Device Settings
1.
Check the Modbus RTU slave address settings.
The Modbus RTU slave address is set by DIP switch from [2] to [5] in the back of UNOnext. The DIP definition
corresponding to the slave address is shown as below table.
Modbus Salve Address
PIN No. of DIP switches
Decimal Hexadecimal
2
3
4
5
208
0xD0
209
0xD1
210
0xD2
211
0xD3
212
0xD4
213
0xD5
214
0xD6
215
0xD7
216
0xD8
217
0xD9
218
0xDA
219
0xDB
220
0xDC
221
0xDD
222
0xDE
223
0xDF
2.
Check the UART settings.
The UART settings for UNOnext as:
Baud: 9600 by default, also supports 38400, 57600, 115200 modified by Modbus RTU protocol. (See
UNOnext Modbus RTU)
Data-bit: 8
Parity: None
Stop-bit: 1
3.
If the UNOnext daisy-chained for longer distances, please pull up the DIP switch [1] to enable Modbus
terminal resister to try.
4.
Try a factory reset.