MVF2000 Fault Configuration Rules
Config.
value
Detection
enable
Alarm
/Fault
Action
Not running
Running
0
Disable
-
-
-
1
Enable
Alarm
No action
No action
2
Enable
Fault
No action
Coast stop
3
Enable
Fault
No action
Coast stop, and bypass system
4
Enable
Fault
No action
Deceleration and stop
5
Enable
Fault
No action
Trip MCB
6
Enable
Fault
No action
Trip MCB, and bypass system
7
Enable
Fault
Trip MCB
Trip MCB
8
Enable
Fault
Trip MCB
Trip MCB, and bypass system