Delta Controls RTS-20 Series Installation & Application Manual Download Page 11

Delta Controls 

Document Edition 2.3

 

 

Page 11 of 13 

 

Network Topology (Only RTS-20Jxx) 

 

Room Temperature Sensors with a Service Port may be connected to a BACnet RS-485 

MS/TP network or to the LINKnet network.  Note that this does not make the RTS-20Jxx a 

MS/TP or LINKnet device, it simply adds a connection point to the network for use with 

the Service Tool. 
 

Network Communications Setup (Only RTS-20Jxx) 

The communication speed is set on the network controllers.  Refer to the 

V3.30 ORCAview 

Technical Reference Manual

 for further detail on configuring the MS/TP network or 

changing baud rates, etc. 

 

 

DCU/DSC

(System Device)

BACnet (MS/TP) - Level 3 Network (Subnet)

DAC

(Subnet

Device)

TRM

DAC

(Subnet

Device)

TRM

Level 4

Network

(LINKnet)

ƒ

 16x16 Controller

ƒ

 12x12 Controller

ƒ

 12x8 Controller

ƒ

 6x6 Controller

ƒ

 Room Controller

ƒ

 VAV/VVT Controller

ƒ

 Lighting Controller

ƒ

 BACstat I

ƒ

 BACstat II

  (with or without I/O)

ƒ

 Input Field Modules

Subnet Devices

ƒ

 DSC-1616EX [DCU]

ƒ

 DSC-1616(H/E)

ƒ

 DSC-1212(H/E)

ƒ

 DSC-1280(H/E)

ƒ

 DSC-T305

System Devices

RS-485

NET1

NET2

NET1

NET2

RS-232

ƒ

 BACstat I

ƒ

 BACstat II

  (with No I/O)

ƒ

 BACstat II

  (with muxed I/O)

ƒ

 I/O Field Modules

LINKnet Devices

TRM

Level 4

Network

(LINKnet)

DFM

DFM

TRM

LINKnet Notes:

1.  Ensure you use the recommended
     balanced cable.
2.  Ensure the cable is installed as a
     daisy-chain from one device to the
     next. (1000' or 300m maximum).
3.  Ensure you install MS/TP terminator
     boards when you have more than 1 or
     2 devices.
4.  Depending on the controller, up to 12
     devices are supported on a LINKnet
     network, with limitations on how many
     of these may have I/O.  (Refer to
     the Technical Reference Manual.)

ORCAview

OWS

DFM

Ethernet Note:

If the DCU or DSC has Ethernet capability, it may exist on an
Ethernet network with other controllers in the same building, on which
the ORCAview OWS could reside as well (instead of PTP).

PTP

MS/TP Notes:

1.  Ensure you use the recommended balanced cable.
2.  Ensure the cable is installed as a daisy-chain from one device to
     the next (4,000' or 1220m maximum).
3.  Ensure you install an MS/TP terminator board (TRM-768) on each
     end of each MS/TP network.
4.  The maximum nodes per MS/TP network is 50 without a repeater,
     or up to 99 with at least one repeater (RPT-768).

Network Diagram

 (with V3.22 Firmware)

RTS

RTS

RTS

* Note

: The RTS is NOT a

network sensor it is connected
to the network to provide
Service Port Access

Summary of Contents for RTS-20 Series

Page 1: ...RJ 11 service port and an Occupancy Override Push button and Setpoint Adjustment Thumb Wheel Room Temperature Sensors are ideal for providing remote temperature sensing occupancy override for room sch...

Page 2: ...rride Pushbutton 9 9 9 20k Setpoint Adjust Dial 9 9 9 Accessories for the RTS 20Jxx TRM 768 Delta Network Terminator for MS TP RPT 768 Delta Network Repeater for MS TP Package Contents Room Temperatur...

Page 3: ...ional RJ 11 Service Port jack 6 wire Wiring 2 for optional BACnet MS TP service port connection 100 120 ohm balanced TSP cable 16 PF FT or lower 2 for optional service port power 2 for temperature 1 e...

Page 4: ...ing section for more details The second is a 20k potentiometer for Setpoint adjustment that must also be programmed and set by Jumper as required See Setpoint Scaling for details Setpoint Scaling for...

Page 5: ...al end of scale reading Note Do NOT connect the Override output to the controller unless you have the jumper in the OVERRIDE position Doing so may skew the actual resistance read in the Thermistor or...

Page 6: ...connections for each input connect the Common from the RTS 20JPS to each Input ground terminal The labeling on the backplate of the RTS 20JPS is labeled TMP for the 10k Thermistor SET for the 20k Setp...

Page 7: ...optional 24VAC with RTS 20J and RTS20JPS Optional Push button with RTS 20JP Thermistor Connector Posts for optional Temperature Sensor Connector Posts for optional Push Button Override Connector Post...

Page 8: ...r RTS 20xxx Rev 3 0 Installation Application Guide Page 8 of 13 Document Edition 2 3 RTS 20P RTS 20S and RTS 20PS Assembled on to the BACstat II top plate RTS 20 Assembled on to the BACstat II bottom...

Page 9: ...ely Network Cabling Requirements Only RTS 20Jxx To ensure network stability and reliable communications when using the Service Port option particularly at high speeds on a BACnet RS 485 MS TP network...

Page 10: ...Room Temperature Sensor RTS 20xxx Rev 3 0 Installation Application Guide Page 10 of 13 Document Edition 2 3 For more detailed information including wiring refer to the Delta Controls Wiring Guidelines...

Page 11: ...o I O BACstat II with muxed I O I O Field Modules LINKnet Devices TRM Level 4 Network LINKnet DFM DFM TRM LINKnet Notes 1 Ensure you use the recommended balanced cable 2 Ensure the cable is installed...

Page 12: ...ton The following program is an example of how to read the temperature of the Room Temperature Sensor without the pushbutton interfering Objects created in the same panel that the RTS is connected to...

Page 13: ...y be required to de energize the equipment before servicing All terminals are acceptable for Class 2 circuit connection only CAUTION Input Class 2 Power Supplies are interconnected To Reduce the Risk...

Reviews: