DeviceNet Slave Communication Card CMC-DN01
DVP-PLC Operation Manual
8
Parameter
Definition
DeviceNet master
Length of output data
Number of the AC motor drive parameters controlled by
DeviceNet master
Data_in[1]
The 1
st
AC motor drive parameter sent back to
DeviceNet master
Data_in[2]
The 2
nd
AC motor drive parameter sent back to
DeviceNet master
Data_in[3]
The 3
rd
AC motor drive parameter sent back to
DeviceNet master
… …
Data_in[32]
The 32
nd
AC motor drive parameter sent back to
DeviceNet master
Data_out[1]
The 1
st
AC motor drive parameter controlled by
DeviceNet master
Data_out[2]
The 2
nd
AC motor drive parameter controlled by
DeviceNet master
Data_out[3]
The 3
rd
AC motor drive parameter controlled by
DeviceNet master
… …
Data_out[32]
The 32
nd
AC motor drive parameter controlled by
DeviceNet master
Table 4.2.1
Example: Suppose the AC motor drive parameters sent back to the DeviceNet master are H2101 and
H2103, and the AC motor drive parameters controlled by the DeviceNet master are H2000 and H2001, we
then set the “Length of input data” parameter to “2”, “Length of output data” to “2”, “Data_in[1]” to “8449”
(converted from the hex 2101), “Data_in[2]” to “8451” (converted from the hex 2103), “Data_out[1]” to “8192”
(converted from the hex 2000” and “Data_out[2]” to “8193” (converted from the hex 2001).
After the setup is completed, download the new mappings to CMC-DN01.
Figure 4.2.1: Input data mapping
Figure 4.2.2: Output data mapping
4.3 Establishing I/O Connection
Open the “Scanner Module configuration…” page (Figure 4.3.1), and we can see that the AC motor