Chapter 4 Parameter Settings
|
DD Series
4-52
Door Close
Holding Speed
Open Door (R EV)
Door Open Limi t
0.0%
100.0%
Close Door (FWD)
04.00
Door Open
Speed
by Ini tial
04.08
Door Open
Acceleration
Time 1
04.09
Door Open
Deceleration
Time 1
04.03
Door Open H igh Speed 1
04.05
Door Open
Final Speed
04.01
Door Open D istance
by Ini tial Speed
04.04
Door Open
Final Speed
by
Begi ns
04.06
Door Open
by Holding
Speed Begins
04.07
Door Open
Holding Speed
05.03
Door Close
High Speed 1
D oor Clos e
Accel er ation Time 1
05.05
05.04
05.06
Door Close
by Holding
Speed
Begins
05.07
05.09
05.01
Door Close
Distance by
Ini tial Speed
05.00
Door Close
Ini tial Speed
Door Close Limit
Door Close
Final Speed
Door Close
Final Speed
Door Close
by Final Speed
Begi ns
05.08
Door Close Holding Torque
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 20.0
Settings 0.0~100.0% (Drive’s rated current)
Response Time of Door Close Holding Torque
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.20
Settings 0.01~10.00sec
When the door is in the close complete position, it needs holding torque to keep the door still in complete
position. To prevent motor overload, holding torque should be set within a limit.
Door Close High Speed 2
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 30.00
Settings 0.00~120.0Hz
Door Close Acceleration Time 2
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 1.0
Settings 0.1~3600sec
Door Close Deceleration Time 2
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 1.0
Settings 0.1~3600sec
Door Close Holding Torque Level 2
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~150.0% (Ac drive’s rated current)
Door Close Time-out Setting
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~180.0sec
(0.0sec:Disable)
When the time for door closing is longer than the setting in Pr.05-17, door will re-open.
Holding Time for CD (Close Door)Terminal
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~999.9sec (999.9sec is always holding)
This parameter is used to clear the CD terminal signal (door close signal) when door open complete.
During the holding period, AC Motor Drive will still be in RUN status. After holding time, AC Motor Drive