background image

                                             

                                           

                                     Switch Mode Power Supply                                                                              DRP024V060W1BA

 

 
 

5/13 

 

 

Rev: 00, 

1/10/2011 

 

 

 

Block Diagrams/Connections: 

 

Block Diagram of Power Supply, 
 

 

DRP024V060W1BA 

 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for DRP024V060W1BA

Page 1: ...ultra compact metal case is shock and vibration resistant according to IEC60068 2 The 60 watts DIN Rail power supply provides overvoltage overload and thermal protection Due to the wide input voltage range from 85 to 264 VAC the Delta s CliQ II power supply is worldwide usable It also comes with multiple output terminals for fast wiring and easy installation Features Ease of wire connection to ter...

Page 2: ...ipple peak switching 20 MHz at nominal values 50mV 150mVpp Can be connected in parallel for redundancy and increased capacity YES with ORing Diode or Redundancy module Surge voltage protection against internal surge voltages YES Certification Standards Electrical equipment of machines IEC60204 1 overvoltage category III Safety transformers for switched mode power supply units Electrical safety of ...

Page 3: ...EC and low voltage directive 73 23 EEC EMC electromagnetic compatibility DINRAIL 1AC 24V DC 2 5A EOE11010248 Immunity to interference according to EN 61000 6 2 EN 61000 4 2 1 Housing Discharge of static electricity ESD Contact discharge Air Discharge LEVEL 4 8 KV 15 KV EN 61000 4 3 1 Housing Radiate Field Immunity Frequency Field intensity LEVEL 3 80MHz 1GHz 10V M with 1kHz tone 80 modulation EN 6...

Page 4: ... XX XX Product Type DR DinRail XX X XXXX XXXX X XX X Model P Power Supply XX X XXXX XXXX X XX XXXX Voltage 024V 24 Voltage XX X XXXX XXXX X XX XXXX Watt 060W 60 Watt 120W 120 Watt 240W 240 Watt 480W 480 Watt XX X XXXX XXXX X XX X Phase 1 1 Phase 3 3 Phase XX X XXXX XXXX X XX XX Variation Eg Customer material Etc BA Delta standard metal case ...

Page 5: ...Switch Mode Power Supply DRP024V060W1BA 5 13 Rev 00 1 10 2011 Block Diagrams Connections Block Diagram of Power Supply DRP024V060W1BA ...

Page 6: ...l go into over temperature protection by switching off i e device will go into bouncing mode It will recover when ambient temperature drops to 50 C or output capacity is reduced as recommended in the graph 3 If the device has to be mounted in any other direction please contact your service provider for more details 4 In order for the device to function in the manner intended it is also necessary t...

Page 7: ...0W1BA 7 13 Rev 00 1 10 2011 Mechanical drawing Device description Fig 1 1 Input terminal block connector 2 Output terminal block connector 3 DC voltage adjustment potentiometer 4 DC OK control LED green 5 Universal mounting rail system ...

Page 8: ...ally when the overload condition is removed Short Circuit Protection The Power Supply has a short circuit protection which is in line with the overload protection and activates whenever there is a short across the output voltage It will go into bouncing mode and recovers automatically when the fault is removed Over Temperature Protection The Power Supply has an over temperature protection OTP This...

Page 9: ...e fault is removed Inrush Current Start up Time Output Hold up Time Inrush Current Inrush current is the first surge current seen on the input side when AC input is applied to the Power Supply It is the first pulse captured See below for the Inrush current in a typical Power Supply Start up Time Start up time is measured from the point AC input is applied to the point output voltage reaches within...

Page 10: ...p time characteristic of a power supply The hold time is measured until the output voltage remains in regulation hence it measured until the output voltage reaches minimum regulation 2 of its set value Output Voltage Adjust The 24VDC connection is made using the and screw connections At the time of delivery the output voltage is 24VDC The output voltage can be set from 24 to 28VDC on the potentiom...

Page 11: ...apable of delivering 3 secs of Surge load about 150 of IO max the o p voltage can be out of regulation limits of 5 Dynamic Load The Power Supply is capable of dynamic output voltage load change from 10 to 90 within 5 of regulation limits and from 0 to 100 within 10 of regulation limits See picture below on the dynamic behavior of the Power Supply ...

Page 12: ...SU1 and A2 is connected to the Ve of PSU2 and both output ground are shorted together The output of PSU1 and PSU2 is drawn from the Cathode K of the twin diode making the Power Supply work in Redundant Parallel operation Redundant Operation When 2 Power Supplies are connected in parallel the Power Supply with the higher output voltage will take the maximum load while the other will operate in stan...

Page 13: ...the Power Supply to the end system load and measure the output voltages from A1 to Ground i e VA1 to Ground of PSU1 and VA2 to Ground of PSU2 Ensure that the output voltages are the same even after the 2 Power Supplies are connected to load If not adjust them with the VR available on the front panel A tolerance of 25mV would be acceptable Note 1 If the output voltage of any Power Supply is higher ...