Installation Instructions

Ground Water Pump Station

Delta Foul V3 (DMS-165-1)

For Foul Water Applications

This manual is to be left 

with the pump station or 

the homeowner

Summary of Contents for Delta Foul V3

Page 1: ...Installation Instructions Ground Water Pump Station Delta Foul V3 DMS 165 1 For Foul Water Applications This manual is to be left with the pump station or the homeowner...

Page 2: ...processed for any other purpose nor otherwise transmitted published or made available to a third party without express written consent from Delta Membranes Subject to technical modification without p...

Page 3: ...nlet pipework 11 Section C Connecting discharge cable duct and vent 12 Section D1 Backfill around chamber with concrete RC Box 14 Section D2 Backfill around chamber with concrete Ground 15 Section D3...

Page 4: ...high water tables The pump station is delivered as a complete package including all internal pipework and a D10SA foul vortex pump It is designed to be installed by contractors with competent building...

Page 5: ...amp 110mm to 2 BSP Female Thread including 2 Male Iron DMS 0151 Saddle Clamp 160mm to 2 BSP Female Thread including 2 Male Iron DMS 0152 2 Pipe Clip DMS 0159 500ml PVC Solvent Cement DMS 0158 Name Com...

Page 6: ...Pump DMS 120 6 Discharge Arm c w DC65 Connector DMS 129 6 Delta Foul V3 1 3 2 1 1 4 5 6 Part Description A Screed B Insulation C MS20 D Basement Slab E Inlet Pipe F Concrete Base G Manhole Cover H Fo...

Page 7: ...C 35 Weight kg 13 Chamber Specification Chamber Material High Density Polyethnylene ICO1314 grade Size mm Chamber Diameter 660 Overall Diameter 902 across spigots Depth 800 Volume L Below Inlet 137 T...

Page 8: ...m below floor finishes A pump chamber installed more than 500mm below floor finishes cannot be serviced safely in accordance with CDM regulations If the inlet does not allow the pump chamber to be wit...

Page 9: ...damage to the pump station either during or after installation Please read these instructions carefully prior to installing the chamber If there is anything that is unclear our technical help desk is...

Page 10: ...arge pipework Allow pipework to protrude into RC box by a minimum of 100mm 1 3 11 0 Installation of Chamber Section A Install re bar as per structural engineer s drawings Pour concrete to form RC box...

Page 11: ...Section B Saw off socket end s where inlet pipe s are to be connected Fit push fit coupler 5 7 Position chamber in RC box 6 Connecting 110mm inlet pipework Connect inlet pipework to the required chamb...

Page 12: ...e around the first 20mm of the external face of the discharge cable duct and vent pipe and internal side of their respective male iron 9 11 Screw the high pressure male iron into the socket Push disch...

Page 13: ...11 0 Installation of Chamber Section C cont Ensure a draw cord is pulled through the cable duct as the cable duct is built 13 Connecting discharge and cable duct Delta Foul V3 13...

Page 14: ...oncrete To be followed when installing chamber in an RC box Check all pipes are connected to the chamber correctly Fill void between RC box and chamber with concrete min C35 grade or as per engineer s...

Page 15: ...etween soil and chamber with concrete min C35 grade or as per engineer s drawings 18 Completely fill chamber with water 17 Backfill around chamber with concrete To be followed when installing chamber...

Page 16: ...d chamber with concrete min C35 grade or as per engineer s drawings 21 Completely fill chamber with water 20 Backfill around chamber with concrete To be followed when installing chamber in the ground...

Page 17: ...a Foul V3 11 0 Installation of Chamber Section E Preparing chamber for installation of pump Pump out water from chamber 23 Manually remove any debris from chamber and residual water using a wet vac 24...

Page 18: ...allation of Chamber Section F Hand tighten the discharge arm into the pump discharge outlet 26 Wrap the thread on the nipple glued in to the 90 bend with PTFE tape 25 Fitting discharge to pump Delta F...

Page 19: ...to release any trapped air Slide the DC65 up to join the manifold to the discharge arm 28 Fill chamber half full with water 27 Installing pump and high level alarm in chamber Tighten the two screws on...

Page 20: ...o allow for maintenance 31 Isolate mains supply and connect the pump and high level alarm according to the wiring diagram overleaf 32 Turn mains supply on and lift the pump float to test the water is...

Page 21: ...cable attached to the pump the cable duct should be no longer than 6m If the cable duct requires to be longer than 6m please follow the cable extension guide to select an appropriate cable core diamet...

Page 22: ...to be longer than 6m please follow the cable extension guide to select an appropriate cable core diameter Pendant Float Switch Supplied with a 10m cable The electrical installation must comply with t...

Page 23: ...d be no eating or drinking during works and only afterwards following a change of clothing and washing Ensure electrical power to the pump is turned off isolated before carrying out installation or ma...

Page 24: ...top of the pump remove pump from DC65 and lower back into water lift float to activate pump before reconnecting the DC65 Discharge pipe is blocked a drainage company is required Pump is tripping Pump...

Page 25: ...25 Delta Foul V3 Notes...