Installation and Operating Manual
IP277, Rev DA
Mobrey MCU200 Series
February 2020
Figure 3. MCU200 housing dimensions
3.3
External connections
Two cables are required per sensor. The RG178 should be used where the cable itself is subject
to temperatures exceeding 74 °C.
Note
Protection for permanently installed equipment:
This equipment is regarded as permanently installed equipment and must be wired up using
suitable cable for the current and voltage specified. A suitable switch or circuit breaker must be
included in the installation and this should be in close proximity to the equipment and marked
as its disconnecting device. A suitable fuse rated at 3 A must be fitted in the supply. Each relay
circuit must be protected by a fuse not exceeding the maximum rated current for the relay as
specified in the manual. As S/C current on the transformer secondary is in the order of 70 mA
and the transformer thermal fuse will not operate for at least 17 minutes (as tested), a smaller
value mains fuse (63 mA) should be agreed upon.