Delta-Therm Corporation 6711 Sands Road Ste A, Crystal Lake, IL 60014 www.delta-therm.com 800-526-7887
CA_SR_PCK-RG_
2002
_DS
stripping the cable
(Detail 1)
1. Score and remove 3" (8cm) of the black overjacket to
expose the braid.
2. Carefully separate 3" (8cm) of braid back to the over-
jacket, then twist the braid into a cold lead. Trim the cold
lead to remove the tapered end.
3. Remove 1" (3cm) of gray over jacket from the end ex-
posing the black conductive core.
4. Cut out the center of core material .125" wide x .75" long
(.32 x 2cm).
5. Strip conductive core .25" (.64cm)
from the end of
each bus wire, using a wire stripper or utility knife.
Detail 1
.
Stripping.
WARNING: This kit and the cable used with it must be installed by a qualified electrician. All
assembly, installation, and test instructions must be followed. Improper installation can result
in property damage, serious injury, and/or death due to electric shock and fires. Please call
Delta-Therm Corporation at 1-800-526-7887 with any installation or operating questions.
Detail 2.
Trim End of Cable.
Detail 3.
Heat Shrink Cap.
enD cap termination
(Detail 2 anD 3)
1. Remove 3” (8cm) of black over jacket and braid from
end. Cut braid off.
2. Trim the end of the heating cable so that one bus wire
is .25” (.64cm) shorter than the other. Caution: Do not
terminate self-regulating cable by connecting the two
bus wires. Doing so will destroy the cable. If you have
any questions, please call 1-800-526-7887.
3. Slide the heat shrink cap over the end of the cable, leav-
ing .5” (1cm) from end cap to black
overjacket exposed.
4. Using a heat gun, shrink the sleeve into place. Heat until
glue begins to flow from cap.
5. Apply silicone sealant over .5” (1cm) exposed area cov-
ering edge of overjacket and braid.
WArNINg
.5”
(1cm)
1.5” (4cm)
1 (3cm)
.75”
(2cm)
.25”
(.64cm)
Braid
Cut at a 45° Angle
Gray Insulation
Overjacket
3” (8cm)
Silicone Sealant
Heat Shrink Cap