Delta-q QuiQ Product Manual Download Page 2

Operating Instructions

CAUTION

: Charger enclosure may be hot during charging. Use hand protection if handling the charger while charging.

 

­

Extension cords must be 3-wire cord no longer than 30m(100’) at 10AWG or 7.5m(25’) at 16AWG per UL guidelines.

 

­

Only connect 

ONE

 QuiQ charger to a single 15A circuit or the circuit may become overloaded.

 

­

Charger 10-LED Display

Delta-Q QuiQ Charger Manual

2

www.delta-q.com

Fault Indicator (

Red Light

)

 

­

Charger error. Refer to troubleshooting information below.

 

­

If solid: AC power is present.

 

­

If flashing: Low AC voltage. Check electrical source and cord length.

AC Indicator

Bulk Charge Indicator

 

­

If solid: Bulk charge phase complete (80% charged); in absorption phase.

 

­

If flashing: Displays charge profile number if no battery is connected.

Charge Completion Indicator (

Green Light

)

 

­

If solid: Charging complete and maintenance mode is active.

 

­

If flashing: Absorption phase complete, in finishing phase.

 

­

If solid: Displays 
scale of output 
during bulk phase.

 

­

If flashing: Output 
has been reduced 
due to high internal 
charger temperature. 
Displays charge 
profiles 1-6 for 11 
seconds if no battery 
is connected.

Ammeter

Troubleshooting Instructions

If a fault occurs, count the number of red flashes between pauses and refer to the table below.

Flashes

Cause

Solution

Charge enable fault or;

Battery temperature fault

Check connector contacts and retry. 

Check that battery temperature is between -10

o

and +50

o

C

Battery voltage too low or high

Check that battery voltage is between 36.0V and 

55.2V and retry. 

Check voltage during charge is < 67.2V.

Charge timeout caused by battery 

pack not reaching required voltage; 

or charger output reduced due to 

high temperatures.

Check connections, that battery type matches 

selected charge profile and operate the charger at 

a lower ambient temperature. Reset the charger by 

interrupting AC power for 15+ seconds.

Battery could not be trickle charged 

up to minimum voltage.

Check for shorted or damaged cells. Reset the char-

ger by interrupting AC power for 15+ seconds.

Charger shutdown due to high 

internal temperature.

Ensure sufficient cooling airflow. Reset the charger 

by interrupting AC power for 15+ seconds.

Internal charger fault

Reset the charger by interrupting AC power for 15+ 

seconds. Return to service depot if fault persists.