DeviceNet Slave Station Communication Module

 

Instruction Sheet 

 

 

Warning 

 

Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent 
damages on the device or injuries to staff. 

 

Switch off the power before wiring. 

 

This instruction sheet only provides introductory information on electrical specification, functions, wiring, 
trouble-shooting and peripherals for DNA02. Details of DeviceNet protocol are not included in this sheet. For more 
information on DeviceNet Protocol, please refer to relevant reference or literatures. 

 

DNA02 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborn dust, humidity, 
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or 
specific tools are required to open the enclosure) in case danger and damage on the device may occur. 

 

DNA02 is to be used for controlling the operating machine and equipment. In order not to damage it, only qualified 
professional staff familiar with the structure and operation of it can install, operate, wire and maintain it. 

 

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power and DO NOT touch any terminal when the power is switched on. Make 
sure the ground terminal 

  is correctly grounded in order to prevent electromagnetic interference. 

 

 

Introduction

 

1.1 Model Explanation 

Thank you for choosing Delta DNA02 DeviceNet communication module. DNA02 can be applied to the connection 
between DeviceNet and Delta’s programmable logic controllers, AC motor drives, servo drives, temperature 
controllers and DOP human machine interfaces. In addition, DNA02 offers custom function, which can be applied 
to the connection between DeviceNet and self-defined equipments with Modbus protocol. 

 

Features 

 Supports Group 2 only servers 
 Supports explicit connection in the pre-defined 

master/slave connection group 

 

 

 Supports polling 
 Supports EDS files in DeviceNet network configuration 

tools 

Nameplate explanation 
 
 

MODEL :
POWER INPUT : 

DNA02000T7020022

VX.XX

DNA02
24Vdc  2.0W

DELTA ELECTRONICS, INC                                   MADE IN XXXXXXX

Model name
Power input spec.

Barcode & serial No.
Version

 

Serial No. explanation 

 

Production No.
Production week
Production year (2007)

Production plant (W: Wujiang  T: Taoyuan)

Version No.

Model name

 

 

1.2  Product Profile and Outline 

1

2

3

4

5

6
7

8

9

10

 

 

Unit: mm

 

 

1

 

Communication port 

2

 

Address setup rotary switch 

3

 

Function setup DIP switch 

4

 

Instruction on function   
setup switch 

5

 

SP (Scan Port) indicator 

6

 

MS (Module Status) indicator 

7

 

NS (Network Status) indicator 

8

 

DeviceNet connector 

9

 

DIN rail 

 

DIN rail clip 

 

 

Specifications

 

DeviceNet Connector 

Type 

Removable connector (5.08mm) 

Transmission method 

CAN 

Transmission cable 

2 communication cables, 2 power cables and 1 shielded cable 

Electrical isolation 

500V DC 

Communication 

Message type 

I/O polling; explicit 

Series transmission speed 

125 Kbps; 250 Kbps; 500 Kbps 

Equipment type 

12 

Company ID 

799 (Delta Electronics, Inc.) 

Electrical Specifications 

Voltage: 11 ~ 25V DC (offered by the power cable in the network) 

DeviceNet 

Current: 28mA (typical), 125mA impulse current (24V DC) 

 
Environment 

Standards 

IEC 61131-2, UL508 

Storage/Operation 

Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity); pollution degree 2 

Shock/Vibration 
immunity 

International Standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 
(TEST Ea) 

Interference immunity 

RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 1.4GHz ~ 2GHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 

Certificates CE, 

UL 

 

 

Components

 

3.1 DeviceNet 

Connector 

To connect with DeviceNet network, use the connector enclosed with DNA02 or any connectors you can buy in the 
store for wiring.   

 

PIN 

Signal 

Color 

Description 

 

1 V-  Black 

VDC 

2 CAN_L  Blue  Signal- 
3 SHIELD 

- shielded 

cable 

4 CAN_H  White   
5 V+  Red 24 

VDC 

 

1

2

3

4

5

 

 

3.2  Address Setup Rotary Switch 

The two rotary address setup switches set up the node addresses on 
DeviceNet network in decimal form. Setup range: 00 ~ 63 (64 ~99 are 
forbidden)

 

5

0

x10

1

0

x10

5

0

 

 

Example:

 

If you need to set the node address of DNA02 as 26, simply switch the corresponding rotary switch of X10

to “2” 

and the corresponding rotary switch of X10

0

 to “6”. 

 

Address Setting 

Description 

0…63 

Valid DeviceNet 

 communication address 

Others 

Invalid DeviceNet   

communication address 

 

 

The changed values on switches are only valid 

when DNA02 is re-powered. When DNA02 is 
operating, changing the set value of 
communication address is invalid.

 

3.3  Function Setup DIP Switch 

The DIP switch is to be used on the equipment connected to DNA02, 
the selection of communication ports and setting up the 
communication speed of DNA02 and the master station in DeviceNet.

 

1 2 3 4 5 6 7 8

SW3

DIP

ON

 

3.3.1  Selecting Equipment Connected to DNA02 

 

PIN 1 

PIN 2 

PIN 3 

Equipment 

ON 

OFF 

OFF 

AC motor drive 

OFF 

ON 

OFF 

Programmable logic controller 

ON ON OFF 

Temperature 

controller 

OFF 

OFF 

ON 

Servo drive 

ON 

OFF 

ON 

Human machine interface 

OFF 

ON 

ON 

Custom equipment 

ON 

ON 

ON 

For internal system use 

 
Example: 

If the equipment connected to DNA02 is Delta servo drive, you only need to switch PIN 3 to “On”, PIN 1 and PIN 2 
to “OFF” and re-power it. 

 

The changed setting of the switch is only valid when DNA02 is re-powered. When DNA02 is operating, changing the 

setting of DIP switch is invalid.

 

 

3.3.2  Selecting DNA02 Communication Mode 

 

PIN 4 

PIN 5 

Communication Mode 

OFF OFF 

RS-485 

ON ON 

RS-232 

ON OFF 

OFF ON 

Incorrect setting 

The changed setting of communication mode is only valid when DNA02 is re-powered. When DNA02 is operating, 

changing the setting of communication mode is invalid.

 

 
3.3.3  Setting up Baud Rate 

 

PIN 6 

PIN 7 

PIN 8 

Slave Device Baud Rate 

OFF OFF 

125K 

bps 

ON OFF 

250K 

bps 

OFF ON 

500K 

bps 

ON ON 

Reserved 

Auto baud rate detection 

 

The changed setting of the baud rate of DeviceNet is only valid when DNA02 is re-powered. When DNA02 is operating, 

changing the communication speed is invalid.

 

 

3.4 Communication 

Ports 

on 

DNA02 

The communication ports on DNA02 are used for connection with 
equipments (Delta PLC, Delta AC motor drive, Delta temperature 
controller, Delta servo drive, Delta human machine interface and 
custom equipments) 

PORT1

PORT2

 

3.4.1 PORT1 
 

PORT1 PIN definition 

 

PORT1 Sketch 

Terminal No. 

Description 

1 N.C. 

GND 

3 DATA- 

DATA+ 

5 N.C. 

1

2

3

4

5

6

PORT1

 

N.C. 

 

PORT1 supports RS-485 communication mode only.

 

 

3.4.2 PORT2 

 

PORT2 Sketch 

Terminal No. 

RS-232 

RS-485 

1 N.C. 

N.C. 

RXD 

N.C. 

3 TXD 

DATA- 

N.C. 

N.C. 

5 GND 

GND 

N.C. 

N.C. 

7 N.C. 

N.C. 

N.C. 

DATA+ 

1

6

2

7

3
8

4

9

5

DB9  male

 

9 N.C. 

N.C. 

 

PORT2 supports RS-232 and RS-485 communication mode only

 

 

Connectors for DNA02 and the Equipments

 

See below communication wiring when DNA02 is connected to an equipment through PORT1. 

 

When connected to Delta AC motor drive 

When connected to Delta PLC 

RS-485 communication mode 

(Using standard cable with RJ-11connectors at its two 

ends is suggested) 

RS-485 communication mode 

DNA02 

RJ-11 (RS-485) 

VFD series AC motor 

drive 

RJ-11(RS-485) 

DNA02 

RJ-11 (RS-485) 

DVP-PLC 

RS-485 wiring terminal 

1

2

3

4

5

6

RJ-11

RJ-11

DATA-

DATA+

DATA-
DATA+

(3)

(4)

(3)
(4)

1

2

3

4

5

6

 

DATA-

DATA+

DATA-
DATA+

(3)
(4)

1

2

3

4

5

6

RJ-11

+

_

PLC  COM2

 

 

When connected to Delta temperature controller 

When connected to Delta servo drive 

RS-485 communication mode 

RS-485 communication mode 

DNA02 

RJ-11 (RS-485) 

Temperature controller 

RS-485 wiring terminal 

DNA02 

RJ-11 (RS-485) 

Servo drive 

CN3 connector (RS-485) 

DATA-

DATA+

DATA-
DATA+

(3)

(4)

1

2

3

4

5

6

RJ-11

DATA+

RS-485

DATA-

 

DATA+

DATA-

(4)

(3)

1

2

3

4

5

6

RJ-11

CN3 connector

1 3 5

2 4 6

(3) 485+ 

(5) 485+

(4) 485-

(6) 485-

 

 