background image

Z

 

Electrical Specifications

 

Specifications 

TP02G-AS1 

Display 

Monochromatic STN LCD 

Effective Display Area 

(W) x (H) = 72 x 22 (unit: mm) 

Display Resolution 

160

×

32: ASCII: 5

×

8, 8

×

8, 8

×

12, 8

×

16 

LCD Contrast Adjustment 

Set by Software, adjust the contrast by the press button in the function table 

LCD Backlight Type 

LED Backlight: Automatic Turn-off Setting 

Function / Numeric Keys 

F0 / 0 ~ F9 / 9, ESC, ENTER

 

and Arrow Keys 

External Input Power 

24V (3W Max.)   

Memory Capacity 

256K Byte 

CPU Hitachi 

HD64F3064F 

RAM of System 

32K Byte 

Communication Interface 

COM1: RS-232    COM2: RS-485 

Waterproof Class of Front 

Panel 

IP65 / NEMA4 

Operating Temperature for 

Hardware 

0 ~ 50°C; 20 ~ 90

RH (non-condensing)   

Storage Temperature for 

Hardware 

-20 ~ 60°C 

Vibration 

5Hz

f

9Hz = Continuous: 1.75mm / Occasional: 3.5mm   

9Hz

f

150Hz = Continuous: 0.5g / Occasional: 1.0g 

Shock 

15g peak, 11ms duration, half-sine, three shocks in each direction per axis,   

on 3 mutually perpendicular axes (total of 18 shocks) 

Radiated Emission 

CISPR11, Class A 

Electrostatic Discharge 

Immunity  

EN61000-4-2 

Radiated Immunity   

EN61000-4-3 

Electrical Fast Transient   

EN61000-4-4 

Weight / Dimensions 

0.24kg; 147×97×35.5mm (Width(W) × Height(H) × Deep(D)) 

Cooling Method 

Natural Air Cooling 

[

 

Program Copy Card

 

TP02 series provides Program Copy Card Function to copy user program, system function and passwords that is 

different from the copy program. It is used to copy the whole HMI environment settings and application programs 

to another HMI rapidly. Using Program Copy Card saves time and manpower. The operation is as follows. 

™

 

Definition: Program Copy Card 

 PCC, TP Series 

 TP 

 

(TP

PCC) 

(PCC

TP) 

Step 1 

Turn the switch on the PCC to TP 

Æ

PCC 

Turn the switch on the PCC to PCC

Æ

TP 

Step 2 

Insert the PCC into the extension slot of TP   

Insert the PCC into the extension slot of TP 

Step 3 

Input the power to TP 

Input the power to TP 

Step 4 

It will display “remove PCC” on the screen and 
power on again.   

It will display “remove PCC” on the screen and 
power on again.   

™

 

HMI Display Message 

 

(TP

PCC) 

(PCC

TP) 

Step 1 

If the TP model type does not correspond with the 
model type of program of PCC, TP will display “TP 
series and PCC is different. Press Enter to 
Confirm TP series

PCC. Press Esc to Exit”. 

If there is no program in PCC, TP will display “The 
PCC is Empty. PCC

TP series is illegal”. 

Step 2 

TP will display “TP

PCC series Please wait!” 

during transmission. 

TP will display “PCC

TP series Please wait!” 

during transmission. 

Step 3 

TP will display “Please Remove the PCC and 
Reboot” when transmission is completed. 

TP will display “Please Remove the PCC and 
Reboot” when transmission is completed. 

\

 

Password Function

 

If the user forgot the password, the password can be cleared by using the following code: 

8888

. This universal 

code will clear the password and all TP02 series internal programs. The TP02 series will be reset to the factory 

settings by using this code also. Please pay close attention when using it.

 

™

 

The password can be the alphabet from A to Z or the number from 0 to 9. But it must use the function 
keys F0 ~ F9 to input the password characters. Please refer to the following table. 

Function Key 

Use Method 

Function Key 

Use Method 

F0 

scrolls in a loop as follows 
0

A

B

C

D

E

F

0  

F5 

It just can be used to be constant 5. 

F1 

scrolls in a loop as follows 
1

G

H

I

J

K

F6 

It just can be used to be constant 6. 

F2 

scrolls in a loop as follows 
2

L

M

N

O

P

2  

F7 

It just can be used to be constant 7. 

F3 

scrolls in a loop as follows 
3

Q

R

S

T

U

 V

F8 

It just can be used to be constant 8. 

F4 

scrolls in a loop as follows 
4

W

X

Y

Z

4  

F9 

It just can be used to be constant 9. 

]

 

Hardware Operation

 

When the user wants to startup TP02 series, a 24VDC power is needed. After applying 24VDC power to TP02 

series, it will enter into the startup display and then enter the user-designed program. Pressing Esc key and 

holding on for 5 seconds can return to system menu. There are five selections in the system menu and are 

described below.

 

SELECTIONS 

EXPLANAION 

Download Program 

Use the connection cable (DVPACAB530) to connect the TP02 serial communication 
port RS-232 to a PC. Then use the TPEdit software to download an application 
program to TP02. 

Upload Program 

Use the connection cable (DVPACAB530) to connect the TP02 serial communication 
port RS-232 to a PC. Then use the TPEdit software to upload an application 
program from

 

TP02.

 

Copy Program 

Transfer a program between two TP02 units. 
1: transmit programs 
2: receive programs 
When transmit programs and data between two TP02 units. Set one TP02 to 
“Receive Program” mode and the other TP02 to “Transmit Program” mode. Please 
use twisted pair wires to connect the two units via the RS-485 ports. 

TP02 Settings 

There are 8 items that used to modify TP02 system settings: 
1.  Communication protocol: Setting the address of TP02, the control port of PLC, 

and the communication string for either RS-232 or RS-485. 

2. Contrast: 

Adjust 

the 

contrast of LCM display screen. 

3.  Back-light: adjust the automatic turn off time of LCM. Setting range is 00 ~ 99 

minutes. If set to 00, the LCM Back-light will not turn off. 

4.  Buzzer: Used to set the buzzer sound, normal mode or quiet mode. 
5.  Language Setting: Used to set the displayed language. English, Traditional 

Chinese, Simplified Chinese or user defined language. 

6.  Password setting: Used to set, enable, and disable the password function. If the 

password function is enabled, it will require the user to input a password before 
entering any system menu. The factory password is 

1234

7.  Startup display: Used to select the TP02 startup display. User can select “user 

defined” to use the file that designed by TPEdit and download to TP02. 

8.  Comm. indicator: The user can determine if the RS-232 and RS-485 LEDs will 

blink or not during communication.   

PLC Connection 

There are two methods to connect to PLC: 
1.  Using TP02 serial communication port (COM1) RS-232: set 8-pin DIP switch to 

RS-485 mode and connect the cable (DVPACAB215 or DVPACAB230) to 
program communication I/O RS-232C of PLC. 

2.  Using extension communication port (COM2) RS-485: set 8-pin DIP switch to 

RS-485 mode and connect 5-pin removal terminal of extension communication 
port to RS-485 of PLC with twisted pair. 

Execution 

Execute the internal program that download from TPEdit or transmitted from other 
TP02 units. When program is in execution, the user can return to system menu by 
pressing Escape / Exit (Esc) key for 5 seconds. 

^

 

Communication Connection

 

™

 

TP02G may connect to a PC by using connection able DVPACAB515

 

PC or TP02 / 04G

1

5

6

9

9 PIN D-SUB

TO PC (RS-232)

TO TP02  / 04G

5

1

9

6

9 PIN D-SUB

   

9  PIN D-SUB female

Rx        2

GND     5

5       GND

PC  COM Port

9  PIN D-SUB female

3       Tx
2       Rx

TP02 / 04G COM Port

Tx        3

 

™

 

TP02G may connect to a DVP-PLC by using connection cable DVPACAB215 / DVPACAB230 / 
DVPACAB2A30

 

1. DVPACAB215 

DVPACAB230 

TO  PC or TP02 / 04G 

1

13

14

1

5

6

9

25 PIN D-SUB

9 PIN D-SUB

TO PLC

MINI DIN TERMINAL 

 

 
 
 

2. DVPACAB2A30 

TO  PC or TP02 / 04G 

1

5

6

9

9 PIN D-SUB

TO PLC

MINI DIN TERMINAL 

 

8 PIN MINI DIN

25 PIN D-SUB female

PC / TP COM Port

PLC COM1 Port

Tx        2

GND

7

    

8 PIN MINI DIN

9 PIN D-SUB female

PC / TP COM Port

PLC COM1 Port

Rx        2

GND    5

6

8

20

4

5

1

4

6

7

8

4       R x 

8       GND
1,2    5V

1

2

3

4

5

6

7

8

5       Tx

Rx       3

Tx       3

  

 

1

2

3

4

5

6

7

8

4       R x 

8       GND
1,2    5V

5       Tx 

 

™

 

The Pin definition of 9 PIN D-SUB

 

3       Tx 

5       GND

RS-232  9 PIN D-SUB male

TP02 / 04G COM Port

2       Rx 

 

_

 

Battery Life

 

™

   

Battery Life 

Temperature (°C) 

-20 

20 

60 

Life 

(Year)  1.972 2.466 2.712 2.835 

 

 

 

 

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or 

download the most updated version at 

http://www.delta.com.tw/industrialautomation

 