DVP02DA-S
DVP02DA-S
Analog Output Module
Instruction Sheet
1
WARNING
Please carefully read this instruction thoroughly prior to use the DVP02DA-S.
The DC input power must be
OFF
before any maintenance.
This is an OPEN-TYPE built-in DVP02DA-S, and the DVP02DA-S is certified to meet the safety
requirements of IEC 61131-2 (UL 508) when installed in the enclosure to prevent high
temperature, high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or
metallic particles. Also, it is equipped with protective methods such as some special tool or key
to open the enclosure, so as to avoid the hazard to users or any damage to the DVP02DA-S.
Do not connect the AC power to any of the input/output terminals, or it may the DVP02DA-S.
Make sure that all the wiring is well conducted prior to power On.
Do not touch the internal circuit for at least 1 minute after the power is Off.
Make sure that DVP02DA-S is properly grounded
, to avoid any electromagnetic noise.
2
INTRODUCTION
2.1 Model Explanation and Peripherals
Thank you for choosing DELTA DVP PLC Series. The analog output module of DVP02DA-S series
can read/write the data of analog output module by using commands FROM / TO via DVP-PLC
SS/SA/SX Series MPU program. The analog output module receives 2 group 12-bit digital data
from PLC MPU and converts it into 2 points analog output signal (voltage or current). There are 49
CR (Control Register) in each module and there are 16 bits in each register.
The software version of DVP02DA-S analog output module can be updated via RS-485
communication. Power unit and module are separate. Size is small and easy to install.
Users can select output either voltage or current via wiring. Voltage output range is 0V ~ +10V DC
(resolution is 2.5 mV). Current output range is 0mA ~ 20mA (resolution is 5 µA).
Nameplate Explanation
02DA-S0T3250003
VX.XX
20.4VDC ~ 28.8VDC
MADE IN XXXXX X
P L C m o d e l
2.5 mV or 5 A
0V ~ + 10V or 0mA ~ +20mA
Input power Supply Spec.
Analog Input /Output Module Spec.
Barcode, series and version
Model Explanation
Serial Number
Model
S: for SS series MPU
P: for EP series MPU
H: for EH series MPU
XA: Analog input/output mixed module
Product Series
Input + Output points
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors (PT-100)
TC: Thermocouple sensors (Type J/K)
Production series
Production week
Production year (2004)
Production place (Taoyuan)
Serial number of version
Production Model
RT: Resistor Thermocouple
HC: Input module of high-speed counter
PU: single axis positioning unit
2.2 Product Profile and Outline
90.00
4.00
3.00
25.20
1
2
3
4
60.00
5
6
7
8
9
3
10
●
FG
V+
I+
COM
C
H
1
FG
V+
I+
COM
C
H
2
11
12
13
3.4
90.00
60.00
3.00
14
Unit:mm
1. Status indicator (Power, RUN and ERROR)
8. Expansion port
2. Model name
9. Expansion unit clip
3. DIN rail clip
10. DIN rail (35mm)
4. I/O terminals
11. RS-485 Communication port
5. I/O point indicator
12. Mounting rail of the expansion unit
6. Mounting hole of the expansion unit
13. DC Power input
7. Nameplate
14. Expansion port
2.3 External
wiring
Voltage output
0V ~ 10V
V+
*
2
FG
COM
V+
FG
I+
CH1
CH2
24+
24-
AG
+15V
-15V
DC/DC
converter
*
3
System
Grounding
Class 3 Grounding
(100 or less)
Ω
DC24V
I+
Current output
0mA~20mA
COM
CH1
CH2
Isolation wire 1
*
Isolation wire 1
*
AC drive, recorder,
scale valve...
AC drive, recorder,
scale valve...
terminal of
power module
Note 1: Please isolate analog output and other
power wiring.
Note 2: If noise interferes from loaded input wiring
terminal is significant, please connect a
capacitor with 0.1~0.47µF 25V for noise
filtering.
Note 3: Please connect
power module
terminal and
analog output module
terminal to system earth point and make
system earth point be grounded or
connects to machine cover.
Warning: DO NOT wire to the No function terminal
2.4 Terminal of analog module layout
DVP04AD-S
DVP02DA-S
DVP04DA-S
DVP04PT-S
DVP04TC-S
DVP06XA-S
DVP08RT-S
V+
I+
COM
FG
V+
I+
COM
FG
I+
COM
FG
V+
I+
COM
FG
V+
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
SLD
L+
L-
L+
L-
L+
L-
SLD
SLD
SLD
V+
I+
COM
V+
I+
COM
I+
COM
V+
I+
COM
V+
V+
I+
COM
V+
I+
COM
L1+
L1-
FG
L3+
L3-
L2-
L2+
L4-
L4+
L51
L5-
FG
L7+
L7-
L6-
L6+
L8-
L8+
3
STANDARD SPECIFICATIONS
3.1 Specifications
Digital/Analog (2D/A) Module
Voltage Output
Current Output
Power Supply Voltage
24 VDC (20.4VDC~28.8VDC) (–15%~+20%)
Analog Input Channel
2 channels / each module
Analog Output Range
0~10V 0~20mA
Digital Data Range
0~4000 0~4000
Resolution
12 bits (1
LSB
=2.5 mV)
12 bits (1
LSB
=5 µA)
Output Impedance
0.5
Ω
or lower
Overall Accuracy
±
0.5% of full scale of 25
℃
(77
℉
)
±
1% of full scale during 0~55
℃
(32~131
℉
)
Response Time
3 ms
×
channels
Max. Output Current
20mA (1K
Ω
~2M
Ω
)
-
Tolerance Carried Impedance
-
0
〜
500
Ω
Digital Data Format
2’s complementary of 16-bit, 13 Significant Bits
Isolation Method
Isolation between digital area and analog area. But no isolation
among channels.
Protection
Voltage output has short circuit protection but a long period of short
circuit may cause internal wire damage and current output break.
Communication Mode (RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of 4800 /
9600 / 19200 / 38400 / 57600 / 115200. For ASCII mode, format is
7Bits, even, 1 stop bit (7 E 1), while RTU mode format is 8Bits, even,
1 stop bit (8 E 1). The RS-485 is disabled when the DVP02AD-S is
connected in series with an MPU.
Connect to DVP-PLC MPU in
Series
If DVP02DA-S modules are connected to MPU, the modules are
numbered from 0 – 7. 0 is the closest and 7 is the furthest to the
MPU. 8 modules is the max and they do not occupy any digital I/O
points of the MPU.
3.2 Other
Specification
Max. Rated Consuming Power
24 VDC (20.4VDC~28.8VDC) (–15%
〜
+20%), 3W, supply from
external power
Environment Condition and Wiring
Follow the DVP-PLC MPU
Spec of
Prevent
Static Electricity
All places between terminals and ground comply with the spec
4
CR (Control Register)
DVP-02DA Analog Output Module
Explanation
CR
No
RS-485
Parameters
Address
Latched Register
Name b15
b14
b13
b12
b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#0
H 4032
○
R Model
type
System used, data length is 8 bits (b7~b0). DVP-04AD model code=H 49
Reserved CH2
CH1
#1
H 4033
○
R/W Output mode setting
Output mode setting: factory setting is H0000.
Mode 0: output voltage mode (0V~10V).
Mode 1: output voltage mode (2V~10V).
Mode 2: output current mode (4mA~20mA).
Mode 3: output current mode (0mA~20mA).
Mode 4: none use.
#2 ~ #9
Reserved
#10
H 403C
○
R/W CH1 output value
#11
H 403D
○
R/W CH2 output value
The output setting range of channel CH1~CH2 is K0~K4000. Factory setting is K0
and unit is LSB.
#12~#21 Reserved
#22
H 4048
○
R/W To adjust OFFSET
value of CH1
#23
H 4049
○
R/W To adjust OFFSET
value of CH2
It is used to set the OFFSET value of CH1~CH2. The setting range is
K-2000~K2000. The factory setting is K0 and unit is LSB.
#24 ~ #27
Reserved
#28
H 404E
○
R/W To adjust GAIN
value of CH1
#29
H 404F
○
R/W To adjust GAIN
value of CH2
It is used to set the GAIN value of CH~CH2. The setting range is K-1600~K8000.
The factory setting is K2000 and unit is LSB.
#30
H 4050
╳
R Error status
It is the data register to save all error status. Please refer to fault code chart for detail.
#31
H 4051
○
R/W Communication
address setting
It is used to set RS-485 communication address. The setting range is from 01 to 255
and the factory setting is K1.
#32
H 4052
○
R/W Communication
Baud Rate setting
It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600,
115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1),
while RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
b0: 4800 bps (bit/sec). b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec). b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec). b5: 115200 bps (bit/sec).
b6-b13: reserved.
b14: exchange low and high byte of CRC check code (only for RTU mode)
b15: ASCII / RTU mode selection
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Reserved CH2
CH1
#33
H 4053
○
R/W Reset to factory
setting and set
characteristics
adjustable priority
Output latched setting, factory setting H0000.
Give CH1 setting for example:
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#22, CR#28).
When b1=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#22,
CR#28).
2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1
(not latched).
3. When b2 is set to 1, all settings will be reset to factory setting.
#34
H 4054
○
R Software version.
In hexadecimal to display software version. For example: H 010A means 1.0A.
#35~#48 System
used
○
means latched. ,
╳
means not latched.
R means can read data by using FROM command via RS-485.
W means can write data by using TO command via RS-485.
LSB (Least Significant Bit): 1. Voltage output: 1
LSB
=10V/8000=2.5mV. 2. Current output: 1
LSB
=20mA/4000=5µA.
Explanation:
1. The content of CR#0 is model type, user can read the data from program to check if there is
expansion module.
2. CR#1 is used to set two internal channels working mode of analog output module. Every channel
has four modes to set that can set individually. For example: if set CH1 to mode 2 (b2~b0=010),
CH2 to mode 1(b5~b3=001). It needs to set CR#1 to H000A. The factory setting of CR#1 is H0000.
3. CR#2 ~ CR#9, CR#12 ~ CR#21, CR#24 ~ CR#27 Reserved.
4.
CR #10 ~ CR#11 display CH1 and CH2 output signal. The setting range is K0~K4000. Factory
setting is K0 and unit is LSB.
5. R#22 ~ CR#23 means the value to adjust OFFSET value of CH1 and CH2. The factory setting is K0
and unit is LSB. If output value equal to 0 after calculating, the adjustable range of analog output
voltage or current is -2000~+2000.
Voltage adjustable range: -5V~+5V(-2000
LSB
~+2000
LSB
).
Current adjustable range: -10mA~+10mA (-2000
LSB
~+2000
LSB
).
6. R#28 ~ CR#29 means the value of adjust GAIN value of CH1 and CH2. The factory setting is K2000
and unit is LSB. If output value equal to 2000 after calculating, the adjustable range of analog output
voltage or current is -1600~+8000.
Voltage adjustable range: -4V~+20V(-1600
LSB
~+8000
LSB
).
Current adjustable range: -8mA ~+40mA (-1600
LSB
~+8000
LSB
).
Please be noticed that GAIN VALUE – OFFSET VALUE = +400
LSB
~+6000
LSB
(voltage or
current). When
this value within this range, the resolution of the output signal will be thin and the
value variation will be larger. When this value exceeds this range, the resolution of output signal
will be thick and the variation of value will be smaller.
7. CR#30 is the fault code. Please refer to the following chart.
Fault Description
Content b15~b8 b7
b6
b5
b4
b3
b2
b1
b0
Power Source Abnormal
K1(H1)
0 0 0 0 0 0 0 1
Analog Input Value Error
K2(H2)
0 0 0 0 0 0 1 0
Setting Mode Error
K4(H4)
0 0 0 0 0 1 0 0
Offset/Gain Error
K8(H8)
0 0 0 0 1 0 0 0
Hardware Malfunction
K16(H10)
0 0 0 1 0 0 0 0
Digital Range Error
K32(H20)
0 0 1 0 0 0 0 0
Average Times Setting Error
K64(H40)
0 1 0 0 0 0 0 0
Command Error
K128(H80)
Reserved
1 0 0 0 0 0 0 0
Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0
means normal and 1 means fault happened.