background image

NOTE

 

 

Before regulating the power voltage, make 
sure the power has been turned off. Please set 
power voltage as the possible highest voltage 
for unstable power system. Take 380VAC 
power system for example. If the voltage may 
be up to 410Vac, 415VAC should be regulated.

 

For DELTA’s AC motor drive VFD Series, 
please set parameter (Over Voltage Stall 
Prevention) as “close” to disable over-voltage 
stall prevention, to ensure stable deceleration 
characteristic. For VFDB-5055, the jumper 
can only be put on the position as shown in the 
following figure. Do NOT remove the jumper 
to other place.

 

 

2007-07-19

5011628404-BM04

 

VFDB Series

 

Braking Modules Instruction Sheet

 

X

Preface

 

Thank you for choosing DELTA’s braking module. VFDB braking units are applied to absorb the motor regeneration energy when the 
three-phase induction motor stops by deceleration. With VFDB braking unit, the regeneration energy will be dissipated in dedicated 
braking resistors. To prevent mechanical or human injury, please refer to this instruction sheet before wiring. VFDB braking units are 
suitable for DELTA AC Motor Drives VFD Series 230V/460V/575V. VFDB braking units need to be used in conjunction with BR series 
braking resistors to provide the optimum braking characteristics. VFDB braking units (2015, 2022, 4030, 4045 and 5055) are approved 
by Underwriters Laboratories, Inc. (UL) and Canadian Underwriters Laboratories (cUL). The content of this instruction sheet may be 
revised without prior notice. Please consult our distributors or download the most updated version at 
http://www.delta.com.tw/industrialautomation.

 

Y

Specifications

 

VFDB Braking Units

 

Braking Resistors

 

Specification

 

230V Series 

460V Series 

575V Series 

 

Model no.

 

Specification

 

Model VFDB- 

2015 

2022 

4030 

4045 

5055 

 

BR1K5W005 

1500W 5.0

Ω

 

Max. Motor Capacity (KW) 

15 

22 

30 

45 

55 

 

BR1K2W6P8 

1200W 6.8

Ω

 

Max. Discharge Current 

(A) 10%ED 

40 60  40  60 

60 

 

BR1K2W008 

1200W 8.0

Ω

 

Continuous Discharge 

Current (A) 

15 20  15  18 

20 

 

BR1K5W040 

1500W 40

Ω

 

O

ut

put

 R

at

ing 

Braking Start-up Voltage 

(DC) 

330/345/360/380/400/

415

±

3V 

660/690/720/760/800/

830

±

6V 

950

±

8V 

 

BR1K0W050 

1000W 50

Ω

 

Input

 

R

at

ing 

DC Voltage 

200

400VDC 400

800VDC 

607-1000VDC 

 

BR1K0W075 

1000W 75

Ω

 

Min. Equivalent Resistor for Each 

Braking Unit 

10

Ω

 6.8

Ω

 20

Ω

 13.6

Ω

 15.8

Ω

 

 

Heat Sink Overheat 

Temperature over +95

 (203

o

F) 

 

Alarm Output 

Relay contact 5A120VAC/28VDC (RA, RB, RC) 

 

P

rot

ect

ion 

Power Charge Display 

Blackout until bus (+~-) voltage is below 50VDC 

 

Installation Location 

Indoor (no corrosive gases, metallic dust) 

 

Operating Temperature 

-10

~+50

 (14

o

F to 122

o

F) 

 

Storage Temperature 

-20

~+60

 (-4

o

F to 140

o

F) 

 

Humidity 90% 

Non-condensing 

 

Envi

ronment

 

Vibration 

9.8m/s

(1G) under 20Hz 

2m/s

(0.2G) at 20~50Hz 

 

Mechanical Configuration

 

Wall-mounted enclosed type IP50

 

 

Z

Dimensions

   

Braking Resistors

 

 

 

Z

Dimensions

 - 

VFDB Braking Units

 

[

Individual Parts and 

Function Explanation

 

80.0 [3.15]

121.0 [4.76]

18

9.

5 [7

.4

6]

20

0.

0 [7

.8

7]

130.0 [5.12]

R3.3 [R0.13]

ACT.
YELLOW

CHARGE
GREEN

ERR.
RED

 

Power Input Circuit

+(P) -(N)

Braking Resistor

B1 B2

SLAVE  Circuit

 Fault Circuit

Jumper for input 
voltage setting

Terminal Wire Gauge

 

Circuit 

Terminal Mark 

Wire Gauge AWG (mm

2

Screw 

Torque 

Power Input Circuit 

+(P), -(N) 

10~12AWG (3.5~5.5mm

2

M4 

18 kgf-cm (15.6 in-lbf) 

Braking Resistor 

B1, B2 

10~12AWG (3.5~5.5mm

2

M4 

18 kgf-cm (15.6 in-lbf) 

Output M1, 

M2 

SLAVE Circuit 

Input S1, 

S2 

20~18AWG (0.25~0.75mm

2

)

 

(with shielded wires)

 

M2 

4 kgf-cm (3 in-lbf) 

Fault Circuit 

RA, RB, RC 

20~18AWG (0.25~0.75mm

2

)

 

M2 

4 kgf-cm (3 in-lbf) 

\

Basic Wiring Diagram

 

Operation Explanation:

 

1. For safety consideration, install an overload relay between the braking unit and the braking resistor. In 

conjunction with the magnetic contactor (MC) prior to the drive, it can perform complete protection against abnormality.

 

2. The purpose of installing the thermal overload relay is to protect the braking resistor from damage due to frequent braking, or due to 

braking unit keeping operating resulted from unusual high input voltage. Under such circumstance, just turn off the power to prevent 
damaging the braking resistor. 

3. Please refer to the specification of the thermal overload relay. 
4. The alarm output terminals (RC, RA, RB) of the braking unit will be activated when the temperature of the heat sink exceeds 95

o

C. It 

means that the temperature of the installation environment may exceed 50

o

C, or the braking %ED may exceed 10%ED. With this kind 

of alarm, please install a fan to force air-cooling or reduce the environment temperature. If the condition not due to the temperature, 
the control circuit or the temperature sensor may have been damaged. At this time, please send the braking unit back to the 
manufacturer or agency for repair.

 

R/L1
S/L2

T/L3

NFB

MC

 VFD

Series

VFDB

MOTOR

O.L.

U/T1

V/T2

W/T3

+ P

- N

( )

( )

B1

B2

RA

RC

E.F

DCM

SA

R/L1
S/L2

T/L3

MC

IM

BR

O.L.

Thermal
Overload

Relay or
temperature

switch

Surge

Absorber

Thermal Overload

Relay

Braking

Resistor

Braking

  Unit

+ P

- N

( )

( )

Note1: When using the AC drive with DC reactor, please refer to wiring diagram in the AC drive
            user manual for the wiring of te(P) of Braking unit. 

Note2: 

 wire terminal -(N) to the neutral point of power system.

Do NOT

Temperature
Switch

 

5. The AC Motor Drive and braking 
unit will be electrified at the same time 
while turning on the NFB (No-fuse 
breaker). For the operation/stop 
method of the motor, please refer to the 
user manual of the AC Motor Drives 
VFD Series. The braking unit will 
detect the inner DC voltage of the AC 
motor drive when it stops the motor by 
deceleration. The extra regeneration 
will be dissipated away rapidly by the 
braking resistor in the form of heat. It 
can ensure the stable deceleration 
characteristic.

 

6. Besides using thermal overload relay to be the protection system and braking resistor, temperature switch can be installed on braking 
resistor side as the protection. The temperature switch must comply with the braking resistor specification or contact your dealer. 

]

Wiring Notice

 

 

 

Do not proceed with wiring while power is applied to the circuit. 

 

 

The wiring gauge and distance must comply with the electrical code.

 

 

The +(P), -(N) terminals of the AC motor drive (VFD Series), connected to the braking unit (VFDB), must be confirmed 
for correct polarity lest the drive and the braking unit be damaged when power on.

 

 

When the braking unit performs braking, the wires connected to +(P), -(N), B1 and B2 would generate a powerful 
electromagnetic field for a moment due to high current passing through. These wires should be wired separately from 
other low voltage control circuits lest they make interference or mis-operation.

 

 

Wiring distance

 

VFD series

15~55kW

230/460/
575V

Max 10M

Max 5M

BR

VFDB
2015

2022
4030

4045

5055

AC Motor Drive

Braking Unit

Braking Resistor

 

 

To prevent personal injury, do not connect/disconnect wires or 
regulate the setting of the braking unit while power on. Do not touch 
the terminals of related wiring and any component on PCB lest users 
be damaged by extreme dangerous DC high voltage.

 

 

Inflammable solids, gases or liquids must be avoided at the 
location where the braking resistor is installed. The braking 
resistor had better be installed in individual metallic box with 
forced air-cooling.

 

 

Connect the ground terminal to the Earth Ground. The ground 
lead must be at least the same gauge wire as leads +(P), -(N).

 

Please install the braking resistor with forced air-cooling or 
the equivalent when frequent deceleration braking is 
performed (over 10%ED).

 

 

The ring terminals are suggested to be used for main circuit 
wiring. Make sure the terminals are fastened before power on.

^

Definition for Braking Usage ED%

 

100%

T0

T1

Braking Time

Cycle Time

ED% = T1/T0x100(%)

 

Explanation: 

The definition of the barking usage ED(%) is for assurance of 

enough time for the braking unit and braking resistor to dissipate away heat 
generated by braking. When the braking resistor heats up, the resistance would 
increase with temperature, and braking torque would decrease accordingly.

 

_

The Voltage Settings

 

1. 

Regulation of power voltage: the power source of the braking unit is DC voltage from +(P), -(N) terminals of the AC motor drive. It is 
very important to set the power voltage of the braking unit based on the input power of the AC motor drive before operation. The setting 
has a great influence on the potential of the operation voltage for the braking unit. Please refer to the table below.

 

Table 1: The Selection of Power Voltage and Operation Potential of PN DC Voltage

 

230V Model 

AC Power 

Voltage 

Braking Start-up voltage 

DC Bus (+(P), -(N)) Voltage

460V Model 

AC Power 

Voltage 

Braking Start-up voltage 

DC Bus (+(P), -(N)) Voltage

575V Model 

AC Power 

Voltage 

Braking Start-up voltage 

DC Bus (+(P), -(N)) Voltage

190Vac 

330Vdc 

380Vac 

660Vdc 

575Vac 

950Vdc 

200Vac 

345Vdc 

400Vac 

690Vdc 

210Vac 

360Vdc 

415Vac 

720Vdc 

220Vac 

380Vdc 

440Vac 

760Vdc 

230Vac 

400Vdc 

460Vac 

800Vdc 

240Vac 

415Vdc 

480Vac 

830Vdc 

NOTE: Input Power With Tolerance 

±

10%

 

Input voltage setting for VFDB-2015/2022/4030/4045

 

Input voltage setting for VFDB-5055

 

For VFDB-4030/4045
Factory setting: 460V

For VFDB-2015/2022
Factory setting: 230V

480V

460V
440V
415V
400V

380V

240V

230V
220V
210V
200V

190V

Input Voltage Setting

CHARGE

Power lamp

ACT

Braking lamp

ERR

Fault lamp

 

For VFDB-5055 Series
Factory setting: 575V

------
575V
------
------
------
------

Input Voltage Setting

CHARGE

Power lamp

ACT

Braking lamp

ERR

Fault lamp

2.  MASTER/SLAVE setting: The MASTER/SLAVE jumper is set “MASTER” as factory setting. The “SLAVE” setting is applied to two 

or more braking units in parallel, making these braking units be enabled/disabled synchronously. Then the power dissipation of each unit 
will be equivalent so that they can perform the braking function completely. 

The position of the jumper

 

The SLAVE braking application of three braking units is 
shown as the above diagram. After wiring, the jumper of 
first unit shall be set as “MASTER” and that of others must 
be set as “SLAVE” to complete the system installation.

 

+ P

- N

( )         

( )

  VFD 

Series

M1

M2

MASTER

B1       B2

O.L.

M1

M2

B1       B2

O.L.

S1

S2

B1       B2

O.L.

S1

S2

SLAVE

SLAVE

BR

BR

BR

+ P

- N

( )         

( )

+ P

- N

( )         

( )

+ P

- N

( )         

( )

 

------

575V

------

------
------

------

240V

230V

220V

210V
200V

190V

MASTER/SLAVE

Setting Jumper

M1: 
M2: 
S1: 
S2: 

SLAVE output 
SLAVE output signal -

SLAVE input 
SLAVE input signal -

NOTE: Please use shielded wires
             while wiring.

Slave 
output/input

Terminal

Alarm output terminals

M

2
M

1
S

2
S

1

RC

RB

RA

MASTER

SLAVE

CHARGE

Power lamp

ACT

Braking lamp

ERR

Fault lamp

480V

460V

440V

415V
400V

380V

 

`

All Braking Resistors & Braking Units Use in the AC Drives

 

Applicable 

Motor

 

V

olta

ge

 

HP 

kW 

Full- load 

Torque

 

kg-M 

Resistor Value 

Spec for Each 

AC Motor Drive

 

Braking Unit 

Model VFDB 

No. of Units 

Used

 

Braking Resistors 

Model and No. of Units 

Used

 

Braking 

Torque

10%ED

Min. 

Equivalent 

Resistor Value 

for Each AC 
Motor Drive

Typical 

Thermal 

Overload 

Relay Value

20 

15 

8.248 

3000W 10Ω 

2015 

BR1K5W005 

2

125 

10Ω 

30 

25 

18.5 

10.281 

4800W 8Ω 

2022 

BR1K2W008 

4

125 

8Ω 

35 

30 

22 

12.338 

4800W 6.8Ω 

2022 

BR1K2W6P8 

4

125 

6.8Ω 

40 

40 

30 

16.497 

6000W 5Ω 

2015 

BR1K5W005 

4

125 

5Ω 

30 

230V 

 

50 

37 

20.6 

9600W 4Ω 

2015 

BR1K2W008 

8

125 

4Ω 

30 

20 

15 

8.248 

1500W 40Ω 

4030 

BR1K5W040 

1

125 

40Ω 

15 

25 

18.5 

10.281 

4800W 32Ω 

4030 

BR1K2W008 

4

125 

32Ω 

15 

30 

22 

12.338 

4800W 27.2Ω 

4030 

BR1K2W6P8 

4

125 

27.2Ω 

20 

40 

30 

16.497 

6000W 20Ω 

4030 

BR1K5W005 

4

125 

20Ω 

30 

50 

37 

20.6 

9600W 16Ω 

4045 

BR1K2W008 

8

125 

16Ω 

40 

60 

45 

24.745 

9600W 13.6Ω 

4045 

BR1K2W6P8 

8

125 

13.6Ω 

50 

75 

55 

31.11 

12000W 10Ω 

4030 

BR1K5W005 

8

125 

10Ω 

30 

460V 

 

100 

75 

42.7 

19200W 6.8Ω 

4045 

BR1K2W6P8 

16

125 

6.8Ω 

50 

20 

15 

8.248 

3000W 60Ω 

5055 

BR1K0W020 

3

125 

60Ω 

15 

25 

18.5 

10.281 

4000W 50Ω 

5055 

BR1K0W050 

4

125 

50Ω 

15 

30 

22 

12.338 

6000W 40Ω 

5055 

BR1K2W008 

5

125 

40Ω 

20 

40 

30 

16.497 

6000W 34Ω 

5055 

BR1K2W6P8 

5

125 

34Ω 

25 

50 

37 

20.6 

7500W 25Ω 

5055 

BR1K5W005 

5

125 

25Ω 

30 

60 

45 

24.745 

12000W 20Ω 

5055 

BR1K2W008 

10

125 

20Ω 

35 

75 

55 

31.11 

12000W 17Ω 

5055 

BR1K2W6P8 

10

125 

17Ω 

45 

575V 

 

100 

75 

42.7 

15000W 12.5Ω 

5055 

BR1K5W005 

10

125 

12.5Ω 

45 

a

Wiring Examples of Braking Resistors

 

NOTE: Before wiring, please notice equivalent resistors value shown in the column “Equivalent resistors specification for each braking 
unit” in the above table to prevent damage. 

 
230V 20HP 

  VFD 
Series

O.L.

B1

B2

Braking

   Unit

VFDB

2015

Thermal Overload

Relay

VFD150_23_

VFD150_23_ uses with 2PCS BR1K5W005 braking resistors in series

+ P

- N

( )

( )

Braking

Resistor

+ P

- N

( )

( )

MASTER

 

230V 25HP/30HP 

+ P

- N

( )

( )

O.L.

Braking 

Resistor

B1

B2

Braking

   Unit

VFDB

2022

Thermal Overload
Relay

VFD185_23_
VFD220_23_

1. VFD185_23_ uses with two BR sets in parallel, which 2PCS BR1K2W008 braking resistors
    in series for each BR set.
2. VFD220_23_ uses with two BR sets in parallel, which 2PCS BR1K2W6P8 braking resistors 

   in series for each BR set.

  VFD
Series

+ P

- N

( )

( )

+ P

- N

( )

( )

MASTER

 

230V 40HP 

O.L.

B1

B2

Braking
   Unit

VFDB

2015

VFD300_23_

VFD300_23_ use with two VFDB2015 braking units, and each braking unit uses with
2PCS BR1K5W005 braking resistors in series.

SLAVE

S1 S2

O.L.

Braking

Resistor

B1

B2

Braking

   Unit

VFDB

2015

Thermal Overload Relay

M1 M2

MASTER

  VFD
Series

+ P - N

( )  ( )

Thermal Overload Relay

Braking
Resistor

+ P - N

( )  ( )

+ P - N

( )  ( )

 

230V 50HP 

O.L.

B1

B2

Braking

  Unit

VFDB

2015

VFD370_23_

SLAVE

S1 S2

O.L.

Braking
Resistor

B1

B2

Braking
   Unit

VFDB

2015

Thermal Overload Relay

M1 M2

MASTER

  VFD
Series

+ P - N

( )  ( )

Thermal Overload Relay

Braking
Resistor

+ P - N

( )  ( )

+ P - N

( )  ( )

VFD370_23_ uses with two VFDB2015 braking units, and each braking unit uses with two
BR sets in parallel, which 2PCS BR1K2W008 braking resistors in series.

 

460V 20HP 

O.L.

Braking 
Resistor

B1

B2

Braking
   Unit

VFDB

4030

Thermal Overload
Relay 

VFD150_43_

VFD150_43_ uses with 

BR1K5W040 

1PCS braking 

resistor

+ P

- N

( )

( )

  VFD
Series

+ P

- N

( )

( )

MASTER

 

460V 25HP/30HP/40HP 

O.L.

Braking

  Unit

B1

B2

Braking

    Unit

VFDB

4030

Thermal Overload

Relay

VFD185_43_
VFD220_43_

VFD300_43_

1. VFD185_43_ uses with 

BR1K2W008 braking resistors in series

2. VFD220_43_ uses 

BR1K2W6P8 

3. VFD300_43_ uses 

BR1K5W005 

4PCS 

with 4PCS 

braking resistors in series

with 4PCS 

braking resistors in series

 VFD

Series

+ P

- N

( )

( )

+ P

- N

( )

( )

MASTER

 

460V 50HP/60HP 

O.L.

Braking

Resistor

B1

B2

Braking

   Unit

VFDB

4045

Thermal Overload
Relay

VFD370_43_
VFD450_43_

1. VFD370_43_ uses with two BR sets in parallel, which 4PCS BR1K2W008 
    braking resistors in series for each BR set.

VFD450_43_ uses with two BR sets in parallel, which 4PCS BR1K2W6P8 

    braking resistors in series for each BR set. 

 

2. 

  VFD
Series

+ P

- N

( )

( )

+ P

- N

( )

( )

MASTER

 

460V 75HP 

O.L.

B1

B2

Braking

  Unit

VFDB

4030

VFD550_43_

VFD550_43_ uses with two VFDB4030 braking units, and each braking unit uses with 
4PCS BR1K5W005 braking resistors in series.

SLAVE

S1 S2

O.L.

Braking Resistor

B1

B2

Braking
   Unit

VFDB

4030

Thermal Overload Relay

M1 M2

MASTER

  VFD
Series

+ P - N

( )  ( )

Thermal Overload Relay

Braking Resistor

+ P - N

( )  ( )

+ P - N

( )  ( )

 

460V 100HP 

O.L.

B1

B2

Braking

   Unit

VFDB

4045

VFD750_43_

SLAVE

S1 S2

O.L.

Braking
Resistor

B1

B2

Braking
   Unit

VFDB

4045

Thermal Overload Relay

M1 M2

MASTER

  VFD
Series

+ P - N

( )  ( )

Thermal Overload Relay

Braking

Resistor

+ P - N

( )  ( )

+ P - N

( )  ( )

VFD750_43_ uses with two VFDB4045 braking units, and each braking unit uses with two
BR sets in parallel, which 4PCS BR1K2W6P8 braking resistors in series.

 

575V 20HP 

VFD150_53_ uses with 3PCS BR1K0W020 braking resistors in series

O.L.

Braking

Resistor

B1

B2

Braking Unit

VFDB

5055

Thermal Overload
Relay

VFD150_53_

VFDSeries

+(P)

-(N)

+(P)

-(N)

MASTER

 

575V 25HP 

O.L.

Braking
resistor

B1

B2

Braking

    Unit

VFDB

5055

Thermal Overload
Relay

VFD185_53_

VFD185_53_ uses with 5

BR1K0W050 braking resistors in series

PCS 

  VFD
Series

+ P

- N

( )

( )

+ P

- N

( )

( )

MASTER

 

575V 30HP/40HP/50HP 

1. VFD220_53_ uses with 5PCS BR1K2W008 braking resistors in series
2. VFD300_53_ 
3. 

uses with 5PCS BR1K2W6P8 braking resistors in series

VFD370_53_ uses with 5PCS BR1K5W005 braking resistors in series

O.L.

Braking
Resistor

B1

B2

Braking Unit

VFDB

5055

Thermal Overload
Relay

VFD220_53_
VFD300_53_
VFD370_53_

VFDSeries

+(P)

-(N)

+(P)

-(N)

MASTER

 

575V 60HP/75HP 

1. VFD450_53_ uses with two BR sets in parallel, which 5PCS BR1K2W008 braking resistors 
    in series for each BR set
2. VFD550_53_ uses with two BR sets in parallel, which 5PCS BR1K2W6P8 braking resistors

   in series for each BR set

O.L.

Braking

Resistor

B1

B2

Braking Unit

VFDB

5055

Thermal Overload

Relay

VFD450_53_
VFD550_53_

VFDSeries

+(P)

-(N)

+(P)

-(N)

MASTER

 

575V 100HP 

VFD750_53_

B1

B2

VFDB

5055

M1 M2

MASTER

VFD750_53_uses with two VFDB5055 braking units, and each braking unit uses with 
5PCS BR1K5W005 braking resistors in series.

VFD
Series

+(P) -(N)

+(P) -(N)

O.L.

Thermal Overload
Relay

Thermal Overload

Relay

Braking

Resistor

Braking Unit

Braking

Resistor

B1

B2

VFDB

5055

SLAVE

S1 S2

+(P) -(N)

O.L.

Braking Unit

 

Reviews: