How to Install DIN Rail

 

DVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and 7.5mm in depth. When 

mounting PLC to DIN rail, be sure to use the end bracket to stop any side-to-side movement of PLC and reduce the 

chance of wires being loosen. A small retaining clip is at the bottom of PLC. To secure PLC to DIN rail, place the 

clip onto the rail and gently push it up. To remove it, pull the retaining clip down and gently remove PLC from DIN 

rail. 

ƒ

 

Wiring 

22-16AWG

< 1.5mm

 

1.  Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring 

terminals. The specification of the terminal is shown in the figure on 

the left. The PLC terminal screws shall be tightened to 1.95 kg-cm 

(1.7 in-lbs). 

2.  DO NOT place the I/O signal wires and power supply wire in the 

same wiring duct. 

3.  Use 60/75ºC copper wires only. 

 

 

 

DO NOT install PLC in an environment with: 

h

 Dust, smoke, metallic debris, corrosive or flammable gas 

h

 High temperature, humidity 

h

 Direct shock and vibration

 

3.4 Notes 

ƒ

 

During the Engineering 

1.  DO NOT drop tiny metallic conductor into the PLC when screwing and wiring. 

2.  There should be a margin of more than 50mm between the PLC and other control device and the PLC should 

be placed away from high voltage wire and power equipments. 

ƒ

 

Arrangement of I/O Points 

No matter the MPU with how many points you are using, the input point No. of the first connected extension unit 

has to start from X20 and output point No. from Y20. The connection of MPU and extension units is demonstrated 

in the figure below. 

 

PLC 

Model 

Input points 

Output points 

Input point No. 

Output point No. 

MPU 

SS/SA/SX/SC 

4/6 

X0 ~ X7 

Y0 ~ Y5 

EXT1 32SM11N 

32 

X20 

X57 

EXT2 32SN11TN 

32 

Y20 

Y57 

EXT3 32SN11TN 

32 

Y60 ~ Y77 

Y100 ~ Y117 

EXT4 32SM11N 

32 

X60 ~ X77 

X100 ~ X117 

 

ƒ

 

Input Point Wiring and Specification

 

The input signal is DC. There are 2 types of DC inputs, SINK and SOURCE. The wirings are as follows. 

SINK 

X1

X3
X5
X7

X11
X13
X15
X17
S/S

X0

X2
X4
X6

X10
X12
X14
X16

S/S

X21
X23
X25
X27

X31
X33
X35
X37
S/S

X20
X22
X24
X26

X30
X32
X34
X36

S/S

DVP32SM

DC24V

 

 
 
 

 
SOURCE 

X1
X3

X5
X7

X11
X13
X15
X17
S/S

X0
X2

X4
X6

X10
X12
X14
X16

S/S

X21
X23
X25
X27

X31
X33
X35
X37
S/S

X20
X22
X24
X26

X30
X32
X34
X36

S/S

DVP32SM

DC24V

 

ƒ

 

Transistor Output Circuit Wiring

 

NPN transistor output 

Y1
Y3
Y5
Y7

Y11
Y13
Y15
Y17

GND

Y0
Y2
Y4
Y6

Y10
Y12
Y14
Y16

GND

Y21
Y23
Y25
Y27

Y31
Y33
Y35
Y37

GND

Y20
Y22
Y24
Y26

Y30
Y32
Y34
Y36

GND

+24V

DVP32SN

+24V

+24V +24V

MC2

MC1

MC2

MC1

2

1

3

4

5

6

7

8

2

5

 

 

c

 

Emergency stop 

g

 

Incandescent light (resistive load) 

d

 

Fuse 

h

 

Reverse current protection diode (

*2

e

 

Manual exclusive output (

*1

i

 

Inductive load 

f

 

DC power supply 

j

 

Resistive load 

 
*1: Manual exclusice output uses external circuit and forms an interlock, together with the PLC internal program, to ensure 

safety protection in case of any unexpected errors. 

*2: Zener diode (39V) inside PLC protects the transistor output. When activating an inductive load, we suggest you 

parallely connect a reverse current protection diode. 

 

[

 

Trail Operation

 

ƒ

 

POWER Indicator 

The “POWER” LED indicator on the front panel of PLC MPU or extension unit will be on (in green) when the 

MPU is powered. That the MPU is powered but the indicator is not on indicates that the DC power supply of the 

PLC is abnormal. Please check if the terminal wirings of +24V and 0V are correct. That the “ERROR” LED 

indicator flashes continuously indicates that the +24V power supply for the PLC is insufficient. That the “L.V” 

indicator on the extension unit is on indicates that the input voltage for the power of the extension unit is 

insufficient and all outputs from the extension unit will be disabled. 

ƒ

 

Preparation 

Before powering, make sure that you have checked if the I/O wiring is correct. You may damage the PLC if 

AC110V or AC220V is directly supplied to input terminals or the output wiring is short-circuited. When the 

peripheral devices are used to write program into PLC and if the ERROR indicator does not flash, the program 

you are using is legal and PLC is waiting for RUN instruction from you. You can use HPP to test “force On/Off” of 

output contacts. 

ƒ

 

Operation & Test 

If the ERROR indicator does not flash, you can give RUN instruction to the peripheral device and the RUN 

indicator should be continuously on at this time. When PLC is in operation, use HPP to monitor the set value or 

temporarily saved value in the timer (T), counter (C), and register (D) and force On/Off of output contacts. That 

 

the ERROR indicator is on (not flashes) indicates that part of the program exceeds the preset time-out. In this case, 

you have to check the program and set On/Off of the power again (PLC automatically returns to STOP status at this 

time). 

 

\

 

How to identify abnormality of PLC

 

5.1 PLC 

Abnormality 

To identify abnormality from the indicators on the panel, please check:

 

ƒ

 

“POWER” Indicator 

When PLC is powered, the POWER LED indicator on the front panel will be on (in green). If the indicator is not 

on, check if the power supply is normal. If the problem still exists, your PLC is malfunctioned. Please change a 

new one or send your PLC back to your distributor for repair. 

ƒ

 

“L.V” Indicator 

That the “L.V” indicator on the extension unit is on indicates that the input voltage for the power of the extension 

unit is insufficient and all outputs from the extension unit will be disabled. 

ƒ

 

Input Indicator 

On/Off of input point is indicated by input indicator or by the monitoring function of the device. When the action 

criteria of the input point are true, this indicator will be on. If abnormality is identified, check if the indicator and 

input circuit are normal by HPP/WPLSoft. Use of electronic switch with too much electricity leakage often results 

in unexpected actions of the input point. 

ƒ

 

Output Indicator 

On/Off of output point is indicated by output indicator. When the output indicator (On/Off) does not correspond to 

the action of its load, please be aware of the follows: 

1.  The output contact may be melted or blocked out of overloading or short-circuited load, which will result in poor 

contact. 

2.  If you are suspicious that the output point may execute undesired action, check the output wiring circuit and 

whether the screw is properly tightened. 

5.2 Regular 

Check 

DVP series PLC does not utilize any disposable components; therefore, you do not need to replace most of the 

components with new ones. However, if the output relay is used for activating big current load, the life of output 

contact will be shortened. In this case, you will need to check whether the contact is in permanently “open circuit” or 

“short circuit” and note that:: 

1.  DO NOT place the PLC under direct sunlight and avoid placing it close to an over-heated object in 

case the high temperature will affect the functions of the PLC. 

2.  Clean the airborne dust or metallic particles in the panel on a regular basis. 

3.  Check regularly that if the wiring and terminals are tightened properly. 

5.3 Suggestions 

for 

Operation 

DVP series pin-headed digital extension unit is relatively more sensitive to the temperature in the operation 

environment; therefore, when using the unit, please note that: 

1.  The lift of I/O points will be shortened if the voltage and the temperature are too high in the external 

environment. 

2.  When the external voltage is larger than 24VDC, it is suggested that the output load current be reduced to 

below 0.1A. 

3.  To sum up, operate the unit in 55ºC/1A (COM), 25ºC/2.4A (COM); otherwise, the life of I/O points will be 

shortened. 