Device Settings 

1.

 

Check the Modbus RTU slave address settings. 

The Modbus RTU slave address is set by DIP switch from [2] to [5] in the back of UNOnext. The DIP definition 

corresponding to the slave address is shown as below table. 

Modbus Salve Address 

PIN No. of DIP switches   

Decimal  Hexadecimal 

208 

0xD0 

 

 

 

 

209 

0xD1 

 

 

 

 

210 

0xD2 

 

 

 

 

211 

0xD3 

 

 

 

 

212 

0xD4 

 

 

 

 

213 

0xD5 

 

 

 

 

214 

0xD6 

 

 

 

 

215 

0xD7 

 

 

 

 

216 

0xD8 

 

 

 

 

217 

0xD9 

 

 

 

 

218 

0xDA 

 

 

 

 

219 

0xDB 

 

 

 

 

220 

0xDC 

 

 

 

 

221 

0xDD 

 

 

 

 

222 

0xDE 

 

 

 

 

223 

0xDF 

 

 

 

 

 

2.

 

Check the UART settings. 

The UART settings for UNOnext as: 

 

Baud:  9600  by  default,  also  supports  38400,  57600,  115200  modified  by  Modbus  RTU  protocol.  (See 

UNOnext Modbus RTU) 

 

Data-bit: 8 

 

Parity: None 

 

Stop-bit: 1 

3.

 

If  the  UNOnext  daisy-chained  for  longer  distances,  please  pull  up  the  DIP  switch  [1]  to  enable  Modbus 

terminal resister to try. 

4.

 

Try a factory reset. 