INSTALLATION
ISO AMP
4 / 7
DELTA ELEKTRONIKA B.V.
rev. Febr. 2021
4
INSTALLATION
Warning!
carefully read the chapter "Safety Instructions" in
this manual before connecting or operating the unit!
4.1
HUMIDITY & CONDENSATION
During normal operation, humidity will not harm the interface,
provided the air is not aggressive. The heat normally
produced in the power supply will keep it dry.
Avoid condensation inside the interface, to prevent break-
down. Condensation can occur during a period the interface
or power supply has been switched off (or operating at no
load) and the ambient temperature is increasing. Always allow
the interface to dry before switching it on again.
4.2
TEMPERATURE & COOLING
The storage temperature range is
–40 to +85 °C.
The operating temperature range is
–20 to +50 °C.
Please note: a lower temperature extends the lifetime of the
interface.
4.3
INSTALLING THE ISO AMP MODULE
Mount the ISO AMP MODULE using the wall or rail mounting
adapter.
Connect the power supply to the ISO AMP MODULE with the
supplied 15 pole cable.
Connect a 15-30 V DC supply voltage to the 2-pole
connector. + and - are indicated on the module, see fig 4 -1.
Finally connect your programming source to the connector
marked ‘TO PROG. SOURCE’, see fig 4 -1 and fig 4 - 2.
For use with other units than Delta Elektronika power
supplies, make sure to connect pin 1 to pin 8 on the
connector 'To Power Supply', see fig 4 - 3.
4.4
WALL OR RACK MOUNTING
Use the included mounting plate, see fig 4 - 4, for attaching
the module to a rack or a wall.
No special cooling is required, the module does not heat up
more than 10 degrees above ambient temperature.
4.5
INSTALLING THE ISO AMP CARD
The ISO AMP CARD should always be factory installed and
calibrated together with the power supply.
Contact factory for more information.
For operation, connect a 15 pole cable to the ISO AMP
connector at the rear side of the power supply.
For the following steps, please advice the operating manual of
the power supply for exact details.
fig 4 - 2
To programming source.
fig 4 - 1
Front panel connections.
fig 4 - 3
To power supply.
fig 4 - 4
A wall mounting adapter is standard supplied with
the ISO AMP Module