4421 Tradition Trail ● Plano, Texas 75093 ● 972-964-2700 ● 800-836-7472 

URL:  

www.iscenclosurecooling.com

 ● Email:  

[email protected]

 

SP-ENG-211-100-11 Rev 1.8        | 

P a g e

                                                                                   

Title: 

EL-20B Air Conditioner for Class I, Division 2 Hazardous Locations Technical Manual

 

 

Department: 

Engineering 

 

Objective: 

To provide important information for maintenance, diagnostics and advance operations of the 

DELTA-T EL-20B Series Air Conditioners. 
 

Revision History: 
 

Rev 

Date 

Owner 

Description of Changes 

1.0 

02-01-18 

B. Slotnick 

Initial Release 

1.1 

05-24-18 

B. Slotnick 

Updated warranty & RMA procedure 

1.2 

09-06-18 

B. Slotnick 

Revised minimum anti-short cycle delay & updated Remote 
Controller option description 

1.3 

09-24-18 

B. Slotnick 

Updated warranty & unit specifications 

1.4 

02-21-19 

B. Slotnick 

Updated mounting instructions, alarm settings & RMA 
procedure 

1.5 

06-20-19 

B. Slotnick 

Updated preliminary testing instructions & compressor 
protection default setting 

1.6 

08-20-19 

B. Slotnick 

Updated preventative maintenance & warranty information 

1.7 

01-02-20 

B. Slotnick 

Updated field serviceable parts 

1.8 

06-03-20 

B. Slotnick 

Updated System Faults, Alarm Signals & Warranty 

 
Statement of Confidentiality 

The Manual and other materials contain proprietary information, comprising ISC Sales, Inc.'s trade secrets. 

Please maintain the confidentiality of all proprietary information during and after the term of the use agreement. 

Also, please refrain from using this proprietary information in any other manner, including in any other 

business, without ISC Sales, Inc

.’s written approval. 

 

ISC Sales, Inc. reserves the right to revise and otherwise modify the Manual to reflect changes in the 

requirements, standards, and operating recommendations. The Manual is the sole property of ISC Sales, Inc. 

It must be returned upon the expiration or the termination of the term of use agreement. 

 

By accepting the Manual you have read and understand the Statement of Confidentiality and will abide by its 

terms and conditions. 

 

Summary of Contents for EL-20B Series

Page 1: ...User Technical Manual EL 20B Series for Class I Division 2 Hazardous Locations Rev 1 8 ...

Page 2: ...tructions compressor protection default setting 1 6 08 20 19 B Slotnick Updated preventative maintenance warranty information 1 7 01 02 20 B Slotnick Updated field serviceable parts 1 8 06 03 20 B Slotnick Updated System Faults Alarm Signals Warranty Statement of Confidentiality The Manual and other materials contain proprietary information comprising ISC Sales Inc s trade secrets Please maintain ...

Page 3: ...ng the Air Conditioner 5 Unit Label 5 Operation 5 Preliminary Testing 8 Mounting the Air Conditioner 9 Unit Specifications 10 Options 12 System Faults 14 Digital Temperature Controller Programming 14 Preventative Maintenance 17 Field Serviceable Parts 18 Safety Information 18 Troubleshooting Guide 19 Physical Dimensions 22 Electrical Schematic 24 Warranty Information 25 Return Material Authorizati...

Page 4: ...ment DELTA T air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect your equipment upon receipt to ensure that there is no visual or hidden damage Upon receipt of the equipment ensure that it is always top side up as indicated by THIS SIDE UP labels This ensures that the compressor oil is ...

Page 5: ... the template below and keep this information in a safe place for warranty and ordering parts To prevent damage to equipment electrical panel and wiring and to prevent personal injury assure that the power source is compatible with the equipment before operating When recharging refrigeration type and amount must be the same as shown on the unit label or air conditioner will not operate properly or...

Page 6: ... THIS APPARATUS IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A B C AND D HAZARDOUS LOCATIONS OR UNCLASSIFIED LOCATIONS ONLY WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOW TO BE FREE OF IGNITABLE CONCENTRATIONS AVERTISSEMENT RISQUE D EXPLOSION AVANT DE DECONNECTER L EQUIPEMENT COUPER LE COURANT OU S ASSURER QUE L EMPLACEMENT EST DESIGNE...

Page 7: ... ST 22 manufactured by SEKI Controls Co Enclosure Manufacture of Material LG Chemical Ltd Designation of Material Type GP 2306F Epoxy Manufacture of Material Rhenatech GbmH Designation of Material Type EP VERGUSSMASSE 5315 Generic Name of Plastic Material epoxy resin Sealed Device Fan Motor Thermal Protector Type S01 manufactured by Thermik Geraetebau GMBH Insulation Cap Manufacture of Material E ...

Page 8: ... in 3 minutes If desired change the cooling set point Refer to Digital Temperature Controller Programming section on this manual for details on changing the set point Factory default settings should be satisfactory however you may want to adjust heat cooling and alarm set points for your specific application The condenser fan is controlled by the refrigerant high heat pressure and will turn on lat...

Page 9: ... from inside the enclosure use the fasteners supplied to attach the air conditioner to the enclosure Screw all fasteners hand tight Then torque to 96 in lbs These fasteners should be checked periodically to ensure that they have not become loose due to vibration The air conditioner is provided with a power cord or a power terminal block Ensure that the power supplied is compatible with the air con...

Page 10: ... Short Circuit Current Rating Amps Recommended Circuit Protection Amps KVA Rating Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi EL 20B 236 207 253 76 3 13 7 2 30 Amp Class CC CCMR Time Delay 3 3 R438a 64 95 327 EL 20B 486 414 506 38 2 6 9 2 15 Amp Class CC CCMR Time Delay 3 3 R438a 64 95 327 HACR Type Circuit Breakers or Time delay Fuses with the following electrical chara...

Page 11: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 8 11 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Page 12: ...will activate to notify you that there is a problem in achieving your cooling set point Default Settings 105 F Dry Contact High Temperature Alarm Set Point 2 F Recovery Differential 3min Temperature Alarm Delay At the default settings the contact initial condition is normally open When the unit is powered on and the temperature exceeds 105 F for a period longer than 3 minutes the contact will acti...

Page 13: ... Controller Programming section for details on all default settings Adjustable Temperature Probe The adjustable temperature probe provides you with a 12 temperature probe that can be installed anywhere in your enclosure This allows you to have the flexibility to monitor and maintain the temperature at any specific location of your enclosure Remote Controller When having our Programmable Digital Co...

Page 14: ...inute time delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is on but is not flashing and the compressor is not running an internal fault may have occurred Refer to the Troubleshooting Guide in this manual Digital Temperature Controller Programming For the end user this section will provide all the necessary information to view and change a...

Page 15: ...ue 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without pressing a key Note The set value is stored even when the procedure is exited by waiting for the time out to expire HOW TO LOCK THE KEYPAD 1 Press and hold the UP and DOWN arrow keys simultaneously for more than 3 se...

Page 16: ...larm Only 2 HA2 Condenser High Temperature Alarm P2 164 F for 3 minutes Compressor turned Off by pressure switch if temperature continues to rise 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Action Alarm Only 2 CA Evaporator Coil Alarm Low Pressure for 2 minutes Compressor Off 2 noP Invalid Probe Selected Low Evaporator Coil No Action Alarm Only 2Note When both Heater and Dry Con...

Page 17: ...ded to enhance air filter efficiency Replacement filters are readily available from ISC Customer Service DO NOT operate the air conditioner without the air filter Such operation will allow the condenser coil to become dirty and lose efficiency causing overheating and diminished cooling capacity Periodically remove dust from the components inside the condenser section of the air conditioner with a ...

Page 18: ... Pressure Switch 38140 1 3 Temperature Probe 0 25m 52126 1 Temperature Probe 1 5m 52126 2 2 Temperature Probe Mounting Clip 52126 375C Condenser Fan Relay 55754 1 Thermal Expansion Value TXV 32010 1 Compressor 31076 1 Compressor Thermal Overload Internal Gasket Installation Kit 71405 HC20 Evaporator Fan Motor 41062 2 1 Condenser Fan Motor 41060 2 1 Filter Media 44260 12 pack Note 3 filters are use...

Page 19: ...ower If problem is still present contact technical support Unit Overheats Insufficient Cooling Is Filter Clean NO Clean Replace Filter YES Are Condenser Evaporator Fans ON NO Check for Faulty Fan replace YES Is Condenser Coil dirty YES Clean Coil NO NO Is Evaporator Coil Frozen Iced YES Potential Bad Evaporator Fan check for faulty fan NO Contact Qualified Refrigeration Service Technician to check...

Page 20: ...Fan on YES NO Is there voltage to compressor Use meter3 Check for faulty evaporator fan3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Check for error code CA LA HA LA2 HA2 P1 or P2 NO Check contactor circuit Does it have power 3 NO YES Refer to Alarm Signals in Digital Temperature Controller Programming Se...

Page 21: ...controller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer to Alarm Signals in Digital Temperature Controller Programming Section Fuse Circuit Protection Nuisance Trip Is fuse opening as soon as unit turns on NO YES Check incoming power supply and connections for ...

Page 22: ... Physical Dimensions Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed against enclosure properly tightly sealed and door closed YES Contact Customer Service NO Ensure air tight seal between air conditioner and enclosure Make sure door is closed ...

Page 23: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 8 23 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Page 24: ...P ENG 211 100 11 Rev 1 8 24 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in this document If you require electrical schematic with options contact our technical support and provide your model number Controller 1 3 4 5 ...

Page 25: ...t at the ISC factory in Dallas Texas Use of equipment for other than its designed purpose or operating conditions Operation in harsh oily corrosive or other abnormal environmental conditions without the proper filtration sealing protective coatings and or weather protection or cosmetic corrosion that does not affect operation Damage to hermetic system resulting from continuous operation with dirty...

Page 26: ...nd contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available If suitable packing is not available arrange for packaging to be shipped to you Air Conditioners must be returned in an upright position properly secured to a pallet Tip unit to empty water from the evaporator and boil off pans Clearly mark the ...

Page 27: ... wires to air conditioners equipped with a Wago power terminal block 1 Remove cover from chassis using T25 Torx bit 2 The sequence of the connecting the wires is from LEFT TO RIGHT 3 Connect each wire as shown by lifting the lever and inserting the wire into the receptacle directly below Snap the lever down to secure the wire in place 4 If wires need to be removed raise the lever directly above ea...

Reviews: