background image

20

Amplon N Series

5.5  Setup Mode 

Press the scrolling button     for more than 3 seconds and the LCD will go into the 

setup menu.

Please note that only qualified service personnel can perform setup action. In setup 

mode, you can set up the following items: 
1.  Inverter voltage 
2.  Inverter frequency
3.  Bypass range 
4.  Buzzer disable 
5.  Overload alarm

For setup procedures, please refer to the following: 

1.  Press the    button for more than 3 seconds to enter into the setup mode.
2.  Press the    button for 0.1 second to change the parameter.
3.  Press the 

 button for 0.1 second to confirm your parameter.

4.  Press the 

 button for 0.1 second to go to the next setup item.

5.  You can skip to the next setup item by pressing the 

 button for 0.1 second.

6.  In setup mode, press the    button for more than 3 seconds, the LCD will go 

back to the original display.

7.  In setup mode, if you don’t press any button for more than 2 minutes, the LCD 

will exit from the setup mode and go back to the original display automatically.

For some settings, they can’t be set in certain operation modes. Please refer to the 
table below for relevant information.

Setup  Item

Standby 

Mode

On-line 

Mode

Bypass 

Mode

Battery 

Mode

Inverter Voltage Setup

Inverter Frequency Setup

Bypass Range Setup

Summary of Contents for Amplon UPS102N2000B035

Page 1: ...www deltapowersolutions com Delta UPS Amplon Family User Manual The power behind competitiveness N Series Single Phase 1 2 3 kVA...

Page 2: ...product Any disposition duplication dissemination reproduction modification translation extraction or usage of this Manual in whole or in part is prohibited without the prior written permission of De...

Page 3: ...1 LED Indicators 8 3 2 Multi function Buttons 9 3 3 LCD Display 11 3 4 7 Segment Display 14 3 5 Flow Chart of the 7 Segment Display 16 Chapter 4 Rear Panel 18 Chapter 5 Operation Modes 19 5 1 Standby...

Page 4: ...IV Amplon N Series Chapter 9 Troubleshooting 25 Chapter 10 Maintenance 28 10 1 UPS 28 10 2 Batteries 28 10 3 Fan 29 Appendix 1 Technical Specifications 30 Appendix 2 Warranty 32...

Page 5: ...e at least 15cm around all sides of the UPS for proper ventilation Connection Warnings z z The UPS must be well grounded due to a possible risk of current leakage z z The installation of upstream and...

Page 6: ...object into the UPS s slits and openings Do not put beverage containers on or around the UPS z z When an emergency occurs press the OFF button and release it after you hear one beep to turn off the UP...

Page 7: ...ric shock and short circuit current is possible when the batteries are connected to the UPS Before maintenance disconnect all batteries to cut off the battery power z z For battery replacement only us...

Page 8: ...connect the UPS from the utility power remove all equipment from the UPS and store the UPS in a dry and well ventilated area at a temperature between 15 C and 50 C 5 F 122 F Idle batteries must be rec...

Page 9: ...d its efficiency in on line mode can reach at maximum 93 The UPS not only pro vides safe reliable and uninterrupted power to your sensitive electronic equipment at all times but also produces greater...

Page 10: ...A UPS202N2000B035 2kVA UPS302N2000B035 3kVA 1 kVA 2 3 kVA SETUP ON OFF SETUP ON OFF 1 2 3 4 5 6 No Item Q ty 1kVA 2 3kVA 1 UPS 1 PC 2 User Manual 1 PC 3 Input Power Cord 10 A 1 PC 4 Input Power Cord 1...

Page 11: ...kVA 2 3kVA 1 UPS 1 PC 2 User Manual 1 PC 3 Input Power Cord 10 A 1 PC 4 Input Power Cord 16 A 1 PC NOTE 1 If there is any damage or anything missing please immediately contact the dealer from whom you...

Page 12: ...uttons 3 1 LED Indicators No LED Description 1 Indicates the output status 1 ON green There is output 2 OFF There is no output 2 1 ON red The UPS detects an internal fault or an environmental fault Yo...

Page 13: ...wersolutions com en mcis software center php or configure the SNMP card optional or ModBus card optional z z For manual battery test please press and hold the button for 3 seconds release it after you...

Page 14: ...turn off its output 2 Fault Clear When the UPS has a fault condition press and hold the button for 3 seconds release it after you hear one beep and the UPS will clear the fault condition and return to...

Page 15: ...e AC input is within the acceptable bypass range 2 Flashing The AC input is out of the accep table bypass range but is still sufficient to let the unit operate in on line mode 3 OFF The AC input is ou...

Page 16: ...Buzzer Icon Illuminates when the buzzer is disabled 9 Warning Icon 1 ON The unit is shut down due to an internal fault or an environmental fault The error code will appear on the 7 segment display Pl...

Page 17: ...ording to the load level 1 2 Flashing The bar graph flashes when there is an overload situation 11 Battery Level Bar Graph Indicates the status of battery level 1 ON The bar graph illuminates accordin...

Page 18: ...Icon Description 1 IN 1 IN V When the above two words illuminate together it means input voltage 2 IN Hz When the above two words illuminate together it means input frequency 2 OUT 1 OUT V When the a...

Page 19: ...ans that the UPS is under battery test 6 BATT 1 BATT When the above two words illuminate together it means the remaining battery capacity 2 BATT V When the above two words illuminate together it means...

Page 20: ...3 5 Flow Chart of the 7 Segment Display The following flow chart helps you to understand how to go through each display screen Here we take Standby Mode as an example Each of the display diagrams show...

Page 21: ...to view the next display Press the button for 0 1 second to view the next display Press the button for 0 1 second to view the next display Press the button for 0 1 second to view the next display Pre...

Page 22: ...tional 2 Output Socket Connect to your loads Output Socket_ 1 Output Socket_ 2 3 USB Port Connects to your computer You can monitor the UPS s status via your computer by installing the Virtual COM Por...

Page 23: ...tion to its connected loads 5 3 Bypass Mode In bypass mode the critical loads are directly supplied by the utility power and the batteries are charged 5 4 Battery Mode When the UPS is operating during...

Page 24: ...meter 3 Press the button for 0 1 second to confirm your parameter 4 Press the button for 0 1 second to go to the next setup item 5 You can skip to the next setup item by pressing the button for 0 1 se...

Page 25: ...l can perform setup action Setup Mode Flow Chart Original Display T 3 seconds T 3 seconds T 0 1S T 0 1S T 0 1S T 3 seconds T 0 1S T 0 1S T 3 seconds T 0 1S T 0 1S T 0 1S T 3 seconds T 0 1S T 0 1S T 0...

Page 26: ...l turn on the UPS Just press and hold the button for 3 seconds release it after you hear one beep and the UPS will start up and run in battery mode 6 3 Turn off Procedures 1 In on line mode if you wan...

Page 27: ...m beeps once every 2 1 seconds 2 Overload_125 150 The audible alarm beeps once every 0 6 seconds 5 Fault The audible alarm beeps continuously for 5 seconds when the UPS detects an internal fault NOTE...

Page 28: ...creases the quantity of dry contacts 4 Mini ModBus Card Lets the UPS have ModBus communication function 5 Mini TVSS Card Lets the UPS have surge protection function NOTE 1 For detailed installation an...

Page 29: ...blem The more detailed description of the problem the better 3 When you see the following problems occur please follow the solutions shown below A About the error codes shown on the 7 segment Display...

Page 30: ...Output has a short circuit issue 1 Check whether the output has a short circuit issue 2 Contact service personnel Sd1 RPO Shutdown Remote shutdown is executed from dry contact After the remote shutdo...

Page 31: ...e internal battery cables and connect them firmly 3 Weak Battery Battery Replacement Batteries are damaged or battery life time is due Contact service personnel 4 Abnormal Input when the AC icon is fl...

Page 32: ...rs the battery life depends on the temperature the usage and the charging discharging frequency High temperature environments and high charging discharging frequency will quickly shorten the battery l...

Page 33: ...please check if each fan works normally and make sure if the ventilation air can move freely around and through the UPS If not contact service personnel NOTE Please ask your local dealer or customer s...

Page 34: ...uency 50 60 Hz 10 Hz Power Factor 0 99 full load iTHD 3 Output Power Factor 0 9 Voltage 220 230 240 Vac Voltage Regulation 2 linear load Frequency 50 60 Hz 0 05 Hz vTHD 3 linear load Overload Capabili...

Page 35: ...x 1 USB Port x 1 Physical Dimensions W D H 145 x 320 x 225 mm 190 x 390 x 325 mm 190 x 390 x 325 mm Weight 9 Kg 18 6 Kg 24 4 Kg Environment Operating Temperature 0 40 C Relative Humidity 5 95 non cond...

Page 36: ...ge maintenance or irresistible force i e war fire natural disaster etc and this warranty also expressly excludes all incidental and consequential damages Maintenance service for a fee is provided for...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...5013226702...

Reviews: