2017 6 This page is intentionally left blank...
Page 467: ...Parameters ASDA A3 8 210 Revision December 2017 8 This page is intentionally left blank...
Page 577: ...Specifications ASDA A3 A 28 Revision December 2017 A This page is intentionally left blank...
Page 597: ...Accessories ASDA A3 B 20 Revision December 2017 B This page is intentionally left blank...
Page 603: ...4 Revision December 2017 This page is intentionally left blank...